Troubleshooting
Why a rotary phase converter overheats after startup
Short answer
Balance the three line-to-line voltages within 5% — at 5% unbalance NEMA MG 1 derates the driven motor to about 3/4 of nameplate horsepower — and confirm the potential relay actually removes the start bank. About 200 V line-to-neutral on the generated leg is normal geometry on a 230 V converter, not a fault.
On this page
- Two failures that match these symptoms
- Read the supply the way the motor does
- Prove the start bank drops out
- Worked example: capacitor currents in a 10 hp converter at 230 V, 60 Hz
- Balance the run bank on both generated legs
- The 5% line: what unbalance costs the driven motor
- The order of operations
- Questions asked
Your 10 hp converter spins up instantly and then cooks because starting torque was never the issue: the start bank is almost certainly still in the circuit after acceleration, and all 235 µF of run capacitance hangs on one pair (L2 to L3), leaving the L3 to L1 pair nothing to pull it up. Confirm the full supply voltage directly across L1 to L2, prove with a clamp meter that the start-bank current goes to zero seconds after full speed, then balance the three line-to-line voltages within 5%. Stop chasing a line-to-neutral number on L3: roughly 200 V there is normal converter geometry, not a fault.
Two failures that match these symptoms #
The instant start tells you the start bank has plenty of capacity and is wired to deliver it. It says nothing about what happens after acceleration ends, and two faults in this build produce exactly fast start plus heat plus smell:
- The start bank never leaves. Your 508–610 µF of start capacitance belongs in the circuit for the few seconds of acceleration only; start capacitors are intermittent-duty parts and cook when energized continuously. A potential relay has to open the contactor once the idler is up to speed, and a relay that audibly clicks is not proof its power contacts opened — welded contacts or a miswired coil path leave the bank in.
- The run bank is one-sided. Every microfarad sits between L2 and L3, which pulls up the L2 to L3 pair and does nothing for L3 to L1. The converter runs unbalanced, and unbalanced line-to-line voltage heats the idler and every motor fed from it.
The 115 V readings that started the investigation are incomplete without a reference: they are almost certainly line-to-neutral readings on a split supply, which is exactly what this idler connection needs.
Read the supply the way the motor does #
A three-phase machine responds to the three voltages between its line terminals — nothing else. Measure those directly, with the converter running:
| Reading | What it decides |
|---|---|
| L1–L2 | The incoming supply; confirm the rated voltage here |
| L2–L3 | First generated pair; the run bank tunes it |
| L3–L1 | Second generated pair; needs its own capacitance path |
| Any leg to neutral or ground | Diagnostics only; never a balancing target |
The equipment grounding conductor stays where it is — it is a safety connection, not a phase conductor, and no balance target lives on it.
The 200 V you did not expect on L3 is arithmetic, not a fault. With the three line-to-line voltages balanced and neutral at the midpoint of the L1 to L2 supply, the generated leg lands at 230 × √3 / 2 ≈ 199 V from neutral. That is why the 120 V plus about 60 V target fails you; the reference-frame distinction behind line-to-line and line-to-neutral readings on a 3-phase 480 V motor transfers unchanged to this converter.
Before going further, read the idler nameplate — rated voltage and connection diagram — and check the terminal links match it. Its previous life as a fan-cooled CNC motor establishes nothing about how it is strapped today. Then measure across L1 to L2: a split supply gives half the line-to-line voltage on each leg to neutral and the full voltage between them, so that is the likely supply, but the direct reading decides. If L1 to L2 really measures 115 V, stop and reconnect — that is not a capacitor problem.
Prove the start bank drops out #
Before hands touch anything: lock out the single-phase supply, test for absence of voltage, and discharge both capacitor banks through a rated bleeder before touching a lead — start electrolytics hold a real charge. NFPA 70E, 2024 edition, the US standard for electrical safe work practices, governs the energized checks that follow; use instruments rated for the circuit.
With the circuit dead, wire-check the starting control against the relay documentation: where the sensing coil connects, its documented pickup and dropout voltages, and the path of the contactor coil through the relay contacts. The relay should sense the generated leg's rising voltage and drop the start contactor out just after the idler reaches speed. Anything wired so the contactor stays energized — a holding contact, the wrong relay terminal — reproduces your symptom exactly.
Then a short unloaded run with a clamp ammeter on the start-bank feed: the current must fall to zero within seconds of full speed. The next section gives the numbers to expect on each bank.
Worked example: capacitor currents in a 10 hp converter at 230 V, 60 Hz #
Inputs, all from this build:
- Run bank: 2 × 50 µF + 3 × 45 µF = 235 µF, connected L2 to L3.
- Start bank: 1 × 130–156 µF + 2 × 189–227 µF = 508–610 µF across the marked ranges, in circuit only during acceleration.
- Supply: 230 V, 60 Hz, measured across L1 to L2.
Rule in words: a capacitor draws current equal to 2π × frequency × capacitance × the voltage across it — I = 2πfCV.
Arithmetic:
- 2πf = 2 × 3.1416 × 60 = 377 per second.
- Amps per volt: 377 × 0.000001 F = 0.000377 A per volt per microfarad, so per volt the run bank draws 0.000377 × 235 = 0.0886 A and each start-bank extreme draws 0.000377 × 508 = 0.1915 A and 0.000377 × 610 = 0.2299 A.
- At the measured 230 V: run bank 0.0886 × 230 = 20.4 A; start bank 0.1915 × 230 = 44.0 A at the low end and 0.2299 × 230 = 52.9 A at the high end.
- Size check: 508 / 235 = 2.16 and 610 / 235 = 2.60 — a common rotary-converter guideline sizes total start capacitance near 2:1 versus run, so the bank is generously sized, not wrong.
Decision: seconds after the idler reaches speed, the run-bank lead should read about 20 A and the start-bank lead zero. A start lead still carrying anything — let alone the 44–53 A this bank draws — means the start circuit never opened, and that current forced continuously through intermittent-duty capacitors is your heat and smell. Repair the release circuit and replace any start capacitor that has swelled or vented before the next run. Scale the numbers to your measured L1 to L2 voltage; capacitor current tracks voltage linearly.
Balance the run bank on both generated legs #
With the start circuit proven, tune the run side:
- Idler running unloaded, record L1–L2, L2–L3 and L3–L1 at the idler terminals in one sitting — same meter, same conditions.
- Compute the unbalance: average the three readings, take the largest deviation from that average, divide by the average, multiply by 100 for percent.
- Add capacitance to a bank to raise its generated pair; remove capacitance to lower it. With all 235 µF on L2 to L3 you can only pull one pair around — the usual layout places one bank on each supply leg (L2–L3 and L3–L1) so both generated pairs are tunable. Split yours and trim each.
- Repeat with the load motor running at working load, reading at the driven motor's terminals: balance shifts with load, and the driven motor is what pays for the error.
The mixed 50 µF and 45 µF units are not a problem. Parallel capacitors all see the same voltage, and each carries current in proportion to its own capacitance — a 50 µF unit carries 50 / 45 ≈ 1.11 times the current of a 45 µF unit. Matched microfarads are a convenience, not a requirement; what each unit needs is a voltage rating above the line-to-line voltage it sits across and continuous run duty.
While balancing, watch the idler's line current against its nameplate. Why rotary phase converter idle current is so high covers what unloaded current to expect before you call it a fault, and Setting overload relays from motor nameplate full-load current shows how to set the idler's overload so a tuning mistake trips instead of cooking the winding.
The 5% line: what unbalance costs the driven motor #
NEMA MG 1, the NEMA standard covering motors and generators, publishes the derating curve for motors operating on unbalanced line voltage; a 2009 IEEE-published test that instrumented motor windings with temperature sensors confirmed the curve holds with margin. The point you will use: at 5% line-to-line unbalance, derate the driven motor to about 3/4 of nameplate horsepower, with less derating as the unbalance drops along the curve. Confirm the curve in the edition your motor was built to, and with the motor documentation, before leaning on it for a production machine.
Decision: treat 5% as the ceiling of acceptable balance. If the best you land at, loaded, is 5%, keep the driven motor at or below three quarters of its nameplate load or go back and rebalance the banks. The deviation-from-average arithmetic is the same discipline behind setting voltage imbalance limits on a 480 V phase monitor, so it carries over to protecting the load side too.
The order of operations #
- Lock out, verify absence of voltage, discharge both banks.
- Measure L1 to L2 at the converter input and confirm the reading against the idler's connection.
- Wire-check the potential relay and contactor against the relay documentation.
- Short unloaded run with a clamp on each bank lead: about 20 A on the run bank, zero on the start bank after full speed.
- Record the three line-to-line voltages, split the run bank across L2–L3 and L3–L1, trim below 5%, recheck loaded.
Questions asked
Why does the generated leg read about 200 V to ground instead of 120 V plus 60 V?
Because that expectation is wrong for this supply. With neutral at the midpoint of the L1 to L2 pair and the three line-to-line voltages balanced, the generated leg lands at 230 multiplied by the square root of 3 divided by 2, about 199 V to neutral. Anything near 200 V there is normal; judge the converter only on the three line-to-line readings.
Can I keep running the converter while I track down the overheating?
No. Until the start-bank dropout is proven, every run can push 44 to 53 A of capacitor current through intermittent-duty start capacitors, which cooks them and can vent electrolyte. Limit yourself to short unloaded runs with a clamp meter on the bank leads, and replace any start capacitor that has swelled or vented rather than reusing it.
Do the run capacitors have to be the same microfarad value?
No. Parallel current shares by capacitance, so a 50 µF unit carries about 1.11 times the current of a 45 µF unit, and the bank total is simply the sum, 235 µF. Matched microfarads are a convenience, not a requirement. What each capacitor needs is a voltage rating above the line-to-line voltage it sits across and continuous run duty.
How much load can the driven motor carry at 5% voltage unbalance?
About three quarters of its nameplate horsepower, per the NEMA MG 1 voltage-unbalance derating curve; below 5% the required derating shrinks along the same curve. Recheck the balance with the load connected, because the line-to-line readings shift between unloaded and loaded operation, and the driven motor is what pays for the error.
Is my start bank too big at more than twice the run capacitance?
No. A common rotary-converter sizing guideline puts total start capacitance near twice the run capacitance to guarantee starting capacity. Your 508 to 610 µF against 235 µF of run is 2.2 to 2.6 times, generous but in line. What matters is that the potential relay removes all of it within seconds of the idler reaching full speed.