Troubleshooting
Why a servo axis trips motor overload only on cold start
Short answer
A servo axis that trips motor overload only on the cold morning start is usually the axis amplifier card, not the motor. Swap the card with a known-good axis: if the fault moves, replace and re-tune the card; if it stays, megger the motor leads to ground with the amplifier disconnected and judge by the reading bands.
On this page
- What the cold-start pattern tells you
- Run the amplifier card swap test
- Check the current-limit pot and re-tune before condemning the card
- Example: splitting an 8 MΩ reading between motor and cable
- Megger the leads with the amplifier disconnected
- Other cold-start causes to rule out
- The decision for each result
- Questions asked
One axis that trips a motor overload fault only on the cold morning start, and clears once the machine has run for about an hour, points at the axis amplifier card first, not the motor. Swap that axis's amplifier with a known-good neighboring axis before ordering anything else: if the fault moves with the card, the card is the problem, and its current-limit pot and tune must be checked before and after the swap; if the fault stays, megger the motor circuit to ground with the amplifier disconnected. Above 100 MΩ is a good reading and below 10 MΩ is a failed one. The sections below give the swap procedure, the reading bands, a worked example that splits a marginal reading between motor and cable, and the decision each result leads to.
What the cold-start pattern tells you #
The fault appears the moment the axis is selected, before the motor turns a single revolution, while the other axes jog normally. That confines the problem to one axis circuit and rules out a machine-wide control failure. A motor overload indication is the amplifier's protection circuit reacting to current it measures or believes it sees; it is not by itself proof of mechanical binding or an overheated motor. Genuine winding heating follows I²R and accumulates over seconds to minutes of current flow, so a trip at the instant of enable is an electrical event: insulation leakage that rises when the machine is cold and damp, or an amplifier whose measurement or protection circuitry misbehaves at low temperature. Record the trip timing as you troubleshoot. A trip before motion points at the amplifier, the enable circuit, the wiring and the insulation; a trip that appears under acceleration or load adds mechanical drag and excess current demand to the list.
Run the amplifier card swap test #
The swap is the fastest way to divide the problem in half while leaving the motor, cable and mechanics in place:
- De-energize the cabinet, lock out, and verify the absence of voltage at the amplifier terminals before opening anything. NFPA 70E, the standard for electrical safety in the workplace, 2024 edition, covers the practices for this kind of work; confirm the requirements with the authority having jurisdiction and the machine documentation.
- Label both amplifier cards, then swap the faulting axis's card with a known-good neighboring axis's card, or swap the motor output connections at the amplifiers where the design allows it.
- Repower and reproduce the failure exactly as it happens: cold machine, first start of the morning, axis select.
- The fault now appears on the other axis: the exchanged card, or its setting, carries the fault.
- The fault stays on the original axis: the motor circuit, meaning the cable, its connections or the motor itself, carries it.
- Change one variable at a time. Swapping cards and cables together destroys the interpretation.
Check the current-limit pot and re-tune before condemning the card #
Before ordering a replacement, verify the adjustment. Many analog servo amplifier cards carry an edge-mounted turnover pot labeled Cur or Gain that sets the current limit, and cards have shipped from the factory below full setting or been turned down during earlier service. Set it fully clockwise as the manual describes before you condemn the card. And whenever an amplifier moves to another slot or a new one goes in, re-tune the axis following the manufacturer's axis drive manual so the card's current loop and limits match the machine; an untuned card can fault on its own and muddy the diagnosis you just finished.
Example: splitting an 8 MΩ reading between motor and cable #
Inputs, all from the faulting machine tested cold, amplifier leads disconnected:
- Combined motor-plus-cable insulation resistance to ground, one-minute reading at the test voltage the machine documentation specifies: 8 MΩ.
- Interpretation bands from amplifier service guidance: readings below 10 MΩ are treated as failed on this class of axis, healthy windings read thousands of megohms, and a minimum of 5 MΩ at 40 °C, one-minute reading, is the commonly quoted floor for a random-wound machine.
- After disconnecting the motor leads from the harness at the motor junction box, each motor lead to the motor case reads 4000 MΩ.
Rule: leakage paths from a conductor to ground sit in parallel, so their resistances combine like parallel resistors: 1/R_combined = 1/R_motor + 1/R_harness, all values in megohms.
Arithmetic:
- 1/8 = 0.125
- 1/4000 = 0.00025
- 1/R_harness = 0.125 − 0.00025 = 0.12475
- R_harness = 1 / 0.12475 ≈ 8.0 MΩ
Result: essentially the entire leakage lives in the cable; the motor alone is healthy by a wide margin.
Decision: the combined reading sits in the failed band and the motor measures clean, so repair or replace the harness and leave the motor in place. After the repair, retest the combined circuit cold and expect the reading back in the good band before returning the machine to service.
Megger the leads with the amplifier disconnected #
An insulation tester pushes a high DC test voltage out its leads, and applied through a servo amplifier it will destroy the output stage. Disconnect at both ends: the motor conductors at the amplifier, and at the motor when you split the circuit. Keep any other electronics out of the test circuit per the machine schematic. Then:
- Lock out, verify absence of voltage, and let the drive bus discharge for the wait time the drive manual specifies.
- Remove and label the motor-circuit conductors at the amplifier before testing.
- Test each conductor to ground one at a time, and record the test voltage, the one-minute reading, and whether the machine was cold or warm.
- Read the bands: above 100 MΩ is good; 10 to 100 MΩ is questionable, so dry the machine out and retest before deciding; below 10 MΩ treat the circuit as failed and split it at the motor as in the worked example above.
- Screen continuity separately with an ordinary ohmmeter: conductor to conductor at the amplifier end should read a few ohms, about 1 Ω to 3 Ω on the machine in this case, a screening figure for that installation rather than a general servo specification. An open or high reading means a circuit problem: inspect the connectors and measure again at the motor terminals. An ohmmeter's low test voltage never replaces the insulation test, and a motor that passes a static continuity check can still leak at operating voltage.
- Discharge the tested conductors with the tester's prescribed method before reconnecting anything.
A drive that still trips even when bench insulation numbers look acceptable is its own pattern, and the article on VFD ground fault trips when insulation tests pass works through why a passing reading does not clear a drive-side fault. For the line-side version of a motor that passes a static test yet trips protection under power, see why a motor meggers good but trips the breaker on start.
Other cold-start causes to rule out #
- Enable path leakage: with control power on but before the run command, check whether the amplifier cards are already energized. On some machines the cards sit behind an enable contactor or solid-state relay, and a relay that leaks when cold can hold an axis in a faulted enable state until the cabinet warms; the documented startup sequence and the schematic show whether yours does this.
- Moisture and contamination in the motor junction box: inspect the terminations for corrosion, coolant residue and leakage paths, and keep the box sealed and dry.
- Supply quality at the drive: a voltage reading taken back at the panel means little on its own, so measure at the drive during axis enable and compare the result against the machine's specified operating band.
The decision for each result #
- Fault moves with the card: replace the amplifier card, confirm its current-limit pot is at full setting, and re-tune the axis per the manual before returning the machine to service.
- Fault stays, the combined reading is in the failed band, and the motor side of the split is clean: repair or replace the cable or harness.
- Fault stays and the motor side of the split fails: rebuild or replace the motor.
- Fault stays and every insulation reading is in the good band: re-tune the axis, check the enable path for a cold-leaking relay or contactor, and if it still trips, capture the axis current at the first cold motion command to look for mechanical drag.
Questions asked
What megger readings count as good on a servo motor and its cable?
Above 100 MΩ is a good one-minute reading. Between 10 and 100 MΩ is questionable: dry the machine, retest cold, and watch for fluctuating values. Below 10 MΩ treat the circuit as failed and split motor from cable at the junction box to find which side leaks. A minimum of 5 MΩ at 40 °C is sometimes quoted for random-wound machines, but a healthy servo reads far higher.
Why does the fault clear after the machine warms up?
Cold, damp windings and cold electronics behave differently: condensation on a machine that sat overnight raises leakage current across insulation, and marginal amplifier components can misbehave at low temperature. As the cabinet and motor warm, the leakage path dries and the marginal component drifts back into range. That is why the diagnosis has to be reproduced cold; a test made after an hour of warm-up reads healthy and misses the fault.
Do I have to re-tune the amplifier after swapping cards between axes?
Yes. Moving an amplifier to a different slot or fitting a new card changes the match between the card's current loop and the axis, so the manufacturer's axis drive manual procedure must be run after any swap or replacement. Until it is tuned, current limits and protection behavior differ from the machine's setup, and the swapped axis can fault or perform poorly for reasons unrelated to the original fault.