Troubleshooting
Why a motor starter feedback signal stays off with low current
Short answer
On the ET 200S fail-safe direct starter F-DS1e-x 2.4-16A HF, the Motor On input I 120.1 sets to 1 only when measured motor current exceeds 18.75% of the configured rated current — 3.0 A at a 16.0 A setting. A conductor-rail load drawing 2.1 A never crosses it, so the bit stays 0 with the contactor energized. Match the rated-current setting to the nameplate or take status from an auxiliary contact.
On this page
The signal is probably behaving exactly as designed. On the ET 200S fail-safe direct starter F-DS1e-x 2.4-16A HF — the High Feature, current-configurable variant of the family — the feedback input the manual calls Motor On, I 120.1 in the process image, does not follow the contactor coil. It sets to 1 only when the starter measures motor current greater than 18.75% of the configured rated current, and it drops back to 0 below that. A light conductor-rail load can run forever under the threshold, so the bit stays at 0 while the contactor sits pulled in. Compute 0.1875 times the configured rated current, measure the real running current, and you can separate documented threshold behavior from a genuine fault in a few minutes.
What the Motor On bit reports #
The manual for this starter family documents the process image input as two bytes wide: with the module configured at byte 120, the image runs I 120.0 to I 121.7, and I 120.1 carries Motor On — 0 = Off, 1 = On. The turn-on criterion in the same tables is a current comparison, not a contact position: the bit goes to 1 when the measured motor current exceeds 18.75% of the set rated current. The electronics get that measurement by sampling the running current on all three phases; there is no auxiliary contact behind the bit.
That makes Motor On a current-only signal, with the blind spots that class of logic always carries — what current-only motor protection can and cannot detect covers them for the broader case. It reports "the motor is drawing meaningful run current." It does not report "the contactor closed." A load too light to cross the threshold holds the bit at 0 with the contactor energized, and that is the documented response, not a defect.
Compute the turn-on threshold #
The formula is:
I_on = 0.1875 × I_rated,configured
Both currents are in amperes. The 18.75% factor comes from the starter family's own documentation, and the same lower-limit rule appears across this class of fail-safe starters; the manual for your exact model is the authority for the number. Use the configured rated current — the value in the starter's parameter set — never the product's 2.4 A to 16 A range limits in its place.
Worked example, with illustrative inputs: a conductor-rail transfer car on a starter configured at 16.0 A, the top of the range, running steadily at 2.1 A per phase on a true-RMS clamp ammeter.
- Threshold: 0.1875 × 16.0 A = 3.0 A
- Running current 2.1 A is below 3.0 A, so I 120.1 stays 0 the whole time the car runs
- The contactor is pulled in and nothing is broken
If the car motor's nameplate full-load current really is about 2.1 A, set the configured rated current to 2.4 A, the bottom of this starter's range. The threshold becomes 0.1875 × 2.4 A = 0.45 A, the load now sits about 4.7 times above it (2.1 A ÷ 0.45 A), and the bit asserts on every run. That setting also drives the starter's electronic overload protection, so it must still match the motor's full-load current — the same discipline as setting overload relays from motor nameplate full-load current.
For quick reference, the threshold at four settings in the range:
| Configured rated current | Turn-on threshold (0.1875 × setting) |
|---|---|
| 2.4 A | 0.45 A |
| 4.0 A | 0.75 A |
| 8.0 A | 1.50 A |
| 16.0 A | 3.00 A |
Why conductor-rail loads land under the threshold #
On conductor-rail systems the starter is sized for the rail's ampacity and the starting current, not for the modest current a transfer car, monorail hoist or light door draws while running. The configured rated current therefore ends up several times the running current, and 18.75% of it can sit above running current too — in the worked example, 3.0 A against 2.1 A, a 30% shortfall rather than a marginal one. The field workaround for this exact symptom is to jumper the feedback so the controller always sees it. Do not carry that forward: a bridged input deletes the only confirmation that the motor is actually running, and on a fail-safe starter it can take out a feedback path a safety function relies on. The two legitimate fixes keep the signal honest.
Work the list before you call it a fault #
Before you open the panel to probe a coil terminal or an auxiliary contact, de-energize, lock out and verify absence of voltage; the clamp-meter reading on the running load is the one measurement that needs the panel closed.
- Command the starter on and confirm the contactor actually picks up — coil voltage present at the coil terminals, audible pickup. No pickup means the problem is in the command path, not the feedback.
- Check the input allocation in the hardware configuration. The documented image is two bytes: at start address 120, I 120.0 to I 121.7. A one-byte reservation covering only I 120.0 to I 120.7 leaves the documented image partly unmapped — reserve both bytes.
- Read the configured rated current from the starter's parameter set.
- Compute the threshold: 0.1875 × the configured value, in amperes.
- Measure the running current on each of the three phases with a true-RMS clamp ammeter while the load runs steadily; on a healthy motor the phases read close together.
- Compare and classify. Current above the threshold with the bit still at 0 is a genuine fault — re-verify the module's start address against the configuration and the manual's tables, then follow the vendor's service route. Current below the threshold with the contactor pulled in is documented behavior — apply one of the fixes below.
The decision for each case #
- Load runs below the threshold and the nameplate allows it: set the configured rated current to the motor's actual full-load current — 2.4 A on this model puts the threshold at 0.45 A — and Motor On becomes a usable run signal. Confirm the overload still protects the connected motor at the new setting.
- No honest setting can cross the threshold — nameplate full-load current above the lowest setting, or runs too brief: leave Motor On for what it reports and take contactor status from an auxiliary contact on a standard digital input. The wiring pattern is the same one that brings overload relay contacts to the coil and the PLC.
- One-byte input allocation: reserve both bytes of the documented image, I 120.0 to I 121.7.
- Current above the threshold, contactor confirmed pulled in, addressing verified, bit still 0: treat it as a starter fault and follow the vendor's documented service route.
End state: a feedback bit that either asserts on real run current, or is replaced by an auxiliary contact that tells the truth about the contactor's position.
Questions asked
Is I 120.1 proof that the contactor physically closed?
No. The bit is current-dependent: it sets to 1 when measured motor current exceeds 18.75% of the configured rated current and to 0 below that. It confirms the motor is drawing run current, not the contactor's mechanical position. When you need positive position proof, wire an auxiliary contact to a standard digital input and keep Motor On for run-current supervision.
What if the configured rated current cannot be set low enough?
On the F-DS1e-x 2.4-16A HF the setting stops at 2.4 A, which puts the turn-on threshold at 0.45 A. If the motor's nameplate full-load current sits above that, the setting cannot go lower, and dropping it below the nameplate would mis-set the overload protection. Use an auxiliary contact for contactor status instead.
Why does the input image need two bytes when Motor On is in the first?
The manual documents the starter's process image input as two bytes wide; at start address 120 it runs I 120.0 to I 121.7, and the remaining documented status positions extend through the second byte. Reserving only I 120.0 to I 120.7 leaves part of the image unmapped in the hardware configuration, so configure the full two-byte range the tables show.
Do newer fail-safe motor starters use the same 18.75% rule?
The current-dependent run feedback concept carries into the newer ET 200SP fail-safe motor starter family (3RK1308 series). Its manual has an Operating motor starters section and designates the fail-safe input on the BaseUnit as F-DI. Confirm the turn-on threshold in that series' own manual rather than assuming the 18.75% figure transfers.
The original integrator jumpered the feedback. Is that acceptable to leave in place?
No. A bridged feedback input hides the exact condition the signal exists to report, and on a fail-safe starter it can defeat a feedback path a safety function relies on. Restore the wiring and use a documented fix instead: a configured rated current that matches the motor's full-load current, or an auxiliary contact on a standard digital input for contactor status.