Troubleshooting
Why a synchronous idler will not balance a rotary phase converter
Short answer
No: a synchronous idler does not self-balance a rotary phase converter, because its rotor neither senses nor corrects the manufactured leg. The converter in question read 240, 253 and 252 V line-to-line, about 3.4% unbalance — tune that with run capacitors under load. The 168 V generated-leg-to-ground reading disagrees with that set, which implies about 222 V to the supply midpoint, so retake it against an identified neutral with a true-RMS meter.
On this page
- Will a synchronous idler balance my rotary phase converter on its own?
- What does a synchronous motor do differently from an induction idler?
- What do the 240, 253 and 252 V readings actually say?
- Does the generated leg's ground reading agree with the line-to-line set?
- How do I retake the readings so they mean something?
- How do I fix the unbalance without replacing the idler?
- When would a synchronous machine earn its place at all?
- Questions asked
The answer is no. Swapping the induction idler for a motor described as synchronous will not make three balanced lines appear on their own, because nothing in a synchronous rotor senses the manufactured leg or corrects its voltage. What you have are two ordinary converter jobs wearing a mysterious coat: a line-to-line set of 240, 253 and 252 V — about 3.4% voltage unbalance, a run-capacitor tuning task — and a generated-leg-to-ground reading of 168 V that disagrees with that set, which points at the measurement, not the machine. Keep the 3 hp lathe's converter as it is, retake one synchronized set of readings, and tune the capacitors under load. The physics, the procedure and the targets follow.
Will a synchronous idler balance my rotary phase converter on its own? #
No. A synchronous rotor holds speed once its field is excited, but it neither senses the manufactured leg nor corrects its voltage — the balance still comes from run capacitors tuned under load, whatever spins in the middle.
A rotary phase converter feeds two of its three lines straight from the single-phase supply and manufactures the third. The manufactured leg exists because the idler's stator couples the two energized windings to the third winding, the way one winding of a transformer couples to another. Its magnitude is set by winding impedances, the run capacitors and the load drawn — the rotor's type does not enter the amplitude question. So the claim that a synchronous machine puts out three lines, all correct in volts and amps on its own, describes a device that does not exist: no idler, induction or synchronous, measures its own manufactured leg and trims it.
What a synchronous machine does hold is speed, and — properly excited — the voltage behind its terminals. Speed is not the problem at the lathe; the manufactured leg's size under load is.
What does a synchronous motor do differently from an induction idler? #
It starts as an induction motor on its amortisseur winding — squirrel-cage bars in the rotor pole faces — then applies DC to the field winding near synchronous speed and locks into step, at which point the damper's job is done and torque comes from the excited field.
The order matters: applying field current during acceleration spoils the smooth run-up, and with no field current a wound-field synchronous machine develops no synchronous torque at all — a motor is either synchronous or induction, never both at once. Once locked in, the damper effect fades and the machine runs on its field.
An overexcited synchronous machine draws leading reactive current — the synchronous-condenser effect — so in principle its excitation could supply some of the vars the run capacitors now supply. That is a deliberate, manual adjustment, not self-balancing: excitation trims vars while the circuit impedances still decide the manufactured leg, and it needs a DC exciter that a 7.5 hp converter otherwise never carries. Wound-field synchronous machines are built mostly in large ratings; small motors sold as synchronous are usually permanent-magnet or reluctance types, which follow the supply's field without correcting anything either. An idler's heavy no-load current, meanwhile, is mostly magnetizing and is normal — that is why rotary phase converter idle current runs high.
What do the 240, 253 and 252 V readings actually say? #
The set reads about 3.4% voltage unbalance — an average of 248.3 V with a worst deviation of 8.3 V — which is a run-capacitor tuning task, and the generated-leg pairs sit just past the 105% band a machine-tool load tolerates.
Unbalance, defined the way NEMA MG 1, the NEMA motors-and-generators standard, defines it, is the largest deviation from the average divided by that average:
- Average line-to-line voltage = (240 + 253 + 252) / 3 = 745 / 3 = 248.3 V
- Maximum deviation = 248.3 - 240 = 8.3 V
- Voltage unbalance = 100 × 8.33 / 248.33 = 3.36%, call it 3.4%
That is an estimate from one set of readings: read the current edition of the standard and the motor's documentation for the limits that govern the machine, and confirm any code-side requirement with your authority having jurisdiction. A motor's current can be substantially more unbalanced than its terminal voltage, so judge the converter by the three line currents under the same load, not by the voltages alone.
The practical tuning bands compare each generated-leg pair with the supplied pair:
| Load on the converter | Unloaded: generated-leg pair vs supplied pair | Fully loaded: pair vs supplied pair | At the measured 240 V supplied pair |
|---|---|---|---|
| General-purpose motors | no higher than 110% | no lower than 90% | 264 V upper, 216 V lower |
| Machine-tool or CNC load | no higher than 105% | no lower than 95% | 252 V upper, 228 V lower |
The measured leg pairs sit at 105.4% and 105.0% of the supplied pair — 253 V and 252 V against 240 V — a hair past the machine-tool band if that set was taken unloaded. Why a manufactured leg runs high at all is a circuit question, and the knowledge-base page on why a rotary converter has unbalanced voltages walks the impedance mechanism step by step. Machine-tool loads care more than a plain motor does, and the page on how a CNC tolerates converted three-phase when leg voltages stay balanced explains the tighter tolerance from the control side.
Does the generated leg's ground reading agree with the line-to-line set? #
No — the ground-referenced leg reading disagrees with your own line-to-line set: that set implies roughly 222 V from the generated leg to the supply midpoint, a balanced set implies about 208 V, and 168 V matches neither, so suspect the measurement first.
The three line-to-line readings must be geometrically consistent with one reference. In a split 120/240 V supply the neutral sits at the electrical midpoint of the two lines, 120 V from each. The generated leg's height above that midpoint follows from each leg-pair reading:
- sqrt(253² - 120²) = sqrt(64009 - 14400) = 222.7 V
- sqrt(252² - 120²) = sqrt(63504 - 14400) = 221.6 V
The two agree within a volt, so the set is self-consistent: the geometry estimate puts the generated leg near 222 V above the midpoint, assuming near-sinusoidal RMS readings. For a perfectly balanced converter the same geometry gives sqrt(240² - 120²) = sqrt(43200) = 207.8 V — the roughly 208 V a well-tuned leg shows the midpoint.
So treat the low ground-referenced number as a measurement event, not a converter fault. Likely explanations: the clip was on a conductor that is not the supply midpoint (an equipment ground is a fault-current path, and its potential carries the drop along the grounding conductors even where neutral and ground are bonded at the service); the reading came from a different operating state than the line-to-line set; or the meter is not true-RMS, and an averaging meter calibrated for a sine wave misreads the harmonic-rich manufactured leg badly enough to invent a fault. Take tuning values line-to-line and reference checks to the identified neutral. The same reference questions decide real third-leg failures, and the guide on fixing a machine shutdown on a converter's third leg works them from the machine side.
How do I retake the readings so they mean something? #
Take one synchronized set — the three line-to-line voltages and all three line currents, first unloaded, then under the cut that pulls the high current — with a true-RMS meter and a written note of which reference and which operating state produced each number.
Before any cover comes off: de-energize, lock out and verify absence of voltage; the live readings below are taken by a qualified person through meter jacks or at terminals, with the meter category and protective equipment the job's NFPA 70E, 2024 edition, risk assessment selects — confirm the details with your authority having jurisdiction and the panel documentation. Then:
- Identify the conductors: the two supply lines, the manufactured leg, and the neutral identified at the service where it is bonded — never an equipment ground as a reference.
- Energize and record the three line-to-line voltages at the lathe terminals with the converter unloaded.
- Run the lathe at the setting that pulls the heavy current and record the same three voltages plus all three line currents at one instant. Note whether the reading belongs to 2000 rpm at the spindle or at the motor — a gearbox makes those different numbers.
- Compare the loaded voltages with the tuning bands and the currents with the nameplate; if one current stands out, set the overload relay from the nameplate full-load current the way setting overload relays from nameplate data shows.
- If a reference check is still wanted, measure the manufactured leg to the identified neutral at the service and compare it with the geometry estimate above.
How do I fix the unbalance without replacing the idler? #
Tune the run capacitors between the generated leg and the two supply lines, judging every step under the real load: the measured pairs sit just past the machine-tool band, and the target is loaded pairs inside it, within 95% to 105% of the supplied pair.
Use motor-run capacitors, one across each generated-leg-to-line pair. Adjust one bank a little, watch which reading moves and which way, then alternate between banks; judge every step under the loaded cut, because the leg sags as load rises. More capacitance is not automatically better — excess capacitor current heats the machine, and why more run capacitance overheats a static converter's motor shows where that current goes — and starting capacitors never belong in the run circuit. Once the loaded pairs hold inside the band, check the three currents against the nameplate under that same cut; if one leg still runs high with balanced voltages and a confirmed mechanical load, the suspects are the tool load and the motor, not the converter. To have the band watched continuously, a phase-monitor relay on the converter output does the job, and the guide on setting voltage imbalance limits on a 480 V phase monitor covers the trip-point arithmetic — the same percentages apply at any voltage.
When would a synchronous machine earn its place at all? #
Not in this converter: wound-field synchronous machines earn their keep as large constant-speed drives or as synchronous condensers for power-factor correction, where excitation is deliberately set and controlled, and nothing in that behavior trims a small converter's manufactured leg on its own.
Even with a true wound-field machine in hand you would add a DC exciter and a field-application control that closes near synchronous speed — and you would still reach for the capacitor banks, because excitation trims vars while the manufactured leg follows the impedances. The induction idler already installed is the right machine.
The decision, in order: retake one synchronized reading set per the list above; trim the run capacitors under the loaded cut until the generated-leg pairs sit inside the machine-tool band; verify the three currents against the nameplate under that same cut. If the currents then match, the 7.5 hp induction idler stays exactly where it is, and the synchronous swap solves nothing it was being counted on to fix.
Questions asked
What should the generated leg read to neutral?
With the neutral at the midpoint of a 240 V supply, a perfectly balanced converter puts the manufactured leg near 208 V above that midpoint, and a leg that reads high line-to-line reads somewhat higher still — the geometry in the article predicts the number from your own set. Use the reading only to catch a mislabeled or high-resistance reference conductor; tuning decisions stay with the line-to-line values measured under load.
Why do the three currents differ when the voltages look close?
A small voltage unbalance produces a much larger current unbalance in a three-phase motor: the negative-sequence part of an unbalanced supply meets a far lower rotor impedance than the positive sequence does, so one line current climbs while the others stay near normal. That is why judging the converter by voltage alone is unreliable — record the three currents under the same load before calling the job finished.
Do I need a true-RMS meter for converter work?
Yes. The manufactured leg carries harmonic content that an ordinary sine-calibrated averaging meter handles poorly, and a wrong waveform assumption can report a healthy leg noticeably low — enough to invent exactly the fault being chased. Use one true-RMS instrument rated for the service panel, keep the leads in the voltage jacks, and use the same meter for every number in a comparison set.
What kind of capacitors go in a rotary converter's run circuit?
Motor-run capacitors only: oil-filled, continuous-duty units rated for the working voltage of the pair they sit across. Electrolytic starting capacitors drop out after acceleration and must never live in the run circuit — run continuously they overheat and burst. Tune in small steps and recheck the idler's current after each step so the total capacitor current stays comfortable for the machine.
Can a VFD replace the converter for one machine?
For a single machine, yes: a VFD makes its own three-phase output from the single-phase supply and adds speed control, sized to that one load under the manual's single-phase input rules. It does not feed a shop's other three-phase equipment. If the lathe is the only three-phase machine in play, that route retires the balancing question entirely.