Troubleshooting
Why a soft starter output shows voltage with no start command
Short answer
A stopped soft starter is switched off, not isolated: thyristor off-state leakage and internal coupling put a high-impedance voltage on floating terminals, and the uncontrolled phase of a two-phase controlled starter is a plain copper link that holds its output at supply potential. Prove the difference with the motor connected and a low-impedance tester; only voltage that survives both indicates a fault.

On this page
- Why does the output show voltage with only the control supply applied?
- Why does one output phase read full phase-to-earth voltage with no start command?
- What is ghost voltage and how do you prove a reading is leakage?
- How do you test the stopped output step by step?
- Which reading tells you the soft starter has failed?
- What is the decision for each case you measured?
- Questions asked
A soft starter that has received no start command is switched off, not isolated, and its terminals prove it. Two readings get reported as faults, and both are usually normal: tens of volts on the power terminals when only the control supply feeds A1 and A2, and full phase-to-earth voltage on an output terminal when the three-phase supply is on. The first is thyristor off-state leakage and capacitive coupling into floating conductors, read by a high-impedance meter. The second is the uncontrolled phase a two-phase controlled starter passes through on copper. The verdict comes from two further facts: what the reading does with the motor connected, and what it does when a low-impedance tester loads it.
Why does the output show voltage with only the control supply applied? #
That reading is off-state leakage and coupling into conductors that are floating, not a conducted output: with the power feed absent, thyristor leakage, the snubber networks and the energized control electronics push microamps into terminals that nothing holds at earth potential. Ohm's law sets the scale: a 10 MΩ meter input shows 60 V when only 6 µA flows through it (I = V/R = 60 V / 10 MΩ).
These units are semiconductor motor controllers under IEC 60947-4-3, the product standard that covers them, and their stop state is a control state: isolation stays with the upstream switch. The indication appears on input and output terminals alike because each snubber ties an input terminal to its matching output terminal, so both ends of an off thyristor float at the same coupled potential. The ATS48 soft starter's support FAQ documents the same behaviour for that family: a residual voltage can be observed at the output in the off state with the motor disconnected. Confirm the voltage on A1 and A2 matches the control-supply rating on the nameplate before concluding anything, because an overdriven control input is a separate failure mode. Powering only the control side is also the legitimate way to bench-test the electronics, as covered in testing a soft starter without three-phase power connected.
Why does one output phase read full phase-to-earth voltage with no start command? #
T2 follows L2 through a copper connection, so it sits at the supply's phase-to-earth potential whenever the isolator is closed: on a 400 V system that is 400/√3 ≈ 231 V, with or without a start command. A two-phase controlled starter regulates only the L1-T1 and L3-T3 paths with inverse-parallel thyristor pairs. The 3RW30 and 3RW40 manual states that phase 2 is uncontrolled and is merely guided through the starter by a copper connection, so the 230 V you measured from T2 to earth is the healthy phase voltage, within meter tolerance. Verify that against the circuit diagram of the installed unit, and label terminals as you go: reports that switch between T1, T2 and T3 describe different electrical paths. The same two-phase layout is what matching a soft starter current range to its power structure is about.
What is ghost voltage and how do you prove a reading is leakage? #
Ghost voltage is what a high-impedance meter builds across its own input from a tiny coupled current, and you prove it by loading the same point with a low-impedance voltage tester and watching the reading collapse.
Illustrative numbers, not a measurement of your unit: a DMM with a 10 MΩ input reads 60.0 V on a floating terminal, and a low-impedance tester with a 3 kΩ internal burden reads 1.8 V on the same point. Treat the leakage as an ideal source E behind an internal resistance Rs, and write both readings as voltage dividers:
- 60.0 V = E × 10 MΩ / (10 MΩ + Rs)
- 1.8 V = E × 3 kΩ / (3 kΩ + Rs)
Setting the two expressions for E equal gives Rs ≈ 98 kΩ, and back-substituting gives E ≈ 60.6 V. The point can therefore deliver about 0.6 mA (60.6 V / 98 kΩ), which will not pull in the smallest relay, let alone turn a motor. Contrast a genuine supply path behind about 1 Ω: the same 3 kΩ burden reads 230 × 3000 / (3000 + 1) ≈ 229.9 V, a reading that barely moves. The arithmetic estimates source impedance; the only pass/fail information is collapse versus hold.
Use a listed low-impedance tester or a DMM mode whose burden the manual states, rated for the measurement category at the terminals. Never hang an improvised resistor on a live terminal or flash an output down to earth with a jumper to see what happens. The meter discipline is the same as in measuring VFD and soft starter current with the right meter.
How do you test the stopped output step by step? #
Work a fixed order: prove the tester, name the terminals, record both supply states, then load each suspect reading, and let the connected motor be the final judge, because leakage that disappears under a real load is not a fault.
These are energized measurements on power terminals. They belong to qualified electrical personnel working under the site's electrical safety program, with the PPE and approach boundaries set by NFPA 70E, 2024 edition, the standard for electrical safety in the workplace, and instruments rated under IEC 61010 for the point of measurement. Isolate and prove dead before moving any conductor, and confirm the procedure with the AHJ and the equipment documentation.
- Prove the tester on a known live source before the survey and again after it; a meter that reads the same everywhere tells you nothing.
- Record the nameplate (control-supply rating for A1 and A2, frame size, circuit diagram) and confirm the installed unit is two-phase controlled and which phase is bridged.
- With the main feed isolated and locked, power A1 and A2 only. Measure every power terminal to earth and across T1-T2, T2-T3 and T1-T3, with the motor connected and then disconnected, and label every pair in the record.
- Repeat each suspect reading with the low-impedance tester. Collapse means coupling; hold means a real source.
- Restore the supply with no command given. Measure L1, L2 and L3 to earth and phase-to-phase first, then T1, T2 and T3 the same way, and compare each controlled output with its own input.
- With the motor still connected and no command, measure across the motor terminals. A controlled phase holding full line voltage here ends the survey: isolate, and treat the unit as failed or backfed.
- Give one start and stop and confirm the stopped pattern returns unchanged; a pattern that differs between stops points at the command circuit or the wiring, not leakage.
Which reading tells you the soft starter has failed? #
One pattern condemns the unit: a controlled phase that keeps full voltage on its output under both the connected motor and a tester burden with no start command, because that means a thyristor pair has shorted or an internal path has welded.
| Reading | Condition | Verdict | Action |
|---|---|---|---|
| Tens of volts on floating terminals | Control supply only, main feed isolated | Leakage and coupling, normal | None; confirm the A1/A2 supply matches the nameplate |
| Full phase-to-earth voltage on the bridged phase | Supply on, stopped | Normal for a two-phase controlled unit | None |
| Reading collapses under the burden tester | Any state | Ghost voltage | None; record it |
| Controlled output holds full voltage under burden, motor connected, no command | Supply on | Shorted thyristor stack | Isolate; check for external feeds; if the only feed is the starter's own input, replace the unit |
| Voltage across the motor with every known source off | Any state | Backfeed through control or bypass wiring | Find and correct that source first |
Everything else in the table is measurement interpretation, and the fix is in how you read, not in what you order.
What is the decision for each case you measured? #
Keep the starter in service for both readings you reported; replace it only if a controlled output holds supply voltage across the connected motor with no start command.
- Control supply only, voltage on the input and output terminals: leakage and coupling. It passes as soon as it collapses under the burden tester, and the only action is confirming the A1/A2 supply matches the nameplate rating.
- Supply on, no command, full voltage from the bridged phase to earth: the two-phase design working as documented. No action.
- Full voltage on a controlled phase to earth that holds under burden with the motor connected: a shorted power stack. Replace the unit, and do not run the motor in the meantime, because one phase applied uncontrolled energizes part of the winding continuously.
- Voltage present with every identified source isolated: a backfeed. Find it before any conductor is moved.
As reported, yours are the first two cases: a two-phase controlled starter behaving exactly as its manual says it should.
Questions asked
Does the leakage voltage on a stopped output harm the motor?
No. A connected winding is an impedance of a few ohms, so the fraction of a milliamp available loads the coupled voltage down to millivolts and the motor produces no torque. Treat the terminals as live all the same: only the upstream isolator, opened and proved dead, makes them safe to work on.
Do all soft starters bridge one phase?
No. Two-phase controlled designs such as the 3RW30 and 3RW40 pass one phase through on copper, so that output sits at supply potential whenever the feed is on. Three-phase controlled units regulate all three outputs, and full phase-to-earth voltage on any stopped output of one of those points at a fault, so check the circuit diagram for your exact unit.
What happens if 230 V is applied to A1 and A2 on a low-voltage control variant?
The A1 and A2 input is rated for one voltage range, printed on the nameplate, and 230 V across a variant built for 24 V overdrives the control electronics and can destroy them. Match the supply to that rating before any power-up, including the bench test that produced the original readings.
Can a multimeter's low-impedance mode replace a solenoid voltage tester?
Yes, when the mode's burden is stated in the meter manual, commonly a few thousand ohms, and the meter is rated for the measurement category and voltage at the terminals. An ordinary high-impedance reading cannot make the distinction, and an improvised resistor on a live terminal is not an acceptable substitute.