Why a shunt alone can't meter DC amps and volts into a PLC

Power quality and harmonics Published 7 min read By Current Intel engineering team

Short answer

One shunt cannot serve both measurements. Its millivolt drop is a differential, non-isolated signal proportional to current only, and either terminal can sit at full bus voltage above the PLC analog common. Read the 5–60 A current with a Hall-effect DC current transmitter and the 110–240 V DC bus with an isolated DC voltage transmitter, each scaled to the module's input range.

On this page
  1. What a shunt actually hands the analog input
  2. Why the transformer idea also fails
  3. Two transmitters, one channel each
  4. Install and wire both channels
  5. Worked example: scaling both channels
  6. When a reading later drifts
  7. Decision
  8. Questions asked

A shunt cannot deliver both readings, and neither reading it gives belongs on a standard analog input. A shunt produces a millivolt-class drop proportional to current only — it knows nothing about the DC bus voltage — and nothing about that drop is referenced to the PLC's analog common. A step-down transformer does not rescue the voltage question either: a transformer transfers only changing flux, and steady DC passes through its winding as a near short circuit. The working arrangement is two isolated transmitters on two channels — a Hall-effect DC current transmitter sized for the conductor and an isolated DC voltage transducer rated for the bus. On a 110–240 V DC bus carrying 5–60 A, that is one split-core Hall transmitter around the current conductor and one isolated voltage transducer across the bus. The steps below cover selection, wiring, scaling and verification.

What a shunt actually hands the analog input #

A shunt is a calibrated low resistance in the power circuit, and a common panel-meter class is 100 A : 50 mV — 0.5 mV of drop for every ampere. At the example's 60 A load that is 30 mV, and at 5 A it is 2.5 mV. Two problems follow. Resolution: a 0–5 V input on an illustrative 12-bit module resolves about 1.2 mV per count, so full load lands in roughly two dozen counts and each count is worth about 2.4 A. Isolation: the drop is a floating differential voltage with no reference to the PLC analog common. With the shunt in the high side, both of its terminals sit near full bus potential; on an ungrounded DC system even the negative-leg position can drift relative to earth. A standard analog channel is not insulated for that, and landing a shunt terminal on it puts power-circuit voltage on the module's front end — and on your terminal block.

Why the transformer idea also fails #

The shunt answers only one of the two questions anyway: its output tracks current, never the bus voltage, so no wiring arrangement turns it into a voltage reading. A step-down transformer is not the missing piece, because a transformer couples alternating flux only — steady DC produces none, so the secondary shows nothing at all. Worse, a winding is just a low resistance to DC, so a primary connected across the DC bus draws a large continuous current through that resistance and can burn itself out. DC voltage gets measured the way transducer makers do it: an isolated resistive or electronic divider built for DC service.

Two transmitters, one channel each #

Buy two devices, and check three things on each datasheet: an input range that covers the real maximum rather than the typical load, an output type and range the analog module actually accepts, and measuring-side isolation rated for continuous duty at the circuit voltage.

Measurement Device Datasheet must show
DC current in the conductor Hall-effect DC current transmitter, split-core where the conductor cannot be broken Input range above the conductor maximum; output matched to the analog channel; clamping option for installation without opening the circuit
DC bus voltage Isolated DC voltage transducer DC input range above the bus maximum; scaled low-energy output; isolation documented for the system type — grounded or ungrounded

Devices of this class come with jumper-selected input ranges and standard industrial outputs, and split-core models clamp around the conductor without opening the circuit — the same approach as measuring DC and AC motor current for a PLC without a VFD. For the voltage channel, look for units sold as isolated DC voltage transducers: datasheet families cover DC inputs into the hundreds of volts, and some are specified for both grounded and isolated systems such as solar arrays.

Install and wire both channels #

  1. De-energize first. Shut the bus down, lock and tag the supply, and verify absence of voltage with a meter rated for DC at the bus level before opening the panel. Sustained DC arcs at this voltage are unforgiving, and this procedure is not a permit for live work.
  2. Clamp the current transmitter around one current-carrying conductor, observing the polarity or direction mark on the housing. Keep the return conductor outside the aperture: both conductors together cancel their fields and the channel reads near zero.
  3. Connect the voltage transducer across the bus through the fusing or disconnect its installation diagram calls for, landing measurement leads only on the terminals that diagram specifies.
  4. Match output to channel. Terminate the current transmitter's 4–20 mA output across a precision 250 Ω resistor to make 1–5 V for the 0–5 V channel, or run its 0–10 V output straight into the 0–10 V channel; a current output does not read on a voltage-only channel unless the module documentation says it accepts one. Keep shields and returns per the analog module's wiring diagram, and never bond the bus negative or a transmitter measurement terminal to the PLC analog common unless the drawings call for it.
  5. Scale the channels from the two datasheets before energizing — the arithmetic is in the worked example below.
  6. Verify before trusting. With the process in a safe state, check each channel's zero, then compare PLC values against an independent DC-rated clamp ammeter and voltmeter across the operating range. A reading that falls as current rises means polarity is flipped; a plausible but proportionally wrong number means the range or scaling is. Keep the channels monitoring-only until those comparisons pass.

Worked example: scaling both channels #

Example inputs, not measured results: a 240 V DC bus operating anywhere from 110 V to 240 V, load current from 5 A to 60 A, an illustrative 12-bit module with 4096 counts, a Hall-effect transmitter ranged 0–60 A with a 4–20 mA output, and an isolated DC voltage transducer ranged 0–250 V DC in and 0–10 V out. The scaling method is the same arithmetic used when conditioning a current sensor signal for a PLC analog input.

Current channel, loop into 250 Ω: 20 mA − 4 mA = 16 mA spans the 60 A range, and across the resistor that is 1 V at zero load and 5 V at maximum, so 4 V covers 60 A — 66.7 mV per ampere. The PLC converts back as amps = (measured volts − 1 V) × 60/4 = (measured volts − 1 V) × 15. Check: 3.00 V reads as (3 − 1) × 15 = 30 A. The same input resolves about 0.018 A per count — roughly two orders of magnitude finer than the shunt's 2.4 A per count.

Voltage channel: 10 V out for 250 V in means the output is 0.04 V for every bus volt, so bus volts = output volts × 25. Check: the 240 V bus shows 9.60 V at the channel, and a 110 V operating point shows 4.40 V. Resolution works out to 2.44 mV per count × 25 ≈ 61 mV per count on the bus — far finer than monitoring needs.

When a reading later drifts #

If the current channel's zero shifts after grounding or bonding work near the panel, the loop has picked up a second path to ground, and the remedy matches the documented fix for a 4–20 mA output ground fault with a signal isolator. Do not solve it by removing an isolation boundary or bonding the measured circuit to the PLC common.

Decision #

  • Shunt wired into the analog input: reject. Its terminals can sit at bus potential, and it resolves only a few counts across the load range.
  • Transformer across the bus to make voltage readable: reject. It passes no steady DC and overheats trying.
  • One device doing both jobs: only with a datasheet that rates voltage input, current input and isolation separately — otherwise keep two.
  • The build for this job: one split-core Hall-effect DC current transmitter ranged above the conductor maximum with an isolated current-loop output, and one isolated DC voltage transducer ranged above the bus maximum with a 0–10 V output, each scaled to its channel and verified against an independent meter before the values drive anything.

Questions asked

Can I read a low-side shunt directly if the shunt sits in the grounded negative leg?

Only when the analog input documentation supports that exact connection: the channel must tolerate the shunt drop within its common-mode range, the DC system must stay solidly grounded, and there must be no ground-potential difference between the shunt and the PLC. If the DC system floats, even the negative conductor can drift toward bus potential relative to earth. The isolated transmitter removes all of those conditions, which is why it is the default choice.

Why choose a 4–20 mA output instead of a 0–10 V output on the transmitters?

A current loop shrugs off cable voltage drop within the transmitter's stated loop-resistance budget, and its live zero gives you broken-wire detection: a reading below the live-zero floor means an open lead, while a genuine zero reading sits above it. A voltage signal cannot distinguish an open lead from a true zero without extra logic in the PLC. Take the current loop for long runs, electrically noisy panels, or whenever the transmitter and the analog module live in different enclosures.

Is there a single device that measures DC volts and amps together?

Combined DC power transducers exist, but treat one as two channels sharing a housing: the datasheet must rate the voltage input for the bus, the current input for the conductor, and the isolation for both, exactly as you would check two separate units. Never assume a transducer rated for AC service will accept DC, because many input stages are AC-only. If any of those ratings is missing, stay with two separate transmitters.

What accuracy should I expect from a Hall-effect DC current transmitter?

Use the accuracy figure the datasheet quotes for the specific input range you select, normally stated as a percentage of the selected span plus an offset rather than a fixed number of amperes. Add the analog input's own resolution and any offset the sensor shows at zero current. The zero and span checks against an independent meter, done before the channel is trusted, catch offset and polarity errors together.

Keep reading

  • Selection guide

    Measuring DC and AC motor current for a PLC without a VFD

    No. A fixed-speed motor that keeps its starter and overload relay gets PLC current feedback from a current transducer wired to an analog input, or from a communicating overload relay that reports over the network. A 12 V DC load needs a DC-capable Hall-effect transducer, because a current transformer cannot read steady DC.

    Control power: 24 V DC, UPS and transformers

  • Selection guide

    Measuring three-phase motor current for a PLC alarm input

    Use a self-powered current-loop transducer with a span at least equal to the motor's maximum current — 100 A here — clamped around one insulated phase conductor and wired to a PLC analog input configured for current. Never land a bare CT secondary on an analog input, never clamp around all three conductors, and treat the alarm as monitoring: the overload relay still does the protecting.

    Motors and motor starters

  • Troubleshooting

    When a CT reads correct volts and the meter reads zero amps

    A current transformer with a 0.333 VAC output collapses to near zero when landed on a power monitor's low-impedance current input; the meter is healthy. Fit a conventional 5 A secondary CT sized just above the circuit maximum, or use the meter variant whose current inputs expect a 0.333 VAC signal. Never open a 5 A CT secondary while the primary carries current.

    Power quality and harmonics