Why a rotary phase converter start capacitor reconnects on shutdown
Short answer
One reconnection of the start bank during coast-down is the potential relay doing its job: the generated voltage falls through the relay's dropout point, the relay releases, and its normally closed contacts reclose across the start capacitors for the last part of coast-down. A single brief pulse is acceptable intermittent duty; repeated reconnections or a bank left in at speed are not. A start-capacitor contactor whose coil goes dead with the run command removes the shutdown pulse, and a hold-to-start permission circuit blocks reconnection during load-start dips too.
On this page
- What the potential relay does during coast-down
- Whether the single reconnection hurts the capacitors or the motor
- When the 90-66 recloses on a 5 hp converter at shutdown
- Checks that separate a normal pulse from a fault
- Fixing the shutdown pulse and the load-dip reconnection
- The decision for each case
- Questions asked
Yes — one reconnection of the start bank as the idler winds down is the potential relay doing its designed job, and one pulse per shutdown is the number to keep it at. When control voltage drops out of the main 240 V contactor, the idler keeps spinning and generating. Its generated voltage decays, falls through the 90-66 relay's dropout point of 90 V, and the relay releases, letting its normally closed contacts reclose across the start capacitors for the last part of coast-down. A single brief pulse of capacitor current sits within the intermittent duty a start bank is built for, so it is not a repair item. It becomes one when the bank reconnects often — on every heavy load start that dips the branch — or stays in after the idler reaches speed. A start-capacitor contactor whose coil goes dead with the run command removes the shutdown pulse; a hold-to-start permission circuit removes the load-dip reconnection too.
What the potential relay does during coast-down #
A potential relay does not watch the start command or the shaft; it watches voltage. Its coil sits across the voltage the converter generates — the idler's back-EMF — and its contacts in the start-capacitor circuit are normally closed. As the idler accelerates, the generated voltage climbs through the relay's pickup window, the relay energizes and opens those contacts, taking the bank out. As the machine slows, the same logic runs in reverse: the relay de-energizes at its dropout voltage and the contacts return to their resting, closed state.
Dropping control voltage from the main contactor tells the relay nothing. The idler is still spinning on residual magnetism, and its terminal voltage decays over several seconds — how many depends on the idler's inertia, the load still coupled and the excitation left in the rotor, so time it on your machine rather than assuming. When that decaying voltage crosses the relay's dropout point, the relay releases and the bank reconnects. That is the click and the hum you hear near the end of the wind-down.
One correction to how the event usually gets described: the relay does not open to allow current. It releases, its resting contacts close, and the current then comes from the spinning idler itself, which exchanges current with the bank through the path from the leg labeled B into the manufactured leg C. The main contactor is open at that moment, so the utility supply is not the source. Under some circuit conditions the reconnected bank even sustains the idler's residual excitation briefly, which is why the decay can linger.
The separation between pickup and dropout is the relay's hysteresis, and it does two useful things: it stops the relay from re-triggering on every small dip near the operating point — one crossing, one transition, no chatter — and it means the shutdown reconnection lands well below running voltage, once, rather than cycling.
Whether the single reconnection hurts the capacitors or the motor #
Is it acceptable? One transition during coast-down is acceptable, and on a relay-switched bank it is also inevitable: the relay has no other state to reach as the generated voltage decays.
Is it detrimental? The start bank is an intermittent-duty motor-start capacitor, built for the few seconds of acceleration, not for continuous current. One brief pulse per shutdown adds one switching event of duty and is not a damage mechanism by itself. Damage comes from multiplied or sustained duty: a converter cycled many times a shift pulses the bank once per stop; a deep dip during a heavy load start can add mid-run reconnections nobody asked for; and a bank still connected after the idler reaches speed is carrying continuous current through a capacitor sized for seconds, which overheats it. The start bank's job, next to the continuous-duty run bank, is laid out in why a rotary phase converter needs three capacitor banks.
Can it be stopped easily? Yes — and which fix you need depends on which event you want gone, so the sections below split them.
When the 90-66 recloses on a 5 hp converter at shutdown #
Inputs. Supply: 240 V, single-phase, 60 Hz, feeding the converter through the main contactor (the reported case). Idler: 5 hp, three-phase (the reported case). Relay: the 90-66 potential relay, 240 VAC version, contacts normally closed in the start circuit, with published pickup of 208–239 V and dropout of 90 V (relay data; confirm against the datasheet for your exact relay revision). Coil: wired to sense the converter's generated voltage.
Rule in words. The start contacts stay open only while the sensed voltage sits above the relay's dropout value. Below it, the contacts reclose and the bank reconnects between the legs.
Arithmetic. Dropout as a share of nominal supply voltage: 90 V ÷ 240 V × 100 = 37.5%. Pickup window as a share of nominal: 208 V ÷ 240 V × 100 = 86.7%, and 239 V ÷ 240 V × 100 = 99.6%. Minimum separation between pickup and dropout: 208 V - 90 V = 118 V.
Result. On the way up, the bank leaves the circuit once the generated voltage passes roughly 87–100% of nominal. On the way down, the contacts stay open through almost the whole coast-down and reclose once, when the sensed voltage decays to 90 V — 37.5% of nominal. On this machine that means one designed transition, confined to the last portion of the wind-down. The thresholds are relay data, not an estimate, but the decay time to reach them is machine-specific: time it with a meter across the relay coil.
Decision. A single reclose below about 90 V sensed is the relay working to its data; leave it alone on a converter that runs occasionally, and add the start-capacitor contactor described below if the machine cycles often. Before assuming the shutdown pulse is the only transition, meter the coil voltage with the idler running: if it sits near the bottom of the pickup window, near 208 V, an ordinary load dip can release the relay mid-run and reconnect the bank while the machine is in use.
Checks that separate a normal pulse from a fault #
Before any of these measurements: open the converter's disconnect, lock it out, and verify absence of voltage at the idler terminals. The start bank can hold a charge after shutdown, so discharge it and verify before touching its terminals. NFPA 70E, 2024 edition, is the standard covering the de-energize-and-verify practice for electrical work of this kind; confirm the details with your site's safe-work procedures and the local authority having jurisdiction.
- Meter across the relay coil with a true-RMS meter through one normal stop. You want one clean decay and one contact transition as it passes the dropout point. Several transitions in a single coast-down means a marginal relay or a coil voltage hovering at a threshold.
- Clamp the start-capacitor lead through a stop. One brief pulse confirms the single-transition case. Steady current while the idler is at speed means the bank never left the circuit — a stuck relay, welded contacts or miswiring, which is a fault to fix before the next run.
- Separate startup noise from shutdown noise. Chatter during acceleration is the relay releasing mid-start and reconnecting the bank while it is still speeding up — a pickup-threshold problem, related to the case in why a rotary phase converter rattles on start. The shutdown pulse happens once, near the end of the wind-down.
- After lockout and discharge, feel the capacitor cans at the end of a shift. Warm after many stops is accumulated duty doing what the contactor fix below prevents. Hot after one stop means sustained connection.
- Identify what actually carries the bank current: the relay's own contacts, or a separate start-capacitor contactor. If a contactor, meter its coil at stop — it must go dead when the run command drops, or the fix in the next section is half-built.
- Read the relay data before swapping models: a replacement for the 90-13/90-27 family lists a dropout maximum of 130 V, higher than the 90-66's dropout point, so thresholds are not interchangeable between relay families.
Fixing the shutdown pulse and the load-dip reconnection #
The shutdown pulse: a start-capacitor contactor that goes dead with the run command. Put a contactor between the start circuit and the bank and feed its coil through an auxiliary contact of the main contactor, so the coil has no supply once the run command drops. The relay can then reclose its start contacts into a dead circuit: nothing energizes the contactor and the bank stays out for the whole coast-down. This is the direct fix for the reported symptom, and it is the arrangement builders of larger idlers already use, because the start current of a big idler — one documented build at 15 hp — is beyond the small relay's contacts.
The load-dip reconnection: a start-only permission contact. While the converter runs, the relay coil is live, and a dip deep enough to release it recloses the start path with the machine up. Put a normally open pushbutton in series between the relay contact and the contactor's coil: hold it through acceleration, release once the idler is up to speed, and the start path has no command afterward, so no dip can pull the bank in. The illuminated style makes the timing unambiguous — the lamp stays lit while the relay is still calling for the bank, so hold until the light goes out. A deep motor-start sag on the service is a real mechanism, not a theory: why a 4.16 kV motor start dips a 120 V branch to 109 V works the same voltage dip on a utility branch.
Both, without relying on the operator: a two-pole toggle. One pole interrupts the start-relay path, the other interrupts the start button circuit. Switch on, press start, switch off once up to speed. If you try to start with the toggle off, the idler simply does not start — the failure mode you want instead of a hidden reconnection.
Any of these adds control wiring to a phase converter: NFPA 70, the National Electrical Code, 2023 edition, Article 455 covers phase converter installations, including disconnecting means and overcurrent protection. Confirm what applies to your installation with the local authority having jurisdiction and the converter's documentation.
The decision for each case #
- One pulse near the end of coast-down and nothing else: normal. Leave it on a converter that starts in the morning and stops at night; fit the start-capacitor contactor when the machine cycles several times a shift, because each pulse is one more duty event on an intermittent-duty bank.
- The bank reconnects when a heavy load starts: fit the start-only permission contact, on top of the contactor if you do not have one — the contactor alone cannot stop a mid-run reconnection, because its coil is still commanded while the converter runs.
- Current in the bank while the idler is at speed: not a relay-behavior question. A welded contact, a stuck relay or miswiring is holding the bank in; diagnose it before the next run, because a bank sized for seconds overheats in continuous service.
- Chatter during startup instead of one shutdown pulse: a relay pickup mismatch to the machine's generated voltage. Solve it by matching the relay's pickup to the measured running coil voltage, not by treating the shutdown event.
Questions asked
Does the coast-down pulse damage the idler motor?
One brief capacitor-current exchange as the idler slows is not a winding-heating event for the motor. The component that accumulates stress is the intermittent-duty start bank, and only when reconnection repeats many times a day or the bank stays in after the idler reaches speed. If the motor itself runs hot or trips its protection, look for a bank that never left the circuit or a relay pickup mismatch rather than at the single shutdown pulse.
Why does my potential relay chatter during startup instead?
Chatter means the relay coil voltage hovers around the pickup point instead of climbing cleanly through it: a pickup window set too close to the converter's running generated voltage, or generated voltage sagging while the bank switches. The 90-66's pickup window is 208 to 239 V, so meter the coil voltage with the idler at speed and use a relay whose pickup sits clearly below that running value, leaving margin so ordinary dips cannot release it.
Can the relay keep switching the start bank directly?
On a small idler, yes, and many small converters are built that way. Builders running larger idlers put a separate contactor between the relay and the bank because the start current grows with idler size; one documented build at 15 hp needed the contactor for exactly that reason. The contactor also gives you the clean place to cut the bank at shutdown, which is the fix for the coast-down pulse.
Is the start bank a shock hazard after shutdown?
It can be. The bank may hold a charge after the converter stops, whether or not it reconnected during coast-down. Open the disconnect, lock it out, verify the idler terminals are dead, then discharge the capacitor through a bleed resistor and verify before touching its terminals. Treat the bank as live until it is verified discharged.