Electrical safety and codes Published 8 min read By Current Intel engineering team

Short answer

No. The PPE category belongs to the incident energy calculated at one equipment location, and the feeder cable between the switchgear and the MCC changes both the arcing current and the clearing time of the device that clears an MCC arc. The MCC's energy can come out lower or several times higher, so it gets its own calculation and its own label.

On this page
  1. What the switchgear label's category covers
  2. The feeder cable changes the arcing current
  3. Where the arcing current lands against the pickup
  4. Worked example: one feeder, two very different energies
  5. The decision for your MCC
  6. Questions asked

No. The category on the switchgear label does not travel down the feeder to the MCC, and equal nominal voltage carries nothing: the cable between the two adds impedance, so an arc inside the MCC runs at a lower arcing current than an arc in the switchgear. Lower current can mean lower incident energy, but if it drops below the instantaneous pickup of the breaker that clears the MCC, clearing moves into a slower band and the energy multiplies. The MCC can come out milder than the switchgear or several times worse, and only a calculation tells you which. Here is why, with the arithmetic.

What the switchgear label's category covers #

NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, covers employee safety around electrical equipment, including arc-flash risk assessment, PPE selection and equipment labeling. It offers two ways to choose arc-flash protection: an incident-energy analysis, and the PPE category method of Table 130.7(C)(15). Under the category method, a task on a given equipment class maps to a category, and that mapping holds only while the available fault current and the clearing time at that equipment stay within the parameters printed in the table.

A category is a clothing ensemble, not a rating of the gear. Category 4 means arc-rated clothing with a minimum arc rating of 40 cal/cm²; it says nothing about how much energy the equipment can produce. Incident energy, expressed in cal/cm², is the thermal energy an arc delivers to a surface at the stated working distance, and it is a result: arcing current and clearing time, adjusted by the enclosure and the distance.

That is why the labeling requirement in NFPA 70E ties the posted value to that piece of equipment, with the date of the assessment. The switchgear's 4 describes the energy at the switchgear's working distance, cleared by the device that protects the switchgear. Your MCC is a different location with a different current and usually a different clearing device, so it needs its own result. The site's electrical safety program and the authority having jurisdiction decide which selection method the labels use; confirm that before anything gets printed.

The feeder cable changes the arcing current #

Two currents matter. Bolted fault current flows through a zero-impedance connection and sets interrupting duty; arcing current is what flows once the fault is an arc, and it is the current that heats the arc and drives the protective device. IEEE Std 1584-2018, the Guide for Performing Arc-Flash Hazard Calculations, covers the calculation of arcing current, incident energy and the arc flash boundary. Its procedure collects the system and installation data, identifies the modes of operation, determines the bolted fault currents at each location, then derives the arcing current. The arcing-current model is built around arc tests at 600 V, 2700 V and 14.3 kV, so a low-voltage system sits at the low end of its range — inside it, but at the edge.

The cable is what separates the two locations. Its resistance and reactance sit between the switchgear bus and the MCC bus, so the bolted current at the MCC is lower than at the switchgear by exactly what the feeder impedance takes away, and the arcing current follows it down. Which bolted current belongs in each device's duty is a separate question — which bolted fault current to use for breaker duty and arc flash answers it — but the copying stops right here: two locations, two currents, two calculations.

Where the arcing current lands against the pickup #

The consequence runs through the trip unit. An electronic-trip feeder breaker clears high currents in its instantaneous band, within a few cycles, and lower currents in its short-time band, after a deliberate delay measured in tenths of a second. The MCC's arcing current sits somewhere on that curve, and where it lands decides the label:

MCC arcing current against the clearing device What sets the clearing time Effect on the MCC's incident energy
Well above the instantaneous pickup The instantaneous band, a few cycles Lower than the switchgear's, because the current is lower
Below the instantaneous pickup, above the short-time pickup The short-time delay, tenths of a second Often several times the switchgear's, because time multiplies
Inside the pickup tolerance Either band Evaluate both currents; the slower result governs the label

So the cable cuts both ways, and the direction is not a judgment call; it is one comparison — the MCC's calculated arcing current against the pickup of the device that clears the MCC. The clearing device depends on where the arc is: the MCC main cannot interrupt a fault on its own incoming terminals, so the line side answers to the upstream feeder breaker while the bus answers to the main. Which breaker sets MCC arc flash duration sorts that out for each arc location.

One more wrinkle: IEEE 1584-2018 has you calculate the energy at the arcing current and again at a reduced arcing current, and the reduced case is what usually drops below a pickup first — why arc flash software reports 85% of the arcing current covers it. Both currents have to clear fast before the MCC earns a fast-time label.

Worked example: one feeder, two very different energies #

Take this hypothetical — every number is an example input, not a plant you know. A 480 V, three-phase, 60 Hz system; the switchgear bus shows a bolted fault current of 30 kA in the existing study. An 800 A frame electronic-trip feeder breaker runs 300 ft to the MCC through two parallel 250 kcmil copper conductors per phase, with the instantaneous pickup set at 12 times the frame, 9.6 kA, and a short-time pickup at 6 times, 4.8 kA, delayed 0.4 s.

Step 1, cable impedance. Chapter 9 Table 9 of NFPA 70, the National Electrical Code, 2023 edition, which tabulates conductor AC resistance and reactance, lists about 0.052 Ω of resistance and 0.041 Ω of reactance per 1000 ft for one 250 kcmil copper conductor. Two in parallel halves both, to 0.026 Ω and 0.0205 Ω per 1000 ft, and over 300 ft that gives R = 0.026 × 0.300 = 0.0078 Ω and X = 0.0205 × 0.300 = 0.0062 Ω.

Step 2, bolted current at the MCC. The source impedance behind the 30 kA bolted fault is Z = 480/(1.732 × 30,000) = 0.0092 Ω; treat it as pure reactance, which is fair for a transformer-fed bus. Totals: X = 0.0092 + 0.0062 = 0.0154 Ω against R = 0.0078 Ω, so Z = √(0.0154² + 0.0078²) = 0.0173 Ω. The bolted current at the MCC is 480/(1.732 × 0.0173) = 16.1 kA — the feeder removed 46 percent of it.

Step 3, arcing current at each location. The low-voltage arcing-current equation from the 2002 edition of the guide, used here only to make the mechanism visible (a compliance study runs the 2018 equations), is log10(Ia) = K + 0.662·log10(Ib) + 0.0966·V + 0.000526·G + 0.5588·V·log10(Ib) − 0.00304·G·log10(Ib), with currents in kA, V in kV, gap G in millimeters, and K = −0.153 inside an enclosure. With a 25 mm gap at the MCC it returns about 8.7 kA; with a 32 mm gap at the switchgear, about 13.8 kA.

Step 4, the trip. At the switchgear, 13.8 kA sits well above the 9.6 kA pickup, so the breaker clears in its instantaneous band, about 0.05 s on its published curve. At the MCC, 8.7 kA sits below that pickup and above the 4.8 kA short-time pickup, so the same breaker waits out the 0.4 s delay.

Step 5, the energy. To first order, incident energy scales with arcing current and directly with clearing time, so the ratio between the locations is (8.7 × 0.4)/(13.8 × 0.05) ≈ 5. The MCC bus carries roughly five times the incident energy of the switchgear compartment on the very same feeder, with 37 percent less arcing current. Copy the switchgear's 4 onto the MCC in this case and the label understates the hazard about fivefold.

The hand arithmetic is an estimate: the study software solves the same network with the actual resistance-to-reactance ratios and the 2018 energy equations, and the result is checked against the governing code and the equipment documentation before it reaches a label.

The decision for your MCC #

Do not copy the 4. Commission the MCC calculation — how to model an MCC bucket for an arc flash study covers the bucket-level detail — and make sure the model includes the feeder cable, the MCC's own gap and enclosure, and the trip settings as installed, not as drawn. Then compare the MCC's arcing current, in both the nominal and the reduced case, against the pickup of the device that clears each location:

  • Above the pickup: the MCC lands at or below the switchgear's energy, and its label may well come out a lower category.
  • Below the pickup: the delay governs, the MCC's energy climbs above the switchgear's, sometimes past what the category tables cover — the case to catch before someone opens a bucket.

If the result is too high, fix the settings, not the label: a lower instantaneous pickup or a shorter short-time delay moves the MCC's arcing current back into a fast band, and the energy falls with the time. Both directions have a price — a lower pickup buys energy down and spends coordination, a higher one buys coordination and spends energy — so the change goes through the coordination study together with the arc-flash study before the settings move.

One note on reading those settings: if the trip unit's face is behind a compartment door, that is de-energized work — lock out the feeder, test for absence of voltage, then open the door, under the site's electrical safety program and NFPA 70E.

Questions asked

Can the NFPA 70E PPE category table be used for the MCC without a calculation?

Only if its parameters hold at the MCC itself. The category table in NFPA 70E (2024 edition) lists a maximum available fault current and a maximum clearing time for each equipment class and task, and both must be verified at the MCC, not borrowed from the switchgear. In a plant where electronic-trip breakers are set for coordination, the slower clearing at the MCC's reduced arcing current is exactly what usually pushes a task outside those parameters, and then the incident-energy analysis is the method that applies.

Does the MCC line side carry the same label as the MCC bus?

Usually not. An arc at the MCC's incoming terminals sits ahead of its main breaker, so the upstream feeder breaker clears it; an arc on the bus or in a bucket is cleared by the MCC main or the bucket device. Each location gets its own clearing time and its own incident energy, so a proper study reports them separately and the label names the location it covers.

What if the calculated MCC energy comes out higher than the switchgear's?

The fix is in the settings, not the label. Lowering the feeder's instantaneous pickup or shortening its short-time delay puts the MCC's arcing current back into a fast band, and incident energy falls almost in direct proportion to clearing time. Any change has to keep the feeder coordinated with the MCC main and the largest bucket starter, so the coordination study is re-run with the arc-flash study before the settings move.

Could both the switchgear and the MCC legitimately carry the same category?

Yes, as a result rather than an assumption. If the MCC's arcing current still clears in the same fast band and the energy at the working distance rounds into the same clothing ensemble, both labels read the same. That agreement has to come out of the MCC's own numbers; when it does, the label is correct, and when it does not, copying the switchgear's value hides a real difference in either direction.

Keep reading

  • Explainer

    How to model an MCC bucket for an arc flash study

    Model the MCC as a bus with the bucket breaker as a branch and the outgoing run as a cable. A magnetic-only HMCP clears a load-side fault only when the arcing current exceeds its pickup, including its plus 30 percent tolerance; the line side of the bucket breaker is cleared upstream and sets the bucket's worst case.

    Electrical safety and codes

  • How-to

    Which breaker sets MCC arc flash duration

    Use the MCC main breaker's clearing time only for faults on its load side. In an MCC with no documented arc-resistant rating — including early-1980s lineups — treat arc propagation ahead of the main as credible and take duration from the upstream 480 V switchgear breaker: at 20 cycles instead of 6, incident energy multiplies by 3.33. Where construction leaves the path uncertain, calculate both cases and label the higher result.

    Electrical safety and codes

  • Explainer

    What PPE operators need to switch 480 V MCC disconnects

    Operators in non-arc-rated clothing may switch a 480 V MCC disconnect only where the bucket label shows 1.2 cal/cm² or less at the stated working distance, 18 in on most labels. A conventional latched door is not arc rated, so above that threshold whoever throws the handle wears arc-rated clothing rated at least the labeled incident energy, or the task moves to someone who has it.