How-to
When a motor falls below the overload relay setting range
Short answer
A motor rated below an electronic overload relay's setting range is protected by routing its conductor through the sensing path several times, multiplying the measured primary current. Three passes turn 0.55 A into 1.65 A, which lands inside a 1.25 to 6.3 A range; set the effective current or enter the ratio, never both.

On this page
A motor whose full-load current sits under an electronic overload relay's minimum setting cannot be protected by turning the dial down. The fix is mechanical, not electronic: route the monitored conductor through the relay's sensing path several times so the relay sees a multiplied primary current, then account for that multiplication in the current setting. Three passes turn a small motor's nameplate current into an effective value three times larger, which lands inside the 1.25 to 6.3 A setting range of the relay in question. The principle is independent of single-phase or three-phase supply, and the same logic in reverse is why you might set an overload from a nameplate value in the first place (see Setting overload relays from motor nameplate full-load current).
Why the relay needs the loop #
An electronic overload relay measures current through a sensing window or internal path and compares it against a set current range. If the actual motor current is below the minimum settable value, the relay cannot resolve it against its trip curve, and overload protection is meaningless. Winding the conductor through the path N times means the same motor current crosses the sensing element N times, so the device measures an effective current of N times the motor current. This is the same current-transformer thinking that lets a protection relay work above its direct range when a CT extends its reach — see Protecting a motor fed by a VFD with a protection relay for the relay-side view of that arrangement.
The multiplication has one cost: the relay's lowest measurable current does not change. A unit that can monitor down to 15% of its minimum set current still stops resolving current at about 0.19 A. Looping raises the effective current into the settable range; it does not deepen the measurement floor.
Working the passes for a small motor on a 1.25 to 6.3 A relay #
The inputs: a motor rated 0.55 A full-load current (from the nameplate), single-phase supply, and an electronic overload relay with a rated motor-current range of 1.25 to 6.3 A and a monitoring floor of 15% of the minimum set current.
The rule: the required pass count is the smallest whole number N where N times the motor current reaches the range minimum.
The arithmetic:
- One pass: 1 x the nameplate current = 0.55 A — below 1.25 A, no good.
- Two passes: 2 x the nameplate current = 1.10 A — still below 1.25 A, no good.
- Three passes: 3 x 0.55 A = 1.65 A — inside 1.25 to 6.3 A. This is the setting.
The decision: three passes is the lowest supported count for this motor. Set the overload current to the effective looped value, or enter the nameplate current with a 3:1 transformation ratio — one method, never both. The 15% floor works out to 0.15 x 1.25 A = about 0.19 A, which the looped arrangement respects because the effective current is well above it.
Installing the loop #
-
De-energize the motor circuit, lock it out, and test for absence of voltage at the relay terminals before touching the conductors. A sensing path is a live circuit whenever the motor runs.
-
Determine the motor's full-load current from the nameplate, not from a horsepower table. If the relay dial itself is the subject, What the thermal overload relay current setting dial shifts explains what the marking moves.
-
Compute the pass count as in the example above: the smallest N that puts N times the nameplate current inside the relay's stated range. Choose a value comfortably inside the range, not sitting on the minimum, so the setting dial has travel in both directions.
-
Route the monitored conductor through the sensing path that many times, making sure every pass carries the same motor current — a pass through the wrong conductor or a pass left out silently changes the ratio. For a three-phase motor, all phase conductors go through the window with identical pass counts.
-
Configure the scaling by one method only. Set the overload current to the effective looped value, or enter the actual motor current with the transformation ratio that matches the pass count (3:1 for three passes). Applying both corrections stacks a second factor of 3 onto the first and the relay will trip far too late, if at all.
-
Confirm the physical work: passes secured so conductor movement cannot change the count, correct phase conductors in the window, terminal torque per the manufacturer's manual.
Verifying the result before trusting it #
Run the motor at its expected load and read the current the relay reports. If you set the effective current directly, the relay should display the looped value of 1.65 A. If you entered the ratio, it should display the nameplate current. Either reading confirms the scaling matches the hardware; the opposite reading means the method you configured is not the one the relay applies, which is exactly the double-correction trap from step 5. Then confirm the overload function itself: a controlled test trip or a check that the trip current dial position corresponds to the motor's nameplate current after scaling, the same discipline used when selecting a relay range for a mid-size motor as in Overload relay range selection for an 18.5 kW motor.
What looping does not fix #
Looping puts the effective current inside the setting range, but it cannot extend the relay's minimum measurable current below what the manufacturer states — about 0.19 A here, measured as 15% of the range minimum. If a motor is small enough that even a three-pass effective current leaves no setting headroom, the relay is simply the wrong frame size and a smaller-range relay is the correct component. And a motor below a relay's range still needs its overload trip coordinated with the conductor protection upstream; the loop changes what the relay measures, not what the breaker or fuse sees.
Questions asked
How many passes do I need for a 0.55 A motor on a relay with a 1.25 A minimum setting?
Three. One pass presents 0.55 A, below the 1.25 A floor; two passes present 1.10 A, still short. Three passes present 3 x 0.55 A = 1.65 A, which sits inside the 1.25 to 6.3 A range. Each pass must carry the same motor current, and the relay's monitoring floor of about 0.19 A is unaffected by the pass count.
Should I set the effective current or enter a transformation ratio?
Either, depending on which method your relay's configuration supports. Pick one method and verify the displayed current matches it; applying both corrections doubles the error and makes the relay trip late.
Does looping work for three-phase motors too?
Yes. The practice of winding the feeder cables through the sensing path to raise the effective primary current applies whether the motor is single-phase or three-phase, and it is the same principle used when external current transformers extend a relay above its direct range. Keep all three conductors through the window with the same pass count per phase.