Which soft starter control mode fits each load type

Motors and motor starters Published 8 min read

Short answer

Pumps get torque control with a controlled stop, fans and compressors get a current ramp with the limit near 3.5 times nameplate full-load current, and conveyors get a current ramp with soft deceleration. Choose the mode from the load's failure mode, then confirm the result with a measured start and stop.

On this page
  1. Which soft starter control mode fits a pump?
  2. Which mode fits a fan or blower?
  3. Which mode fits a conveyor?
  4. Which mode fits a compressor?
  5. How do you set the current limit, and what does it do to the voltage dip?
  6. Which stop mode goes with each load?
  7. What should you measure before and after a mode change?
  8. When does no soft starter mode fix the symptom?
  9. Questions asked

A soft starter's control mode decides how motor voltage rises and falls; the load decides which behavior you need. Pumps take torque control with a controlled deceleration stop, because water hammer is a torque step, not a current magnitude. Fans, blowers and compressors take a current ramp with the current limit set near 3.5 times the nameplate full-load current, then a coast stop, because their risk is belt slip and breakaway shock. Conveyors take a current ramp with soft deceleration when product shift matters. The table gives the call for each load, the sections below give the reasoning, and the worked example puts a number on the voltage dip.

Load Failure you are limiting Start mode Stop mode Verify by
Pump Water hammer, pressure shock Torque control Controlled deceleration stop Pressure trace through both transitions
Fan or blower Belt slip, duct shock Current ramp, long ramp time Coast stop Belt behavior during acceleration
Compressor Mechanical shock at breakaway Current ramp with current limit Coast stop Starting current and sound at breakaway
Conveyor Product shift, belt stretch Current ramp Deceleration ramp only if the loaded stop disturbs product Product handling on a loaded stop

Which soft starter control mode fits a pump? #

Use torque control on the start and a controlled deceleration stop at shutdown, because a pump's damage comes from water hammer, which is caused by torque steps as the voltage jumps between thyristor conduction states, so the mode that holds accelerating torque steady fixes it. A plain current ramp often does not.

Torque control is a closed-loop mode: the starter estimates motor torque from voltage, current and power factor, and adjusts the voltage continuously so acceleration follows the ramp setting instead of the motor's own torque curve. That smoothness is what keeps the pump's pressure wave off the piping.

The controlled stop matters just as much. A pump deceleration mode walks the voltage down so the pump slows with the fluid column and the check valve seats gently instead of slamming. One limit to know: deceleration needs voltage headroom. The motor must stay magnetized as the voltage falls, so on a weak supply or a long cable run the motor can drop out mid-ramp and deliver exactly the jolt you were trying to avoid. Test a deceleration stop with the pump loaded before trusting it.

Which mode fits a fan or blower? #

Give a fan a current ramp with a long ramp time and a coast stop. The failures you are limiting are belt slip and duct shock at breakaway, and the fan freewheels down after shutdown anyway, so a controlled stop buys nothing and only heats the motor.

The ramp time is the working variable here. A belt drive accelerates slowly, and a centrifugal fan's torque demand rises with the square of speed, so the ramp has to be the longest of the common loads. If the blower's inertia is high enough that no published ramp applies, the guide to specifying soft starters for high-inertia blowers without curves walks the sizing path from the load data you do have.

A long ramp also means the motor spends seconds at reduced voltage carrying reduced but real current. The guide on setting a soft starter current limit without overheating the motor covers the thermal side of that trade, and the starter's own duty-cycle rating is the ceiling you cannot trade away.

Which mode fits a conveyor? #

Start a conveyor on a current ramp and add a deceleration ramp only when the load shifts or the belt stretches on an uncontrolled stop.

Conveyors are low-inertia loads with nearly constant torque demand, so the ramp can be short compared with a fan's, and most start cleanly on the plain ramp. Let the machine tell you where to spend effort. If product disturbs on acceleration only, stretch the start ramp. If it disturbs on stopping only, tune the deceleration ramp with the belt loaded, because an empty belt behaves differently and will not reproduce the symptom.

Which mode fits a compressor? #

Run a compressor on a current ramp with the limit set at roughly 3.5 times the motor's nameplate full-load current, and let it coast to a stop. The compressor's failure mode is mechanical shock at breakaway, and limiting the current limits the torque that goes with it.

The start must be unloaded where the compressor's unloader permits it. A compressor that starts against full pressure asks for breakaway torque that a voltage-limited start may never deliver, and the motor will sit at the limit, heating, until the overload or the starter's own protection stops the attempt. The write-up on why a large motor stalls when the soft starter hits current limit shows how to tell that torque shortfall from a ramp-time problem, which needs the opposite fix.

How do you set the current limit, and what does it do to the voltage dip? #

Set the limit as a multiple of the nameplate full-load current, then estimate the voltage dip from the transformer's short-circuit capacity; the estimate tells you before the first start whether the chosen limit passes the plant's dip criterion.

The dip formula is:

voltage dip (%) = starting kVA ÷ available short-circuit kVA × 100
available short-circuit kVA = transformer kVA ÷ (impedance % ÷ 100)

Worked example, with illustrative inputs: a three-phase motor at 460 V with a nameplate full-load current of 77 A, fed from a 500 kVA transformer at 5.75 percent impedance, with an across-the-line start of 6.5 times full-load current.

  1. Available short-circuit capacity: 500 kVA ÷ (5.75 ÷ 100) = 8,696 kVA.
  2. Across the line: 6.5 × 77 A = 500 A, so starting kVA = 1.732 × 460 V × 500 A = 398 kVA, and dip = 398 ÷ 8,696 × 100 = 4.6 percent.
  3. With the limit set at 350 percent: 3.5 × 77 A = 270 A, so starting kVA = 1.732 × 460 V × 270 A = 215 kVA, and dip = 215 ÷ 8,696 × 100 = 2.5 percent.

Decision: against a 3 percent dip criterion, the limited start passes at 2.5 percent and the across-the-line start fails at 4.6 percent, so this machine gets the current-ramp mode with that limit. This estimate assumes the transformer impedance dominates the supply, which a stiff utility makes slightly conservative, and it treats starting current as roughly proportional to applied voltage, which is an approximation rather than a measured result. Confirm the dip criterion with the utility and the authority having jurisdiction. The conductors and short-circuit protection stay sized for the full locked-rotor current under NFPA 70, the National Electrical Code, 2023 edition, Article 430, regardless of the limit. If the starter states its limit in kVA instead of as a multiple of full-load current, the article on converting a 350 kVA soft start limit to starting current gives that conversion.

Which stop mode goes with each load? #

Ramp the pump down with a controlled deceleration stop, coast the fan and the compressor, and ramp the conveyor down only when the loaded stop shifts product or stretches the belt; the stop mode is set by what the load does once the starter stops driving it.

Deceleration on a soft starter works by lowering voltage until the load's own resisting torque drags the speed down. It is not braking. A load that the process back-drives, or one whose torque demand collapses at low speed, will not follow the ramp; the motor drops out of the ramp and the machine jerks to rest. Coast is the right call whenever the load freewheels harmlessly, as fans and unloaded compressors do, because decelerating them only adds heat without changing the outcome.

What should you measure before and after a mode change? #

Record a baseline start and stop with the machine's own instruments, change one setting at a time, and repeat the same cycle with the same load before you accept the new mode.

De-energize and verify absence of voltage before opening the starter or changing any connection; NFPA 70E, 2024 edition, covers the de-energize-and-verify sequence and the arc-flash boundaries for that work, and the requirement belongs with your authority having jurisdiction and the equipment documentation.

For each load, the confirming measurement is the one tied to the failure mode: a pressure or flow trace through both transitions for the pump, belt behavior through acceleration for the fan, a current trace from the starter's display or a clamp meter for the compressor. Keep the overload and protection settings unchanged while you tune, and check that running current returns to nameplate after bypass. When it does not, the article on a motor running over nameplate amps after soft starter bypass covers the causes. If the starter shows a fault or alarm during testing, the diagnostic write-up on reading a soft starter fault before resetting it tells you what to capture first, and a trip during tuning is a stop sign, not a setting to override.

When does no soft starter mode fix the symptom? #

If the symptom is still there at steady speed, no starting mode will fix it: a soft starter shapes the transition only, and the cause lives in the mechanical system, the process or the supply.

Belt slip at full speed, vibration at full speed, product damage during steady running and a process variable that never settles all point away from the starter. Fix those at the coupling, the belt, the unloader or the process before touching another ramp.

The other escape case is a load that must change speed while running. A soft starter reaches one speed only, so a fan that needs flow control or a conveyor that needs speed matching belongs on a VFD, and that swap changes the control wiring too; the article on wiring start and stop pushbuttons when a VFD replaces a DOL starter covers the terminal side of that change. For everything that starts once, runs at full speed and stops, the mode chosen from the table above is the answer.

Questions asked

Can one soft starter keep two parameter sets for two different loads?

Many starters store several parameter sets, so give each load its own set and record both configurations. A set tuned for a pump's torque-controlled stop will over-accelerate a compressor or under-torque a loaded conveyor. After any switch between loads, run one unloaded verification cycle before returning the machine to production.

Why does the motor stall during a fan start even with the current limit active?

The limit is holding the voltage too low to develop breakaway torque for that fan's inertia and static pressure. Raise the limit in small steps if the supply dip budget allows, or extend the ramp. If the motor still stalls, the start needs more current than the supply can give and a VFD is the next step.

Does a conveyor benefit from torque control too?

It can, but most conveyors start and stop cleanly on a plain current ramp because they are low-inertia loads with nearly constant torque demand. Reserve torque control for conveyors where jerk damages product, such as long inclined belts with loaded stops, and confirm the improvement with a loaded cycle against the baseline.

What if the voltage dip is still over the plant limit with the current limit active?

A soft starter can only cut voltage, and the current that follows is still several times full-load current. When the dip budget is tighter than that, a VFD is the usual answer because it controls frequency as well as voltage and can hold the start near rated current. Strengthening the supply is the alternative.

Keep reading

  • Selection guide

    Specifying soft starters for high-inertia blowers without curves

    Torque, not kilowatts, decides the start: at a 400% current limit on a motor with 800% locked-rotor current, torque falls to about 25% of DOL and a 15 s blower start stretches to four times that or stalls. Close the dampers, hold the limit near the square root of the load-torque fraction times the measured inrush (about 500% of full-load current here), buy duty to cover it, or specify a drive.

    Motors and motor starters

  • Troubleshooting

    Why a soft starter barely improves utility bus voltage dip

    On a fixed-impedance screening calculation, cutting starting current from 600% to 400% scales a 10% utility-bus dip to about 6.7%, so a modeled 2-point gain signals a study-method or data problem, not a soft-starter fault. A 10% dip on a shared medium-voltage feed also exceeds the roughly 5% planning ceiling utilities apply at the point of common coupling. Keep the starter for the motor and the mechanical train; fix the study, then the supply, before ruling the starter out.

    Motors and motor starters

  • How-to

    Second motor starting voltage drop calculation

    The second motor's dip is √3·I·(R cosφ + X sinφ) through the shared source-and-feeder impedance, with I the phasor sum of the running motor's load current and the starting motor's locked-rotor current. The running motor supplies none of the start; it adds to the drop. Iterate once on the reduced terminal voltage, then judge by torque, which falls with the square of voltage.

    Motors and motor starters