Troubleshooting
Why a large motor reports 150 A earth fault during start
Short answer
When a large 11 kV motor reports an earth fault current above 150 A but the stator, rotor and feeder cables pass insulation tests, treat the event record as pointing to a false residual signal first: a fault that size leaves burn damage behind. Confirm the timing against the start, then check the relay sensing circuit, CT ratios and polarity, and the star-point grounding before changing any equipment.

On this page
- Is a real earth fault possible when the motor meggers clean?
- How much voltage drives an earth fault on an 11 kV system?
- Why does a motor start fake residual current in the CTs?
- What does the relay event record decide before you touch anything?
- Residual or balanced: which connection does the relay actually use?
- What earth fault setting rides through a motor start?
- Does the star point or the capacitor bank change the answer?
- Which tests confirm the motor and cables are healthy?
- Which decision follows from each outcome?
- Questions asked
A report of an earth fault current above 150 A on an 11 kV cement mill slip ring motor is, on the numbers, almost certainly not a genuine insulation failure. A fault carrying that current at phase-to-earth voltage burns terminations, marks the cable route and leaves the stator or the two parallel single-phase feeder cables failing their insulation tests. When those tests pass, the evidence points the other way: an apparent residual current manufactured inside the sensing circuit during the start, most often by unequal saturation of the three phase current transformers. Pull the relay event record first, then verify the CT circuit, the settings and the star-point grounding in that order, and replace no motor, cable or the 1500 kvar bank until the record tells you which case you are in.
Is a real earth fault possible when the motor meggers clean? #
Treat the report as a false indication until the evidence says otherwise: a real earth fault of that magnitude on an 11 kV machine burns terminations, marks the cable route and fails an insulation test, so clean megger readings make genuine damage the unlikely explanation.
A fault current of that size is a physical event, not a soft alarm: you would find a burned termination, tracking at a cable joint or a failed winding, and at least one insulation test would have gone low. Before deciding anything, establish what the value actually is. Ask three questions of whoever reported it: did the reading come from the relay's residual element, from an event record, or from a separate instrument; did the relay actually trip the feeder or only alarm; and what were the phase currents at the same moment. A symptom reported second-hand is not a measurement, and the whole investigation changes depending on which of the three it was. The same pattern, a motor that passes insulation tests yet operates its protection on start, shows up at low voltage too, as covered in Why a motor meggers good but trips the breaker on start.
How much voltage drives an earth fault on an 11 kV system? #
Every phase conductor on this feeder sits 6351 V above earth, because 11,000 V line to line divided by the square root of three gives 6351 V, and that phase-to-earth voltage, not the line voltage, is what drives any real earth current.
Earth current returns through whatever impedance the star point and the earth path put in the way, so the reported value has to be consistent with that loop. Worked example with the reported figures: 6351 V ÷ 150 A = 42.3 Ω of total earth-loop impedance. Compare that number with the star-point equipment: if the neutral is grounded through a resistor rated below the reported current, that current physically cannot flow to earth and the relay is misreporting. If the source is solidly grounded, 42.3 Ω of loop impedance describes a high-resistance fault at a termination or joint, and a fault carrying that current continuously leaves thermal damage an inspection will find. The result is an estimate that depends on the grounding arrangement, so read the neutral equipment nameplate before you judge the relay.
Why does a motor start fake residual current in the CTs? #
During a start the feeder carries several times rated current, and when the relay sums three phase current transformers, unequal saturation between them manufactures an apparent residual current even though no current physically leaves the conductors.
In the residual connection the relay computes the vector sum of the three phase currents, and that sum is only as good as the CTs behind it. A relay manufacturer's review of ground fault protection methods documents that in the typical residual connection, CT errors including angle errors can change the sign of the element's output, so the mechanism is documented rather than hypothetical. Worked example with illustrative inputs: for a 2 MW motor at 11 kV, rated line current is 2,000,000 W ÷ (1.732 × 11,000 V) = 105 A, and a start at six times rated draws about 630 A. The reported residual of 150 A is then 150 ÷ 630 ≈ 24% of the start current, so only a quarter of the phase current has to mismatch between CTs, which unequal saturation in the first cycles of a start easily produces. The saturation physics behind this is covered in Why CT saturation at the knee point cuts secondary current.
The timing signature is the tell: a false residual collapses as the start current decays, while real leakage persists at any load.
What does the relay event record decide before you touch anything? #
Read the relay event record before you reset or reconfigure anything: the timestamp, the pickup and trip outputs, the captured currents and the motor's operating state decide between a transient sensing error and a sustained real fault.
Work the record in this order:
- Read the timestamp and confirm whether the pickup indicator, the trip output or both operated.
- Pull the captured residual and phase currents from the event record and note how long the indication lasted.
- Compare that duration with the motor's start time: an indication confined to the starting window points to a sensing transient, while one that persists while running or stopped points to real leakage or a wiring fault.
- Record the capacitor bank's switching state during the event, because bank operations change the zero-sequence paths.
- Establish the source of the reported value — relay measurement, event record or separate instrument — before you quote it to anyone.
A trip during the start is a strong clue toward CT response, but it is a clue, not proof: an intermittent termination fault can also choose the start, when current and vibration are highest.
Residual or balanced: which connection does the relay actually use? #
The CT circuit drawings and the relay's configured input answer this on paper first: a residual connection sums three phase CTs and inherits their mismatch, while a core-balance CT threaded over all three conductors measures the earth return directly.
Before you open any terminal box or CT circuit on this feeder, de-energize, lock out and verify the absence of voltage under the site's high-voltage procedures, and never open a CT secondary circuit while primary current flows. Then confirm the sensing path on paper and on the terminals:
- The connection method as drawn: residual summation of three phase CTs, or a core-balance CT over all three conductors.
- The CT ratios and locations against the relay configuration; a residual connection with mismatched ratios produces a standing error even at load.
- Polarity of each CT and the wiring back to the relay input.
- Continuity of the residual path, and that the relay input is wired to match the physical arrangement.
A core-balance CT cannot inherit mismatch between phase CTs, which is why it is the usual fix for a feeder that misbehaves only during starts.
What earth fault setting rides through a motor start? #
Set the element to ride through the start without going blind to real faults: read the actual pickup and time delay from the relay, compare them against the measured start duration, and leave the pickup below the earth current your grounding method can deliver.
Read the settings from the relay rather than assuming them, then decide between the two common characteristics: an IDMT curve that lets the short start transient pass, or a definite-time delay set just above the measured start duration. Keep the pickup below the earth current the grounding method can deliver; if the star point is grounded through a resistor, a pickup above the resistor's rating blinds the element to every real fault that system can produce, which is the opposite of what a start problem justifies. Change one thing at a time, and after any change capture a start with the relay to prove the element holds off through the full accelerating current and still responds to an injection test.
Does the star point or the capacitor bank change the answer? #
The bank's reactive rating never fixes earth fault current; the star-point arrangement at the source does, because the grounding method and its earthing impedance cap how much current a genuine earth fault can carry.
A solidly grounded star point lets a real fault reach kiloampere-class currents; a resistance-grounded one caps it at the resistor's rated current; an ungrounded or high-resistance system limits it to capacitive charging current of a few amperes. Those cases differ by orders of magnitude, which is why the grounding method, not the motor and not the bank, sets what the relay should be allowed to report. The 1500 kvar bank belongs in the picture for its switching state and its contribution to zero-sequence charging current, but a reactive rating is not a fault-current number; get the grounding arrangement and the network extent at the point of common coupling instead. How relay sensing changes under resistance grounding is covered in Ground fault relay replacement for high resistance grounding.
Which tests confirm the motor and cables are healthy? #
The passing insulation tests are valid only for what was actually connected and isolated during each test, so record the equipment tested, the test voltage, the temperature and every reading before comparing them with anything.
Scope the tests to match the installation: the stator, the wound rotor circuit with its slip rings, leads and external resistors, and both parallel single-phase cables at both ends. Perspective on the contrast: at an example insulation resistance of 100 MΩ, the phase-to-earth voltage drives only 6351 V ÷ 100,000,000 Ω ≈ 0.06 mA of leakage, six orders of magnitude below the reported current, which is why healthy readings and a fault of that size cannot both be true. Interpreting a low-but-not-failed reading on a medium voltage machine after a trip is covered in Why a 6.6 kV motor reads 4 MΩ after an earth fault trip. Test the cables separately from the motor so a cable result never masks a stator result.
Which decision follows from each outcome? #
Each outcome of the checks above leads to a different decision, and you should be able to name yours from the event record and the sensing checks before any equipment is replaced.
Name the case from the evidence:
- Indication confined to the start window, sensing circuit checks clean, insulation tests passing, no physical damage: false residual from unequal CT response. Correct the sensing or the delay, capture a start to prove stability, and return the feeder to service.
- Sustained indication while running or stopped, a value at or above the earthing resistor's rated current, or visible damage on inspection: treat it as a real fault. Isolate under the site's high-voltage procedures, sectional-test the stator, the rotor circuit and each parallel cable, and keep the feeder out until the fault is found.
- Records that cannot decide between the cases: hand the event record, the CT scheme and the test results to the site protection engineer before the motor or the bank is replaced.
Either way the sequence is the same: the record decides, the sensing circuit confirms, and equipment is changed last.
Questions asked
Can a motor pass a megger test and still have an earth fault?
Yes. A megger applies DC at a test voltage, while the motor in service lives with AC at operating voltage and switching surges, so a weak spot can pass the DC test and still break down under load. A pass also covers only what was connected during the test: a fault inside a joint, a termination left out of the test scope, or an intermittent weakness escapes it.
Does the slip ring rotor need its own insulation test?
Yes. A wound rotor is a separate three-phase winding with its own slip rings, leads and external resistors, and it can hold an earth fault that the stator tests never see. Test the rotor circuit separately with the rotor terminals isolated, and include the external resistor bank and its cabling in the scope so a stator pass never masks a rotor fault.
What decides how much earth fault current a real fault on this feeder can carry?
The star-point arrangement at the source, not the motor or the correction bank. Read the neutral equipment nameplate before judging the relay report.
Do the parallel single-phase feeder cables change the investigation?
They can. With two cables per phase the load current splits between them, so each cable, both ends and every joint belongs in the insulation test scope. A faulted conductor carrying part of the load can heat for a long time before it fails outright, and testing the cables separately from the motor keeps a cable result from hiding a stator result.