Why a rotary phase converter rattles on start

Motors and motor starters Published 8 min read

Short answer

A one-second rattle at converter start, repeating when the load motor starts, is contactor chatter: the accelerating motor drags the coil voltage down until the armature drops out and re-pulls. Trace the dip; a bigger breaker will not fix it. The reported 245, 250 and 270 V output is a larger fault — 5.9% unbalance against the 1% NEMA MG 1 derating threshold — so balance the generated leg before production; feed the converter from the load machine input plus its idle draw, not the idler nameplate current.

On this page
  1. Why the rattle points at a contactor
  2. Find the dip: measure through both starts
  3. The start circuit: a contactor with a short, timed job
  4. The output voltages: the bigger finding
  5. Sizing the supply breaker: machine input plus idle draw
  6. The decisions for this installation
  7. Questions asked

A rotary phase converter that rattles loudly for about one second at switch-on — and again when the machine motor starts — is not running normally. That sound is a contactor chattering: the accelerating motor drags the coil voltage down until the armature drops out and slams back in, several times inside that second. A 5 hp idler makes it loud. The reported output voltages of 245, 250 and 270 V are the second finding, and the larger one: they compute to 5.9% voltage unbalance, nearly six times the 1% level NEMA MG 1 treats as the derating threshold, so the generated leg has to be rebalanced with the mill running before it cuts metal again. Neither problem is fixed by a bigger breaker — and no, breaker sizing does not add the idler's nameplate current to the machine's; it uses the machine's input current plus the converter's idle draw.

Why the rattle points at a contactor #

An AC contactor takes more energy to close than to hold. When a motor accelerates it draws inrush current many times its running current, and that current drops voltage across every impedance between the service and the machine. If the contactor's coil is fed from a circuit that shares that path, the coil voltage dips exactly while the contactor is still building its magnetic field. Once the coil falls to roughly 85% of its rated voltage, the armature starts to separate; the load current steps back, the voltage recovers, and the contactor slams in again. Half a dozen cycles in a second, and the enclosure rattles audibly.

That is why the noise lands on the two starts and vanishes at steady running, when coil current and line voltage settle. The dip follows the same arithmetic as any motor-start sag, so the size of it can be checked the way you would when calculating voltage drop when a second motor starts: starting current, supply impedance, volts lost.

The two events implicate different coils:

  • At converter switch-on: the main contactor pulls in and the start-circuit contactor energizes the start capacitors. Chatter here points at the converter's own control wiring or coil supply.
  • At mill-motor start: the mill's contactor pulls in against a supply already carrying the idler. Chatter here points at the start dip reaching whichever coil is fed from the sagging point.
  • At steady running: a marginal coil usually holds, because holding costs less than closing — which is why the machine appears to run fine between starts while the contacts pit.

A larger breaker changes none of this: the rattle is a control-voltage event, not an overcurrent trip, so the breaker never sees it as a fault.

Find the dip: measure through both starts #

De-energize, lock out and verify the absence of voltage before any cover comes off — NFPA 70E, 2024 edition, governs that verification and the protective equipment for energized work — and confirm the practice with the authority having jurisdiction. The voltage measurements below are energized work: they belong to a qualified person with a true-RMS meter rated for the panel and a min/max or recording function, because the event lasts about a second and a steady reading will miss it.

  1. Listen with the covers closed and find the source: the converter enclosure (a contactor), the idler itself (mechanical), or the mill.
  2. Measure the incoming single-phase supply at the converter input through both starts and note the minimum captured.
  3. Measure directly across the coil of the contactor that rattles, during the same start, and compare the captured minimum with the coil's rated control voltage printed on its body.
  4. Only after lockout and verification, inspect control terminations, coil leads and the start-circuit switching device for looseness, heat discoloration and contact wear.

Also check which source feeds each control coil: a coil fed from the generated leg sees a voltage that moves with load and tuning, so its dip behavior changes between converter start and mill start.

What the measurements mean #

What the measurements show What it means Next step
Incoming supply dips and the coil dips with it The inrush is exposing supply impedance or a loose input termination Repair terminations after lockout; check conductor sizes against the load
Incoming supply steady; coil dips toward 85% of its rating The fault is in the control supply: undersized control conductors, a weak control transformer, or a coil fed from the moving generated leg Refeed the coil from the incoming side and re-test
Supply and coil both steady; the contactor still chatters The contactor itself: sticking armature, weak coil, or an interrupted hold command Inspect or replace the contactor; trace the command path
No electrical disturbance; the noise tracks the idler Mechanical looseness, not chatter Check mounting bolts, cooling fan, coupling and bearings with power isolated

The start circuit: a contactor with a short, timed job #

In a rotary converter the second-noisiest part after the idler is the start-capacitor contactor. Its job is narrow: energize the start capacitors for the fraction of a second the idler needs to come near speed — a common design figure is about 0.3 s after the main contactor closes — then drop out and stay out. Rattle at converter switch-on very often lives in this circuit: a loose control termination, a weak coil supply, or contacts already roughened by earlier chatter.

The failure modes branch from there. A start contactor that sticks closed leaves the start capacitors in circuit continuously; they overheat, and the generated leg's voltage is pulled out of shape — the pattern behind why a rotary phase converter overheats after startup. A start circuit that never engages leaves the idler spinning up on run capacitance alone, humming and slow to accelerate — why a rotary phase converter with no start circuit hums. Neither fault is corrected by adding run capacitance at random: identify which circuit each capacitor serves before changing anything, and work from the converter's schematic.

The output voltages: the bigger finding #

Before comparing any readings, label which output conductor is the generated leg, as the guide to labeling the generated leg in rotary phase converters describes; a mixed-up conductor label is the most common way a converter gets tuned against the wrong numbers. Then take the three line-to-line pairs in one defined condition, and take them again with the 2 hp mill motor running under real cut load: a rotary converter's balance moves with load, and the loaded numbers are the ones that decide.

The reported set — 245, 250 and 270 V — was read once, and the operating condition behind it is not recorded, so treat what follows as a calculation on reported inputs, not a measurement:

  • Average voltage = (245 + 250 + 270) / 3 = 765 / 3 = 255 V.
  • Deviations from the average: 10 V, 5 V and 15 V; the largest is 15 V.
  • Voltage unbalance = 100 × 15 / 255 = 5.9%, using the NEMA definition in ANSI/NEMA MG 1-2016 (Revised 2018): percent unbalance equals 100 times the maximum deviation from the average voltage, divided by the average.

A 5.9% result sits past the end of that curve, and the unbalance heats the idler and the mill motor alike, because unbalanced voltage drives a disproportionate current unbalance in the windings.

The decision follows: repeat the three line-to-line readings at the mill terminals with the machine under load, and if the high pair persists, rebalance the generated leg under load using the converter's balancing procedure and its specified capacitor values before the machine returns to production. Why one pair sits high, and what pulls it down, is covered in the page on why a rotary converter's generated leg voltage reads high.

Sizing the supply breaker: machine input plus idle draw #

The breaker question has a clean answer: do not add the idler's nameplate current to the machine's. The idler runs unloaded, so its single-phase input is mostly magnetizing current plus friction and windage losses — small next to the machine's input. Size the branch from the load machine's rated input current plus the converter's idle input, or better, from the maximum single-phase input current the converter's documentation publishes for the converter-and-load pair.

Read the machine's 15 A nameplate as what it is: the whole machine's input, spindle motor and controls included, not one motor winding. That machine input plus a small idle increment is the arithmetic that lands this kind of installation on a 20 A branch breaker. The detail more often missed is the conductor: NFPA 70, the National Electrical Code, 2023 edition, Article 430 lets motor branch-circuit protection exceed conductor ampacity within its limits, which is why the NEC allows #14 AWG conductors on a motor branch circuit under the standard's own conditions. Confirm the conductor size, the breaker and the converter's input rating with the machine documentation and the authority having jurisdiction.

The decisions for this installation #

Committing to each branch:

  • The rattle is contactor chatter from a coil-voltage dip during acceleration. Measure across the chattering coil through both starts and repair what the measurement shows — a loose termination, an undersized control conductor, a weak control transformer — and leave the breaker alone.
  • The start-circuit contactor must drop out shortly after the idler is up to speed. If its contacts show arcing or welding, replace it before any further starts.
  • The voltages compute past the end of NEMA's unbalance curve. Repeat the three line-to-line readings at the mill terminals under load; if the high pair persists, rebalance the generated leg with the machine running, using the converter's procedure and specified capacitor values. Until that is done, the mill stays out of production.
  • The breaker at 20 A behind a 15 A machine input is consistent with the sizing rule above; verify the conductor ampacity and the converter's published input current, and confirm both with the authority having jurisdiction.

Questions asked

Is it safe to keep starting the machine while the converter rattles?

No. Each chatter cycle makes the contactor contacts touch and separate under load, which pits them and can end in a welded contact. A welded start-circuit contactor is worse than the noise: the start capacitors stay in the circuit, the idler overheats and the output balance gets worse. Stop repeated starts, measure the coil voltage during a start, and repair the dip before running work.

How much voltage unbalance can a three-phase motor tolerate?

ANSI/NEMA MG 1-2016 (Revised 2018) starts derating polyphase induction motors once terminal voltage unbalance exceeds 1%, and its published derating curve ends at 5%; above that, the motor manufacturer must be consulted. Unbalanced supply also drives a much larger current unbalance, so the motor overheats even at nameplate load. Measure the three line-to-line voltages at the motor terminals with the machine running, and confirm limits against the motor documentation.

Do you add the idler motor current to the machine current when sizing the supply breaker?

No. Size from the load machine's rated input current plus the converter's idle input, which is mostly magnetizing current and friction losses and sits far below the idler's three-phase nameplate current. If the converter maker publishes a maximum single-phase input current for the converter-and-load pair, use that figure. Size the branch per NFPA 70, 2023 edition, Article 430 and confirm with the authority having jurisdiction; a 15 A machine input on a 20 A branch breaker is the pattern this arithmetic produces.

Why is one leg of a rotary phase converter higher than the incoming pairs?

The high voltage is on the generated leg, which the idler synthesizes rather than receiving from the service. Its voltage depends on the balancing capacitors and on the connected load: a converter tuned to look reasonable unloaded can leave that pair high, and load pulls it down. Judge balance with the machine running, and label the generated conductor first so the three line-to-line pairs are not mixed up.

Keep reading

  • Troubleshooting

    Why a synchronous idler will not balance a rotary phase converter

    No: a synchronous idler does not self-balance a rotary phase converter, because its rotor neither senses nor corrects the manufactured leg. The converter in question read 240, 253 and 252 V line-to-line, about 3.4% unbalance — tune that with run capacitors under load. The 168 V generated-leg-to-ground reading disagrees with that set, which implies about 222 V to the supply midpoint, so retake it against an identified neutral with a true-RMS meter.

    Motors and motor starters

  • Troubleshooting

    Fixing a machine shutdown on a rotary phase converter third leg

    Move the machine's single-phase control supplies and interlock boards off the manufactured leg: they belong across the two utility legs, and only three-phase motor loads should see the generated leg. In one reported case a larger converter and a rewired 100 A service did not stop the trips until the legs were re-landed; balance the legs to the builder's tolerance, typically 5%, after that.

    Motors and motor starters

  • Troubleshooting

    Fixing AC contactor chatter on a loaded 80 HP motor start

    Chatter with the motor connected but a clean pull-in with the motor disconnected is the supply sagging under locked-rotor current; the 750 VA and external-outlet tests already cleared the control transformer. At 6x the 81 A label the start draws about 486 A on a 271 A transformer, so limit the start to roughly 270 A with a soft starter and verify the coil holds above 102 V.

    Motors and motor starters