Explainer
Why CT saturation at the knee point cuts secondary current
Short answer
Saturation is one core effect, not two opposite behaviors. In a reactor the collapsing inductance is a series element, so current from the supply rises; in a loaded CT the same collapsing excitation branch is a parallel shunt that diverts secondary current, and the knee-point voltage marks where the diversion becomes severe.

On this page
- Why does a saturated CT deliver less current to the relay?
- Is the saturation physics different in a saturable reactor?
- What does the knee-point voltage tell you on an excitation curve?
- How much secondary voltage does a fault demand from the CT?
- Why does DC offset saturate a CT that passes the steady-state check?
- How do you keep a high-impedance bus zone stable through a through-fault?
- Can CT saturation explain a slow feeder trip?
- Questions asked
If a saturable reactor and a current transformer share the same iron, why does saturation make one draw more current and the other deliver less? It does not, really: saturation is one effect. The reactor's collapsing inductance is the series element between supply and load, so its current rises. A loaded CT's collapsing inductance is the excitation branch in parallel with your burden, so the current it swallows never leaves the CT and the relay sees less. That series-versus-shunt distinction is the whole puzzle. This article works through the CT equivalent circuit, the excitation curve and its knee-point voltage, a steady-state voltage-demand calculation, the DC-offset transient that saturates CTs which pass that calculation, and what saturation can and cannot explain when a feeder clears slowly.
Why does a saturated CT deliver less current to the relay? #
A saturated CT delivers less current because the collapsing excitation impedance sits in parallel with your burden: the turns ratio still forces the same secondary current, but most of it now flows through the CT's own magnetizing branch instead of out the terminals to the relay.
Model the CT as three parts. An ideal transformer carries the turns ratio. A magnetizing (excitation) branch sits in parallel with its secondary. The secondary winding resistance lies in series out to the terminals. The primary circuit, switchgear and cables included, behaves as a current source: it forces primary ampere-turns, and the ratio fixes the secondary current the ideal part delivers. That current then splits at the excitation branch. Well below saturation the branch impedance dwarfs the burden, so nearly all of it reaches the relay. As the core saturates, the branch inductance collapses, its impedance falls to the same order as the burden, and the split reverses: excitation current grows toward the full secondary current while terminal current falls, distorts, and loses whole portions of each half-cycle to the excitation draw.
Nothing on the primary side changed when that happened. Saturation does not put a series impedance in the fault path; it opens a shunt inside the CT, and your burden sits on the wrong side of that shunt.
Is the saturation physics different in a saturable reactor? #
No — the core physics is identical: saturation drops the permeability, the inductance falls, and so does the reactance; the difference is that the reactor is a series element while the CT's excitation branch is a shunt, so the reactor passes more current and the CT diverts current internally.
Saturation lowers permeability, and winding inductance follows L = μN²A/l, so a saturated core means less inductance and less inductive reactance, X = 2πfL. Both devices obey that chain, and the contradiction lives in circuit position, not in the iron. A saturable reactor is a series element between a voltage source and its load: when its reactance falls, the source pushes more current through it, I = V/X, and the rising current is exactly what you measure. A CT's magnetizing branch is a shunt across an ideal current source: when its impedance falls, it diverts current that was headed for the burden. Same curve, opposite placement.
| Device | Circuit position | What saturation changes | What you measure |
|---|---|---|---|
| Saturable reactor | Series with the supply | Reactance falls, so supply current rises | More current at fixed voltage |
| Loaded CT | Shunt across the burden | Excitation impedance falls, so current diverts internally | Less, distorted terminal current |
What does the knee-point voltage tell you on an excitation curve? #
The knee-point voltage marks where the excitation curve stops rising linearly and turns sharply: below it a few extra volts cost milliamps of excitation current, above it the same few volts cost amperes, so it sets how much secondary voltage the CT can develop before saturation.
To plot the curve, de-energize the switchgear, lock out and verify absence of voltage, short the secondary terminals, disconnect the burden, leave the primary open, then apply a rising voltage to the secondary from a test set and record excitation current against applied voltage (NFPA 70E, 2024 edition, frames the de-energize-and-verify program; confirm the details with your authority having jurisdiction). The plot climbs almost linearly through the linear region, bends through the knee, then turns nearly vertical as small voltage steps buy amperes of excitation current.
Standards pin the knee two ways. The ANSI/IEEE definition (IEEE C57.13) takes the point where a tangent to the curve sits at 45 degrees on log-log axes. IEC 61869-2 defines the knee-point voltage as the secondary voltage where a 10% increase in voltage produces a 50% increase in excitation current. Gapped cores bend so gradually that the tangent criterion relaxes to 30 degrees. Whichever definition your data sheet uses, the knee is the number that sizes the CT against your fault.
How much secondary voltage does a fault demand from the CT? #
Multiply the fault's secondary current by the total series burden: 24,000 A through a 1200:5 CT is 100 A, and 100 A into a 1.5 Ω burden demands 150 V, so a 300 V knee-point CT holds, a 100 V knee-point CT saturates.
The estimate is E_s = I_2 × Z_s: the excitation voltage the CT must develop equals secondary fault current times the total series impedance. Scope every ohm before adding. Winding resistance, lead resistance and the relay's current-path impedance all belong; a stabilizing resistor belongs only to high-impedance schemes and never mixes into a feeder CT's burden.
Worked example, all inputs declared as example values: a 1200:5 CT (ratio 240:1) on a feeder that can carry 24,000 A symmetrical, with 0.4 Ω of secondary winding, 0.6 Ω of leads and 0.5 Ω of relay impedance.
- Secondary fault current: I_2 = 24,000 A ÷ 240 = 100 A
- Excitation voltage demand: E_s = 100 A × 1.5 Ω = 150 V
The decision: choose a knee-point voltage above the demand with margin, and treat half the knee as the workable floor for symmetrical duty. A 300 V knee-point sits at exactly that floor here, while a 100 V knee-point is already below the 150 V demand and saturates before any DC offset enters. Excitation current is the error current, and keeping it near 10% of the 100 A at maximum fault is the budget relaying practice uses for ratio and angle error. The result is an estimate from design values; confirm the final CT against the manufacturer's excitation curve and the governing standard for the installation.
Why does DC offset saturate a CT that passes the steady-state check? #
A fully offset fault drives the core past its symmetrical demand within one half-cycle: worst-case closing gives about 1.6 times the symmetrical flux excursion, and with a primary X/R of 6 to 11 the DC component keeps pushing for several cycles, so saturation can arrive in one to two cycles.
Fault current arrives as symmetrical AC plus a decaying DC term, set by the closing angle and decaying with the primary time constant T_p = (X/R)/ω = (X/R)/(2πf). At 60 Hz, ω ≈ 377 rad/s, so X/R of 6 gives 6/377 ≈ 16 ms and X/R of 11 gives 11/377 ≈ 29 ms. The offset lives long enough to matter.
Flux is the time integral of secondary EMF, and with a resistive burden that EMF tracks the secondary current, so compare half-cycle areas of the current wave. A symmetrical wave integrates to 2I/ω per half-cycle; a fully offset wave integrated over the same first half-cycle gives πI/ω, a ratio of π/2 ≈ 1.6, and the unidirectional part keeps adding while it decays.
Now apply the previous section: the 150 V symmetrical demand sat at half the 300 V knee-point, which looked safe. The offset erases that margin in the first half-cycle and keeps pushing, so the core reaches the knee within the first cycle or two, mid-fault, while the primary fault is still near full value and the relay current collapses. Remanent flux left by the previous fault moves that moment earlier still. Closing angle governs how much offset you get, the same angle-dependent flux mechanism that point-on-wave switching manages in transformer work (Point-on-wave closing for transformer inrush reduction).
The decision for a high X/R feeder with a modest ratio: step the CT up one ANSI voltage class, from C200 to C400 (roughly 400 V of capability at 20 times rated secondary current), so the knee clears the offset demand, or accept saturation and specify relays that ride through it, which is the next section's problem. Do not fold the offset transient into one RMS number to compare with the knee; the quantity that decides is time-to-saturate on the actual burden, read from the manufacturer's excitation curve.
How do you keep a high-impedance bus zone stable through a through-fault? #
Matched ratios, matched knee-point voltages and a stabilizing resistor sized for the zone's worst through-fault keep a high-impedance bus zone stable: the healthy CTs must be able to force the through-fault current through the one saturated CT's collapsed impedance without developing relay operating voltage.
In an external fault every CT in the zone carries the through-fault current. When one CT saturates, its excitation branch collapses to a low impedance, and the healthy CTs' driving voltage then circulates current through that collapsed branch instead of through the high-impedance relay path. That circulation is what stability means here. Two things protect it: the stabilizing resistor's voltage setting, checked against what a healthy CT can develop above the lowest knee-point in the zone, and matched CTs across the zone, because one mismatched replacement with a lower knee-point drags the whole zone's margin down with it. The burden arithmetic behind that check is worked step by step in Motor differential CT saturation and C50 burden limits.
A reported retrofit shows which inputs decide the outcome: an 11 kV metal-clad board, a 34.5 kA fault level, a proposed 300 V knee-point, a 6 Ω secondary winding resistance and a primary X/R judged across the range used above. Those are exactly this article's variables, but the CT ratio was never reported, so the excitation voltage demand cannot be checked from the report alone, and the CT time constant quoted as 3 s needs its definition confirmed before it describes anything. Keep the winding's 6 Ω separate from lead, relay and stabilizing-resistor ohms; mixing scopes breaks the sum.
Relay design helps too: differential elements with a dual-slope characteristic reduce the effect of CT saturation at higher fault currents, and saturation detectors block or restrain operation on the distorted signature. That buys margin; it does not replace the knee-point-and-burden calculation for the zone.
Can CT saturation explain a slow feeder trip? #
Timing alone never proves saturation: a reported switchboard case cleared a 40 kA-rated feeder in 260 ms although contact separation began at 58 ms, which is a discrepancy worth investigating, but the proof has to come from event records and a saturation calculation on the actual CT and burden.
The mechanism is plausible on its face. The feeder CTs carried lower ratios than the bus-zone CTs while both saw the same primary fault, and a lower ratio means more secondary current for the same fault, more excitation voltage demand, and an earlier knee. A saturated feeder CT delivers a collapsed, distorted current on which an instantaneous element can underreach or chatter while the upstream incomer's backup clears instead.
Plausible is not proven, and the numbers set the size of the gap to explain: a two-cycle relay element plus a five-cycle breaker clears in about 33 ms + 83 ms ≈ 117 ms at 60 Hz, so roughly 200 ms of arcing time went unexplained. To close that gap, pull the relay event record and breaker operations, compute the excitation voltage demand for the feeder CT with its real burden, read the implied excitation current on the manufacturer's curve, and compare secondary waveforms if they were captured. Only then assign the delay, to saturation, or to pickup margin, breaker performance, or the relay element's own DC response.
Questions asked
Why must a CT secondary circuit never be opened under load?
The CT keeps forcing its ratio current regardless of burden. Open the secondary and that current has nowhere to go except the excitation branch, the core saturates every half-cycle, and the voltage across the open terminals can rise to levels that destroy insulation and endanger anyone at the cabinet. Short the secondary terminals before removing any burden, and treat every CT circuit as energized until verified dead.
Does the connected burden change a CT's knee-point voltage?
No. The knee-point voltage is a property of the core and the secondary winding, measured from the excitation curve with the primary open. The burden decides where on that curve the CT operates during a fault: a heavier burden pushes the operating voltage toward the knee sooner, but it does not move the knee itself. That is why the knee travels with the CT, not with the circuit.
What did the reported three-second CT time constant mean?
Treat it as unconfirmed until you know its definition. The three-second figure reported in one switchboard retrofit cannot describe the fault response that matters, because the primary circuit's DC decays with the primary time constant, roughly sixteen to twenty-nine milliseconds for the reported X/R range of six to eleven. A value like that more likely describes the CT's own magnetizing branch, not the fault. Ask for the definition and the measurement basis in writing.
Do all CTs in a high-impedance bus zone need the same knee point?
Yes, in practice. A high-impedance bus zone is only as stable as its weakest CT, so the zone CTs should share ratio, accuracy class and knee-point voltage, bought and maintained as a set. One CT replaced with a lower knee-point unit lowers the voltage every healthy CT can be counted on to develop, and the through-fault stability margin goes with it.