Troubleshooting
Why a servo motor burns one winding despite drive protection
Short answer
One destroyed winding with two intact ones is the single-phase burn signature: an open in one phase of the motor circuit while the axis stayed commanded. The drive's thermal model protects the winding only when it is enabled and its rated-current entry matches the motor nameplate. Find the open in the terminations, cable or connector first; the working second motor on a shared double module proves nothing about the suspect channel.

On this page
One destroyed winding with the other two intact is the classic single-phase burn signature, and it points first at an open in one phase of the circuit between the drive's output and the winding — not automatically at the power stage. The case behind this article: a 1FK7032-2AK71-1CA0-ZX01 servo motor on a double motor module 6SL3120-2TE15-0AXX with control unit 6SL3040-1MA01-0AXX in a SINAMICS S120 system, one winding burnt out, the second motor on the same module still running. A drive protects that winding with a calculated thermal model, not a fuse sized to the copper, and the model acts only when it is enabled and its rated-current entry matches the nameplate. What follows: why the protection can watch this happen, how to find the open phase before any motor is connected, and what the healthy second motor does and does not prove about the module.
One burnt winding is the open-phase signature #
Stator-winding failure guides from the Electrical Apparatus Service Association describe a single-phased winding failure as the result of an open in one phase of the supply circuit, with blown fuses, failed contactor poles and loose or corroded terminations as the usual openings — for the contactor version, see why only one contactor pole burns on a small motor. One destroyed winding between two intact ones fits that description: the load current keeps flowing through whatever phase path survives, and because winding heating rises with the square of the current, the windings left in that path cook while the motor's total power draw barely moves. Nothing upstream sees an overcurrent, so nothing upstream trips.
Where the open lives is anywhere in the output circuit: the terminations in the motor terminal box, the cable conductors and their connector pins, or one phase of the drive's own output path. Note the difference from a line-started machine: a three-phase motor fed from the line cannot accelerate from standstill on two phases, but an axis under closed-loop control has no stall to save it — the regulator keeps driving current through the remaining path for as long as torque is commanded, so the run continues until protection acts or the insulation fails.
Why the drive's thermal model did not act #
The thermal motor protection documented for this drive family is a software model, not a stator sensor: the function manual describes it as monitoring motor temperature and responding to overtemperature with alarms or faults, and the manufacturer's application note on additional motor protection states that the I²t model adds protection beside the temperature sensor in the case of excessive single-phase current. That is precisely the mechanism aimed at this failure.
The model computes thermal utilization from the measured output currents and the configured motor data. It is only as correct as that data and only as active as its enable: a model whose rated-current entry does not match the winding never reaches its trip threshold, and a model that is switched off does not watch at all. The same rule holds one technology over — a soft starter protects against single phasing only if that function is enabled — and it sits inside the broader limits of what current-only motor protection can and cannot detect: current-based protection responds to the currents it measures and the data it holds, not to the actual temperature of the copper.
The decision: an enabled model with nameplate-correct data trips before a winding burns. This winding burned, so treat the model as disabled or mis-fed until the drive's own records prove otherwise. Read the fault and alarm history before touching any setting — it is the only record of what the protection saw — and check the I²t configuration against chapter 9.5 of the S120 function manual, which documents thermal motor protection for this family.
Worked example: a data set entry that doubles the rating #
These are illustrative values, not this motor's nameplate. Suppose the motor's nameplate lists 10 A continuous rated current and the drive's motor data set holds 20 A — an entry carried over from a larger motor commissioned on the same hardware. At the nameplate load the winding carries 10 A, but the model computes thermal load from the square of the measured current divided by the configured current: (10 / 20)² = 0.25. The model concludes the winding sits at a quarter of its thermal capacity, so its computed temperature creeps and never reaches the trip point while the real insulation ages at full rated heating. That configuration acts only near 20 A, twice the nameplate value.
Run the mismatch the other way: a data set holding 5 A on the same motor computes (10 / 5)² = 4, and the drive trips long before the winding warms. The entries that survive commissioning are the ones that never nuisance-trip — which is exactly how a doubled rating ends up protecting nothing. The check takes minutes: the nameplate rated current against the data set entry on the affected axis, and the same check on the second axis before anyone trusts it.
Find the open before the replacement goes in #
Safety gate first: lock out and de-energize the drive, wait out the capacitor discharge interval stated in the drive's documentation, and verify absence of voltage at the terminals before anything is opened. Shops working to NFPA 70E, the 2024 edition, will find the de-energize-and-verify process there; where IEC-based national rules govern, follow those — and confirm the exact requirements with your authority having jurisdiction and the equipment documentation.
- Read and record the fault and alarm history before anything else; clearing the buffer destroys the evidence.
- Disconnect the motor leads at the terminal box and continuity-test each cable conductor end-to-end. Flex the cable hard near the connector while measuring: a cable that failed in a moving axis can read continuous at rest and open under flex.
- Inspect both ends of every connection — module output terminals, connector pins, terminal-box links — for looseness, discoloration or a pin that is not fully seated. A loose termination can run hot enough to fail open without any breaker trip; the mechanism is the one behind why loose motor terminals burn with no breaker trip.
- At the motor face, measure the resistance between each pair of phases and compare the three readings; what a multimeter shows about three-phase motor winding resistance covers how to read them. On the burnt motor expect the damage to show; on the replacement, the three readings should agree before it is connected.
What the healthy second motor proves about the module #
The second motor on the 6SL3120-2TE15-0AXX proves the shared power-unit electronics were at least partly functional when you looked, and nothing more: a double module gives each axis its own output channel, and the two channels do not share their health.
Discriminate with resistance before energizing anything. With the cable still connected to the burnt motor and the system verified dead, measure the three phase pairs at the module's output terminals: one pair reading open with two continuous places the open in the winding between that pair, while two pairs open with one continuous names a broken conductor — and clears the module. All three pairs open means conductor and winding are both gone. When the cable and terminations test clean, the open-phase evidence no longer points at the cable, and the documentation at hand publishes no bench test for a motor-module channel; do not hang a new motor on an unverified channel. Take the captured fault history through the manufacturer's documented service channel and use their verification procedure for that module before reuse.
Bringing the replacement online #
Before the first run, verify the configured motor designation and data against the replacement's nameplate and ordering data. If they differ, run the drive's documented motor identification — the S120 function manual places it in chapter 4.12 — and enter the nameplate rated current so the I²t model is fed real data. After commissioning, run the axis under load and confirm no phase or thermal alarms and normal heating.
The decision, end to end: an open in one phase burnt this winding, so find it in the terminations, the cable or the connector with the sequence above; verify the thermal model is enabled with nameplate-correct data on the affected axis; and only then bring the replacement in, on a channel that has passed the resistance test or been cleared through the manufacturer's documented service procedure.
Questions asked
Doesn't the winding temperature sensor stop this?
Only if the sensor circuit is wired through to the drive and its monitoring is enabled. A sensor reports the temperature it measures; it does not remove the need for the thermal model, and a sensor that is not configured protects nothing. The manufacturer's application note treats the I2t model as the layer that adds protection beside the temperature sensor, including against excessive single-phase current. Check both: sensor wiring and monitoring enabled, thermal model enabled with nameplate data.
Why did no fuse or breaker trip while the winding burned?
Upstream devices guard against short circuits and current above their own ratings. An open phase in the output circuit changes how current distributes through the windings, but the line-side current often stays inside the protective devices' ratings, so they see a normal load while one winding carries far more than its share. The winding's thermal margin lives only in the drive's model and its insulation; nothing else in the chain measures it.
Do I have to run motor identification on the replacement motor?
Follow the drive's documented decision path rather than a fixed yes. If the replacement matches the configured motor's ordering data, verify the designation and rated data against the nameplate and correct the data set where it differs. If it differs, run the documented motor identification, which the S120 function manual places in chapter 4.12, then confirm the rated-current entry against the nameplate before the first loaded run.