What sets MCC breaker unit space requirements

Motors and motor starters Published 5 min read

Short answer

There is no generic breaker unit space to scale from a starter. The 14 by 20 inch figure applies to Size 1 and Size 2 starter units; a breaker bucket takes whatever height the MCC builder's unit schedule shows for that exact breaker catalog number. The conductors and their termination access usually decide whether that space grows, so size the cable first and get a dimensioned layout for each breaker before the MCC design freezes.

On this page
  1. What the 14 by 20 inch figure actually describes
  2. Why the ampere rating alone does not fix the space
  3. Conductors decide the real minimum
  4. Worked example: minimum conductor size behind a 225 A breaker unit
  5. What to get from the MCC builder before the layout freezes
  6. Verify the bucket before you terminate
  7. Questions asked

Breaker unit space in an MCC is not a number you can scale from a starter. The 14 by 20 inch figure applies to Size 1 and Size 2 starter units; a 100 A, 150 A or 225 A breaker takes whatever height the MCC builder's unit schedule assigns to that exact breaker catalog number in that MCC series. In practice the conductors, not the breaker, decide whether the space grows: a compact bucket that physically holds the breaker can still be unusable if the designed cable cannot form into the lugs. This article gives what sets the space, a worked conductor example, and the decision for each case.

What the 14 by 20 inch figure actually describes #

That figure is a starter footprint, not a breaker allowance. In the common North American layout it means 14 in of vertical space in the unit stack of a section 20 in wide. Structures of this style are documented at 90 in tall by 20 in wide, with a vertical wireway running alongside the units, and one builder's catalogue lists an optional 25 in wide section with a 9 in wide wireway when a unit or its cabling needs more width. Unit heights are not continuous: one arc-resistant design documents unit sizes in fixed steps of 6, 12, 18, 24, 30, 36, 42 and 48 in, covering NEMA frame sizes 1 through 6. A breaker bucket therefore occupies whichever step the builder's unit schedule assigns to its frame, and that schedule is the only source of the number.

Why the ampere rating alone does not fix the space #

The ampere rating names the trip unit; the frame sets the dimensions. Two devices with the same trip rating can ride in different frames, with different heights, depths, stab arrangements and terminal orientations, so a bucket sized for one will not necessarily accept the other. A larger frame may also be the only one that meets the short-circuit duty at the bus, and the tested rating combination can restrict which breaker may sit in a given bucket; that interaction is worked through in MCC short-circuit rating versus bucket breaker ratings. Before reserving space, fix three identifiers: the MCC series and unit configuration, the breaker catalog number and pole arrangement, and the mounting style, fixed or drawout.

Conductors decide the real minimum #

A breaker that fits its compartment can still be impossible to terminate. Feeder-class cables are stiff, need their bending radius, and must reach the lugs with the bucket door and the neighboring units in place; a layout that leaves the cable approach unplanned leaves the electrician improvising on the floor. Take the conductor size from the run, not from the breaker handle: when a long run or a tight voltage-drop budget pushes the cable up a size or two, the layout must take the actual cable, and the way feeder and branch drops stack is worked through in why total system voltage drop exceeds the feeder drop at an 800 A MCC.

Check what the terminals accept before counting on a landing point: whether one lug may take more than one conductor is governed by the NEC and by the terminal maker's own listing, set out in NEC and manufacturer requirements for multiple conductors per terminal. If the cable cannot land on the breaker itself, the fix is a suitably rated terminal strip in the cableway, agreed with the builder during design rather than discovered during construction.

Worked example: minimum conductor size behind a 225 A breaker unit #

The inputs, each from the feeder design:

  • Load current to be carried: 225 A, non-continuous. If the load is continuous, the NEC requires sizing at 125 percent of the continuous load, and the next conductor size up applies.
  • Conductor material: copper.
  • Termination and conductor temperature rating: 75 degrees C.
  • Ambient: 30 degrees C, the basis of the ampacity table; correction factors apply above that.

The rule, in words: NFPA 70, the National Electrical Code, 2023 edition, lists conductor ampacities in Table 310.16, and for terminations rated at 75 degrees C you take the conductor from the 75 degrees C column at or above the load; Article 430 carries its own sizing rules for motor branch circuits. Confirm the final selection with the authority having jurisdiction and the equipment documentation.

The arithmetic: in the 75 degrees C copper column, 3/0 AWG is listed at 200 A, which falls short of the load. The next size up, 4/0 AWG, is listed at 230 A, which meets and exceeds it. The minimum conductor is 4/0 AWG copper per phase. In aluminum the same load needs more metal: 250 kcmil is listed at 205 A, short, while 300 kcmil is listed at 230 A, adequate, so an aluminum feeder of this rating means a physically larger cable in the same compartment.

The decision: the bucket must accept and terminate three 4/0 copper conductors, one per phase, or three 300 kcmil aluminum conductors, with bending radius and lug access to match. Verify the breaker's lug conductor range in the breaker catalog; if the lugs stop below that size, move to a frame whose lug range covers the conductor or have the builder add approved terminal lugs in the cableway. Then require a dimensioned termination layout for that exact cable before the design is released.

What to get from the MCC builder before the layout freezes #

  • A dimensioned unit schedule showing the height and width assigned to each breaker catalog number, fixed and drawout.
  • The breaker's lug conductor range and terminal orientation, from the breaker catalog.
  • A termination detail showing the designed conductor size and quantity formed into the compartment, with workable access to each lug.
  • Any restrictions on adjacent units, door-mounted accessories, or the wireway the cable route crosses.

If any document does not show the selected combination, hold the layout and ask; do not substitute a dimension from a different frame, lineup or starter unit. Where a roomier unit is available and the schedule permits it, take it: it costs section inches and buys years of easier forming and service.

Verify the bucket before you terminate #

On receipt, compare the MCC and bucket labels against the approved schedule and drawings, and confirm each breaker occupies the intended space with the planned cable route and workable lug access; resolve any difference with the builder before landing conductors. Before any bucket door or dead front comes off, de-energize the section, lock out and verify the absence of voltage; NFPA 70E, 2024 edition, governs that sequence, and local requirements should be confirmed with the authority having jurisdiction.

Questions asked

Does a drawout breaker need more unit space than a fixed breaker?

Usually yes. A drawout breaker rides in a cradle with disconnect stabs and a racking mechanism, so the unit needs height for the cradle and the withdrawal travel, and clear space in front for the test and disconnected positions. The builder's unit schedule lists the drawout height separately from the fixed-mount height for the same frame, so never copy the fixed figure for a drawout bucket.

Do series ratings change the space a breaker needs?

Not physically. A series rating pairs a specific line-side device with a specific branch breaker in a tested combination, so the rating decides which breaker catalog number may occupy the bucket, while the bucket's size still comes from the builder's layout for that breaker. Select the breaker first, then take the space from the schedule for the selected number.

Does breaker size change the working clearance in front of an MCC?

No. The depth and width of the working space in front of the equipment come from NFPA 70, the National Electrical Code, 2023 edition, Table 110.26(A)(1), which sets them by voltage and working-space condition; 480 V equipment under condition 1 needs a 3.5 ft deep space. A taller or wider bucket does not change that clearance, and local amendments should be confirmed with the authority having jurisdiction.

Can a breaker occupy the space an existing starter unit used?

Only if the builder's unit schedule lists that breaker for that space. The starter figure was the starter's own footprint; breaker frames land on different stabs and terminals, and the section's wireway and internal clearances were arranged around the original layout. Get the swap confirmed on a drawing before the bucket is ordered, not after it arrives on site.

Keep reading

  • Comparison

    Switchgear vs MCC: what each term actually means

    The terms mark different equipment: a low-voltage MCC is a UL 845 assembly of stab-in buckets — motor controllers to NEMA size 4, 100 hp at 460 V, feeder frames to 250 A — while switchgear is UL 1558/ANSI C37 distribution gear. A 5.5 kV metal-clad lineup with starters in its draw-out breaker compartments is switchgear with integrated motor control; document it that way.

    Power distribution and transformers

  • Explainer

    What makes a motor control center intelligent

    An intelligent MCC is a motor control centre where each withdrawable starter carries its own microprocessor that owns motor protection, measurement and command response over an internal bus. Trips come from the module, so a bus or DCS outage costs you visibility and remote commands, not protection. Emergency stops and safety interlocks stay hardwired either way.

    Motors and motor starters

  • Explainer

    MCC door-mounted overload reset: order it, don't assume it

    A door-mounted overload reset on a motor control centre is an order-time option, not an inherent feature of non-compartmentalized construction. The option exists only when the installed overload relay has a documented door-reset or remote-reset accessory. Name it in the MCC order per starter with each relay's full type designation; for a retrofit, verify the relay's accessories first, fit only the documented kit, and confirm the control circuit does not restart the motor on reset.

    Motors and motor starters