Short answer

A molded-case breaker trips from its own integral trip unit; a protection relay can open it only through a fitted shunt trip coil at that coil's rated control voltage. The MCCB's fixed instantaneous override stays armed whatever the relay is set to, because an MCCB carries no short-time withstand rating. Read the override from the trip curve and coordinate below it, or use a breaker with a short-time withstand rating when a delay is unavoidable.

On this page
  1. What a relay can and cannot drive on an MCCB
  2. The shunt trip coil is the only path in
  3. Why the instantaneous override stays armed
  4. Worked example: a 120 V AC shunt trip and its 66 V floor
  5. When the external relay earns its place
  6. Verifying the trip path before you rely on it
  7. Questions asked

A multifunction protection relay does not take over a molded-case circuit breaker the way it drives a power circuit breaker. The MCCB trips from its own integral trip unit, and an external relay can open it only through a shunt trip accessory fitted to that exact frame and control voltage. The relay never replaces the integral protection either, because the breaker's fixed instantaneous override stays armed whatever the relay settings say. One extra trip path, one unstoppable fast trip: that combination decides how the interface is built and how the coordination study is written.

What a relay can and cannot drive on an MCCB #

On a low-voltage power circuit breaker, the relay is effectively the trip brain. Its output drives the breaker's trip mechanism, and because the manufacturer assigns that class of breaker a short-time withstand current, the breaker can stay closed through a deliberate relay delay while a downstream device clears the fault. That withstand rating, published as Icw, is the current the equipment is assigned to carry for a stated short time, and it is what makes delayed, selective tripping possible on switchgear-class breakers. The contrast with the equipment around them is set out in switchboard short-time withstand ratings versus LV power breaker coordination.

An MCCB gives you neither of those behaviors. A relay output contact has nothing to drive unless the breaker carries the optional shunt trip accessory, so a relay ordered without it produces the first symptom people report: the relay picks up, its output closes, and the breaker stays closed. The second behavior shows up as trips you cannot delay. You set a relay curve with a defined delay at high fault current, and the breaker still opens instantly at a fixed level, because its integral instantaneous element never left the circuit.

The shunt trip coil is the only path in #

The shunt trip is an accessory ordered for the specific breaker frame at a specific rated control voltage; 24 V DC, 48 V DC and 120 V AC are the ratings manufacturers' accessory ranges commonly offer. When the relay trip output closes, the coil energizes, releases the breaker's latch, and the contacts open. Because the coil is rated for momentary duty, an auxiliary contact, wired per the accessory instructions, interrupts the coil current once the breaker has opened; continuous energizing cooks the coil. The logic is energize-to-trip, so loss of control power removes the relay path. If the scheme must trip on loss of voltage, that is a different accessory, an undervoltage release, with the opposite logic.

Size the trip supply from the accessory datasheet's maximum absorbed power, which for one molded-case accessory family is 5 W at 24 V DC, and feed the coil from a supply that holds up through the fault. A coil supplied from the bus the fault depresses cannot trip the breaker at the moment it matters most. Give the trip path a secured control supply, independent of the circuit being cleared.

Why the instantaneous override stays armed #

IEC 60947-2, the product standard for low-voltage circuit breakers, assigns each breaker a utilization category: category B breakers carry a rated short-time withstand current and may delay under short-circuit conditions for selectivity, while category A breakers, the class typical MCCBs fall into, may not. Without a withstand rating there is nothing to coordinate against, because the breaker is built to interrupt, not to carry fault current while a delay runs. Molded-case breakers listed to UL 489 in North America are likewise rated to interrupt a fault rather than to carry one through a deliberate delay. Confirm the category and the ratings for your breaker against its own documentation and the local authority having jurisdiction.

That is why the override exists, and why it is not a coordination nuisance you can remove: the fixed instantaneous clears fault currents beyond what the breaker's contacts and mechanism can be expected to carry. Manufacturer documentation describes it as a fixed, non-adjustable trip that opens the breaker in under 25 ms on faults above its setting. Where the magnitude sits is frame-specific. One coordination reference places it typically at a maximum of about ten times the breaker's rated current, while the selection guide for one molded-case family activates it at twelve times rated current or greater. The multiplier does not transfer between frames, so read the time-current curve for the exact catalog number and trip unit.

Two practical consequences follow. On insulated-case families that let you switch the adjustable instantaneous off, the fixed override remains, and it can sit surprisingly close to the top of the adjustable range; read it from the curve, never from the dial. Any relay short-time delay is also dead above the override level, because the breaker opens at the override before the relay's delay can matter, so both curves belong in the coordination study side by side.

Setting adjacent instantaneous functions so the breakers coordinate instead of racing each other is covered in setting instantaneous trips for low-voltage coordination between breakers. Removing or lowering the instantaneous function to trim incident energy is not an option here, and the caution extends upstream, where why an upstream instantaneous setting may not cut arc flash sets out what such settings can and cannot deliver.

Worked example: a 120 V AC shunt trip and its 66 V floor #

The inputs, each with its source:

  • Rated coil voltage: 120 V AC, the accessory's rated control voltage from the shunt trip accessory data.
  • Minimum operate threshold: 55% of the rated coil voltage, the figure that manufacturer publishes for its 120 V AC shunt trips.
  • Coil-terminal reading during a trip test: 74 V, an example reading for illustration, not a specification.

The rule: a shunt trip fires only while the voltage reaching the coil stays above its operate threshold, and control voltage sags on exactly the faults the relay exists to clear. The published threshold therefore sets the floor the trip supply must hold, and the trip test measures the real margin.

The arithmetic:

  • Minimum operate voltage: 0.55 × 120 V = 66 V
  • Sag budget below nominal: 54 V
  • Margin at the example reading: 74 V - 66 V = 8 V

The illustrative reading passes, but with only 8 V of headroom. A long control-circuit run, a loaded control transformer or a deep sag on a weak source consumes that quickly.

The decision: at or above 66 V at the coil terminals during a trip test, the relay path is valid. Below 66 V, the coil does not fire and the relay cannot open that breaker, whatever its indicators show. If the margin is thin, move the coil feed to a secured control supply; do not fix it by weakening the relay settings, because the settings were never the problem.

When the external relay earns its place #

In most applications the integral trip unit is enough: it already provides the long-time and instantaneous protection, and often a short-time function as well, while the external relay adds wiring, a control-supply dependency and commissioning time. The relay is justified when the coordination scheme needs settings the trip unit does not offer, such as a lower pickup, a defined delay or a curve shape the trip unit cannot produce.

Before ordering, work through five checks:

  • Compare the settings the scheme needs against the integral trip unit's adjustments, including the adjustable instantaneous function; what the Im setting on an MCCB trip unit means covers that function in detail. If the trip unit already covers the need, stop here.
  • Read the fixed override from the trip curve for the exact frame and trip unit, and plot it against the available fault current at the breaker location.
  • Order the shunt trip accessory listed for that frame and your control voltage, never a coil from another frame.
  • Wire the relay output to the coil with the auxiliary cut-off, per the accessory instructions, from a control supply that survives the fault.
  • Document that the integral trip unit remains active, and put its curve in the coordination study next to the relay's.

Verifying the trip path before you rely on it #

De-energize, lock out and verify the absence of voltage before removing terminal covers or wiring the coil. NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, sets out the safe work practices and risk assessment for this kind of work, and the applicable requirements should be confirmed with the local authority having jurisdiction and the equipment documentation.

With the power side isolated and the control supply healthy, close the relay trip output, by secondary injection or the relay's own test function, and measure the voltage at the coil terminals. Confirm the breaker opens and the auxiliary contact removes coil power. Repeat the test at the lowest control voltage the supply can deliver in service, because coil voltage drop under load is the most common cause of a missed trip.

Confirm the integral protection with the breaker manufacturer's test method: primary injection where the frame allows it, checked against the published curve. Record the as-found trip value and compare it with the value the coordination study used. If the breaker stays closed while the relay output operates, work down the list: no shunt trip fitted, coil voltage below its threshold, auxiliary contact miswired, or a control supply that collapses on the trip pulse.

When the trip test, the override check and the control-supply review all pass, the installation is fit to rely on. When any one fails, fix that item before returning the breaker to service, and remember that the breaker's own trip unit has been protecting the circuit the whole time either way.

Questions asked

Can I switch the instantaneous trip off when a protection relay sets the delays?

No, not reliably. Utilization category A breakers carry no short-time withstand rating, so the fixed instantaneous override stays in service even on families whose adjustable instantaneous function can be switched off. Manufacturer literature typically places the override near ten to twelve times the breaker's rated current, but the value is frame-specific. Read it from the time-current curve for the exact catalog number and coordinate below it.

How fast does the instantaneous override trip?

The override is fixed and non-adjustable, and manufacturer documentation describes it as opening the breaker in under 25 ms on faults beyond its setting. No relay short-time delay can beat that, so selectivity above the override level is not achievable with a molded-case breaker. Where a deliberate delay must ride through a downstream fault, the equipment to use is a power circuit breaker with a rated short-time withstand current.

What control voltage does a shunt trip coil need?

Coils are ordered for a specific rated control voltage; 24 V DC, 48 V DC and 120 V AC are common accessory ratings. The operate threshold is published in the accessory data. One manufacturer gives 55 percent of rated voltage for its 120 V AC shunt trips, a floor of 66 V. Size the control supply for the coil's maximum absorbed power and feed the trip path independently of the circuit being cleared.

When is an external protection relay worth fitting to an MCCB?

In most applications the integral trip unit already gives the circuit the protection it needs, and an external relay adds wiring, a control-supply dependency and commissioning time. It earns its place when the coordination scheme demands settings the trip unit does not offer. Before ordering one, confirm the breaker frame has a matching shunt trip accessory and read the fixed instantaneous override from the trip curve.

Does losing control power disable the protection?

Only the relay path. The shunt trip is energize-to-trip, so with the control supply down the relay can no longer open the breaker; the integral trip unit keeps working on its own, because it operates the mechanism mechanically without depending on control power. Source and size the trip supply so it survives the faults the relay is meant to clear, and treat loss of control power as a protection gap worth reviewing.

Keep reading

  • Troubleshooting

    What the Im setting on an MCCB trip unit means

    Im is the instantaneous magnetic pickup of an MCCB trip unit — the current above which the breaker trips with no intentional delay. Set the dial so the worst starting transient stays below the pickup's lower tolerance bound, the minimum fault current sits above the upper bound, and the frame's interrupting rating covers the available fault current; the worked example lands at 5 × In, or 1250 A.

    Protection: breakers, fuses and SCCR

  • Selection guide

    Setting 50 and 87 functions on a fused medium voltage motor starter

    On a NEMA Class E2 fused starter the current-limiting fuses are the short-circuit interrupter, so the phase 50 element defaults to alarm-only or disabled unless the coordination study and the contactor's interrupting rating support tripping. The 87 element follows the same test through its differential zone. Ground fault is separate: on an HRG 4.16 kV system with a core-balance CT and about 25 A or more of available ground-fault current, set 50G.

    Protection: breakers, fuses and SCCR

  • Troubleshooting

    Why differential trips on transformer inrush but overcurrent does not

    Differential compares the current entering a zone with the current leaving it, so energizing an unloaded transformer is genuine differential current while a brief inrush from a small transformer stays under the generator's overcurrent criteria. Pull the sequence-of-events record to learn whether 87G or 87T operated, verify the transformer differential's second-harmonic blocking, and recheck CT compensation after the replacement before changing any setting.

    Protection: breakers, fuses and SCCR