Why a 350 HP motor cannot run a 398 HP load on service factor

Motors and motor starters Published 7 min read

Short answer

Service factor is a margin for uncertain and intermittent load, not continuous extra horsepower, and NEMA MG 1 says service-factor load reduces insulation and bearing life. A 398 HP load on a 350 HP motor runs at a 1.137 load ratio and uses 91 percent of a 1.15 service-factor band, so the overcurrent trips at nameplate settings report a duty problem. Fit a 400 HP motor for a continuous load; never raise the overload setting.

On this page
  1. What the service factor is for
  2. The arithmetic on this nameplate
  3. What the thermal calculation proves and hides
  4. Why the starters time out
  5. Checking the 80 percent service factor claim
  6. The decision, case by case
  7. Questions asked

Service factor is not continuous extra horsepower. NEMA MG 1, the standard for motors and generators, defines it in its 2014 edition as a multiplier applied to rated output that indicates a permissible loading at rated voltage and frequency, and NEMA's published guidance adds that insulation life and bearing life are reduced by operation at service-factor load. The case at hand is a 398 HP load on a 350 HP nameplate: a load ratio of 1.137, inside the arithmetic of a 1.15 service factor but spending the reserve on the base load. The starters that time out on overcurrent the moment the compressors load are the protection reporting that the duty exceeds the rating. For a continuous load at that level the decision is a 400 HP motor, never a higher overload setting. Below is the arithmetic, the thermal check and the two cases that change the answer.

What the service factor is for #

NEMA's tables apply the 1.15 value to Design A, B and C polyphase squirrel-cage machines, and the standard's stated uses are modest: absorbing error in a predicted load, covering intermittent peaks, and letting a machine that runs below its rating operate cooler and last longer. Spend the reserve on the base load and none of those jobs gets done. A service factor is a permitted operating point, not a promise of normal life at that point.

The physics behind the life warning is ordinary. Insulation aging follows an Arrhenius relationship, and the working rule is that every 10 °C of winding temperature halves insulation life. Magnetic forces on end turns and slot conductors scale with current squared, so at this load ratio they reach about 1.29 times rated. Torque, shaft stress and bearing loading rise with the same load while the frame runs hotter, and none of that shows up in a horsepower multiplication, which is why NEMA treats service factor as margin, not a second rating.

The arithmetic on this nameplate #

The load ratio is the shaft load divided by the nameplate rating: 398 ÷ 350 = 1.137. A 1.15 service factor gives an arithmetic ceiling of 350 × 1.15 = 402.5 HP, so the stated requirement leaves 4.5 HP, about 1.1 percent of the load, to cover voltage deviation, ambient above the 40 °C rating and process swings. As a share of the band, the machine would run (1.137 − 1.00) ÷ (1.15 − 1.00) = 91 percent of the way from rated load to the service-factor limit, continuously.

Case Shaft load Load ratio What it means
Rated duty 350 HP 1.00 Base rating; 35 °C measured rise on a like machine's dynamometer test
Service-factor ceiling at 1.15 402.5 HP 1.15 Permitted loading, with reduced insulation and bearing life
The compressor duty 398 HP 1.137 91 percent of the band spent on the base load
Claimed ceiling at 1.25 437.5 HP 1.25 Paper rating until the machine is tested at that load

The later upgrade letter changes the multiplier, not the machine. At 1.25 the ceiling is 437.5 HP on paper; whether the delivered frame, winding and bearings suit that duty is exactly what a heat run at that load would show, and no such run is on record. Treat a service-factor change issued after delivery as a claim until the motor manufacturer supplies measured, stabilized winding and bearing temperatures for the delivered machine at that load, plus a warranty naming the operating point.

What the thermal calculation proves and hides #

The defense of the smaller machine rests on the motor manufacturer's data: a measured rise of 35 °C at rated load on a dynamometer test of a like machine, calculated rises of 46 °C at 1.15 load and 52 °C at 1.25 load, and a worst-case winding temperature of 40 °C ambient + 52 °C rise + 15 °C hot spot = 107 °C, well under the 155 °C total-temperature limit of Class F insulation. The rated-load rise also shows a conservative design: NEMA MG 1 permits a 105 °C rise by resistance at rated load for a Class F machine with a 1.0 service factor, and this winding tested at 35 °C.

What the calculation proves is that the winding will not fail soon from temperature. What it hides is larger. The loaded rises are calculated, not measured, so no stabilized temperature exists for the actual duty. Staying under the Class F limit is not the same as rated life: the same data has the winding running about 11 °C hotter at service-factor load than at rated load, and with insulation life halving every 10 °C that projects to roughly half the insulation life of operation at the nameplate rating. Interpolating to the real duty gives a rise near 45 °C and a winding temperature near 100 °C, still under the limit and still hotter than the rating assumes. Thermal aging is also only one failure mode; the end-turn forces and bearing loading above appear nowhere in the sum.

Why the starters time out #

The overload was set from the nameplate, which is the correct basis. NFPA 70, the National Electrical Code, 2023 edition, sets separate overload protection at 125 percent of nameplate full-load current for a motor marked with a service factor of 1.15 or more, and at 115 percent for a 1.0 service factor, the difference behind why a motor protection relay trips at full load with service factor 1.0 while the same machine at 1.15 is set higher. Confirm the applied rule with the authority having jurisdiction and the medium-voltage starter's documentation.

Estimate the loaded current from the shaft power, using the tested efficiency and power factor interpolated to this load (94.5 percent and 0.895): 398 HP is 296.8 kW at the shaft; input power is 296.8 ÷ 0.945 = 314 kW; apparent power is 314 ÷ 0.895 = 351 kVA; on a 4160 V three-phase system the current is 351,000 ÷ (1.732 × 4160) = 48.7 A. That is 113 percent of the 43 A the like machine drew at rated load, a sustained current parked between the 115 and 125 percent marks, where a relay set tighter, an ambient-compensated element, or a real current a few percent above the estimate produces exactly the trips reported. The relay is telling the truth.

The trip is a duty problem, not a protection problem: raising the magnetic overload setting to clear it is the one move to refuse, because it removes the only element protecting the winding and conductors from the very overload under discussion. Measure instead, recording phase current during start, unloading, loading and steady loaded operation, and keep the protection as it is, since setting overload relays from motor nameplate full-load current is the correct basis. Take the readings from the starter's metering or protection current transformers at the relay, and de-energize, lock out and test for absence of voltage before opening any compartment to add metering.

Checking the 80 percent service factor claim #

The statement that the unit runs at 80 percent of the service factor does not survive arithmetic. Eighty percent of total service-factor capacity is 0.80 × 402.5 = 322 HP, below the nameplate rating and nowhere near the requirement. Eighty percent of the service-factor band is a load ratio of 1.00 + 0.8 × 0.15 = 1.12, or 392 HP. The stated duty sits at 91 percent of the band, not 80. Put the question to the compressor manufacturer in units that cannot slide: the shaft horsepower at the rated operating point, and whether that figure is a guaranteed maximum or a continuous requirement. The decision forks on that answer.

The decision, case by case #

The load is continuous at the stated horsepower: fit a 400 HP motor. The base rating then carries the duty, the service-factor band stays in reserve for the conditions it exists for, the overload coordinates without fighting the process, and NEMA's life warning no longer applies to the operating point. That is the design the submittal should have carried, and it is where this job should end up.

The high load is a short peak over a lower continuous average: the smaller machine can stay if a recorded current profile over a full production cycle shows a thermal-equivalent current at or below nameplate full-load current, and the peaks fit the starter's curve. Record before concluding.

The 1.25 service-factor letter is the only new evidence, and on its own it buys nothing: accept it only with a heat run at that load on the delivered machine, with measured, stabilized winding and bearing temperatures rather than calculated rises, and a warranty that names the operating point.

The trips continue at nameplate settings: the duty is over the rating, and the fix is the motor, the compressor's operating point or the load profile, never the overload setting.

Questions asked

Can the smaller motor stay if the high load is only a short peak?

Yes, if the thermal-equivalent current stays at or below nameplate full-load current. Square the measured phase current, weight each value by its duration over one full production cycle, and take the square root of the average. Worked simply: 20 minutes at 49 A and 100 minutes at 41 A gives the square root of (20 × 49² + 100 × 41²) ÷ 120 = 42.4 A, below the 43 A rated-load test value, so the winding sees a rated-duty thermal cycle and the machine can stay, provided each peak fits the starter curve.

Does an inverter-fed motor get a service factor to spend?

No. NEMA MG 1 Part 31, which covers definite-purpose inverter-fed motors, requires a service factor of 1.0, and running such a machine above rated output reduces insulation life. If this compressor ever moves to a drive, the service-factor question disappears: the motor must carry the load at its base rating, and the drive is sized to the motor's full-load current.

How do you read loaded current on a 4160 V starter safely?

Read it through the starter's existing metering or protection current transformers at the relay display, never with a handheld clamp on medium-voltage cable. If metering must be added, de-energize the circuit, apply lockout, and test for absence of voltage before any compartment opens. Verify the transformer ratio on its nameplate so the displayed secondary current converts correctly to primary amperes.

How long must a loaded acceptance test run before its temperatures count?

Until temperature stabilizes, not for a fixed interval. A common criterion is winding and bearing sensors changing less than 1 °C across one hour, which for a machine this size typically means several hours at the real load. Log phase current, voltage, winding and bearing temperatures and cooling-air inlet temperature at fixed intervals, and file the log with the manufacturer's validation.

Keep reading

  • Troubleshooting

    Why no-load current exceeds nameplate on a small motor

    An uncoupled small three-phase motor drawing about 1.06 A against a 0.8 A published no-load value was running on 486–488 V against a 460 V rating. A controlled 455 V test returned every phase to 0.8 A, so the cause was supply overvoltage, not the motor.

    Motors and motor starters

  • Explainer

    What the 125% trip current dial setting on an overload relay means

    Set the overload relay dial to the motor nameplate full-load current — 27.4 A in the worked example — and enter nothing extra. The trip-amps marking means the relay trips at 125% of the setting you enter (27.4 A × 1.25 = 34.25 A), so the multiplier already sits inside the plate. A 1.15 service factor is a loading allowance, not a reason to raise the setting, and the current-limit function is a separate threshold with its own delay.

    Motors and motor starters

  • Troubleshooting

    Why raising a magnetic overload setting won't fix a hard start

    No. Raising the dashpot pickup toward the 125% ceiling a 1.15 service factor permits adds no starting torque; it only lets the motor sit at locked-rotor current longer while its running protection shrinks. Find which device opened — breaker instantaneous element or overload relay — and fix what makes the start hard; in the case behind this article, an over-filled fluid coupling was the whole problem.

    Motors and motor starters