Where overloads and run capacitors sit in a rotary phase converter
Short answer
Put the run capacitors between the contactor and the overload elements, wire the elements in the two single-phase supply legs, and set them to the idler nameplate full-load current, so the overload protects the motor alone. Keep the resistor soldered across the start capacitor: it is the bleeder that discharges the capacitor after power-down.

On this page
On a shop-built rotary phase converter, put the run-capacitor banks between the contactor and the overload elements, wire the elements in the two legs tied to the single-phase supply, and set the overload to the idler motor's nameplate full-load current. That way the overload reads idler winding current alone and protects exactly the motor. The resistor already soldered across the start capacitor's terminals is a bleeder that discharges the capacitor after power-down: leave it fitted, never remove it.
Why capacitor placement changes what the overload reads #
An overload element responds to the current flowing through it. Run capacitors draw a leading current, roughly 90 electrical degrees ahead of the voltage, while the idler's magnetizing current lags. If the capacitors connect between the overload and the idler, the element carries the vector sum of those two currents, which is lower than the true winding current. The overload then trips later than the motor needs, and a setting picked from the nameplate under-protects the windings.
With the capacitors tapped on the contactor side of the overload, the element carries only motor current, so the nameplate setting protects the motor and nothing else. Because the capacitors sit downstream of the contactor, opening the contactor still isolates them, which keeps the layout acceptable from a safety standpoint. This needs an accessible junction between the contactor load terminals and the overload; if the overload is direct-mounted on the contactor with no room to tap in between, either mount the overload separately or accept that the trip point under-reads the winding current.
Which legs carry the overload elements #
The two legs fed directly from the single-phase supply (labelled A and C in most converter diagrams) carry the balanced portion of the idler current, and the generated leg (B) carries the rest. Two overload elements in A and C are a legitimate layout: older magnetic starters protected three-phase motors with two elements, so this is not a compromise. A three-element block with all three legs through it also works and covers the generated leg as well. Verify the leg labelling against your own idler wiring before assigning elements, and set the trip current from the nameplate, the same discipline as setting overload relays from motor nameplate full-load current.
Placement options and what each one costs you #
| Layout | Overload carries | Verdict |
|---|---|---|
| Contactor, run caps tapped, then overload, then idler | Idler current only | Preferred layout |
| Contactor, overload, then run caps at the idler terminals | Vector sum of idler and capacitor current | Works, but the trip setting under-reads winding current |
| Overload only in the single-phase feed | Total input current, load machines included | No nameplate value to set against; avoid |
| Direct-mounted overload, no tap point between it and the contactor | Depends on where the caps land | Separate the overload or accept the second layout |
Decide the load-output tap point separately. A tap on the contactor side leaves the idler overload unaffected by load current; a tap on the idler side puts load current through those elements, and they must then be rated and set for the combined current. Every load motor keeps its own overload regardless of which tap you choose. Size the supply conductors and branch breaker for the single-phase input current, which carries idler plus load current, and check the run-capacitor banks themselves against why a rotary phase converter needs three capacitor banks.
Worked example: bleeder resistor dissipation at 240 V on a 1.5 kΩ, 5 W resistor #
The inputs: a start capacitor bank across the single-phase supply at 240 V RMS (a typical single-phase shop supply, as read with a meter across the capacitor group), and a wire-wound bleeder of 1.5 kΩ, 5 W, a value commonly fitted to this job.
The rule: a resistor across a live AC capacitor dissipates P = V²/R, where V is the RMS voltage across the group and R is the bleeder resistance.
The arithmetic: P = 240 V × 240 V ÷ 1500 Ω = 57,600 V² ÷ 1500 Ω = 38.4 W. That is about 7.7 times the resistor's 5 W rating.
The result: a 1.5 kΩ, 5 W bleeder is grossly over its continuous rating at 240 V RMS. It survives across a start capacitor only because that capacitor sits in circuit for roughly a second per start; 38.4 W for about a second is about 38 J per start, within a start capacitor's intermittent duty. Across a run capacitor, which stays energized the whole time the idler runs, the same resistor would overheat.
The decision: on the start capacitor, keep the fitted bleeder as supplied. On a run-capacitor group, size the bleeder for continuous duty: to hold 38.4 W of dissipation down to a 5 W rating you would need at least R = 240² ÷ 5 = 11,520 Ω, about 11.5 kΩ, before any derating for enclosure temperature, and the resistor should run warm at most after a few minutes. A bleeder that is hot to the touch is undersized; raise the resistance or the wattage. DigiKey's capacitor safety discharge calculator works the same V²/R and discharge-time relationships if you want to solve for discharge time instead of dissipation.
Discharge and the safety step that goes with it #
NFPA 79, 2021 edition, requires that hazardous stored energy be discharged before anyone works on the equipment. The bleeder does that job in the minutes after power-down, which is exactly why it stays soldered in place. Before handling any capacitor, de-energize the converter, wait for the bleeder to act, and verify the terminals with a meter set to read DC voltage. Discharge a still-live capacitor through a resistor, never by shorting the terminals with a screwdriver: the short dumps the stored energy into an arc at the contact point. Confirm the details with your local authority having jurisdiction and the capacitor manufacturer's documentation.
Wiring sequence #
- Feed the single-phase supply through the disconnect to the contactor, landing on the A and C idler legs.
- Tap the run-capacitor groups on the contactor load side, ahead of the overload, and connect them from A and C to the generated leg B.
- Fit a bleeder across every capacitor group. Keep the factory resistor on the start capacitor.
- Wire the overload elements in the legs between the capacitor tap and the idler terminals, two elements minimum, three if you want B covered.
- Set the overload to the idler nameplate full-load current.
- Choose the load-output tap point, and fit separate overload protection for each load motor.
- Confirm the start capacitor switches out after acceleration, as the start relay or pushbutton circuit is designed to do.
- Read all three leg-to-leg voltages unloaded, then retune with the real load running, since unloaded balance does not carry over.
If your supply is single-phase and you are considering driving the idler through a drive instead, compare the approach against feeding a rotary phase converter idler from a VFD, and note why more run capacitance overheats a static phase converter motor before adding capacitance to chase a better balance reading.
Questions asked
Do I need overloads on a rotary phase converter at all?
No code section names a rotary phase converter as an assembly that must carry them, but without them a stalled, overloaded or single-phased idler has no trip at all, and the idler can sit unnoticed in an unattended corner of the shop. Fit the overload, set it to the idler nameplate full-load current, and let the branch breaker or fuses handle the short-circuit case. The larger the idler, the more the protection earns its place.
Can I run only the single-phase legs through the overloads?
You can, but then the overload measures total single-phase input current: the idler, the capacitor current and whatever the converter is feeding to connected load machines, all mixed together. That sum has no nameplate number to set against, so the trip point becomes a guess. Setting the elements to the idler nameplate full-load current with all three legs through them, capacitors tapped ahead of the overload, gives a defensible setting.
Should I remove the resistor on the start capacitor when I install it?
No. The resistor is a bleeder that pulls the stored charge down after the converter switches off, so the capacitor terminals are closer to safe when someone handles or replaces the capacitor later. Leave it fitted. Verify the capacitor is actually discharged with a meter before touching the terminals, and never discharge one by shorting the terminals with a screwdriver, which dumps the stored energy into an arc at the contact point.
Why did my balanced voltages drift once I put a load on the converter?
Balance readings taken with the idler running alone do not carry over. As a load motor draws current, the voltage and phase angle of the generated leg shift, so the tuning point you found unloaded moves. Retune the run-capacitor banks with the actual load motor running and settled, reading all three leg-to-leg voltages and the current in each leg with a clamp meter.