Why a static phase converter buzzes and only starts when tapped
Short answer
A buzz and a creep that clear when you tap the box are a start-circuit fault: the potential relay's contacts are pitted or its armature is sticking, or a crimp in the start-capacitor path has failed. The 4 V start sag on the 220 V line clears the supply, so with the connections already tight, test the start capacitor's microfarads and replace the relay with a part matched on pick-up voltage, drop-out voltage and capacitance rating.

On this page
- What the potential relay does during a start
- The fixes that cannot work
- Checking the 4 V start sag on the 1 HP 3.7 A mill motor
- Match the symptom to the fault
- Inspect the start circuit with the power locked out
- Measure the start capacitor in microfarads
- Replace the relay with a matched part
- Prove the fix with ten cold starts
- Questions asked
A buzz, a slow creep and a start that only happens after you tap the converter box is a start-circuit fault, and on a static converter the start circuit is the potential relay and the start capacitor. Your voltage reading settles the supply question: the line sags only 4 V at switch-on, so a bigger receptacle or heavier wire cannot fix this. With every connection already re-made and tight, the part to replace is the potential relay, because pitted contacts or a sticking armature behave exactly like a tap-sensitive buzz. Confirm the start capacitor's value in microfarads with a capacitance meter, never a voltmeter, then fit a relay matched on pick-up voltage, drop-out voltage and capacitance rating.
What the potential relay does during a start #
A static converter runs a three-phase motor from a single-phase line by feeding the third motor terminal through run capacitors. A start capacitor is paralleled in for the run-up only, and a potential relay switches it. The relay coil sits across the generated leg, and its normally closed contact sits in series with the start capacitor. As the rotor accelerates, the voltage on that leg rises; when it reaches the relay's pick-up voltage (also called the pull-in voltage), the armature pulls in, the contact opens and the start capacitor drops out. The drop-out voltage is the coil level at which the armature releases again. A smaller run-capacitor set carries the motor from there.
Three faults in that chain end in the same buzz and stall:
- Contacts that fail to make, from pitted faces, dirt or a bent or sticky armature, leave the start capacitor weakly connected or out entirely. The motor sees almost no phase shift and hums; a tap shifts the armature enough to close the contact.
- A relay that picks up below its intended voltage drops the start capacitor out before the rotor is up to speed, and the motor falls back into the buzz.
- Contacts that weld or hang closed keep the start capacitor in circuit; it is an intermittent-duty part and overheats if it stays in.
The fixes that cannot work #
Retire the changes that never touch the start circuit:
- A higher-amp receptacle. Swapping to a 50 A outlet changed nothing because ampacity was never the limit; the measured sag proves it.
- Re-tightening terminals. It got its one pass with no change. Repeat it only if the inspection below finds a discolored or loose crimp.
- A voltmeter across the capacitor. It reads the voltage on the terminals, not the microfarads, and a start capacitor can hold normal voltage after losing most of its capacitance.
- A guessed replacement capacitance. Overshoot and the relay contacts arc; undershoot and the motor stays under-started. Read the converter and relay markings before buying anything.
- Tapping the box as a routine. It is evidence of a mechanical or contact fault, nothing more, and it lets the motor run with the start circuit in an unknown state.
Checking the 4 V start sag on the 1 HP 3.7 A mill motor #
Inputs, all taken from your own case:
- Line: 220 V single phase at the outlet.
- Sag measured at motor switch-on: 4 V.
- Motor nameplate: 1 HP, 3.7 A, 1200 rpm.
- Frequency: 60 Hz, the North American grid frequency; redo the pole count below if yours differs.
The rule: NFPA 70, the National Electrical Code, 2023 edition, covers electrical conductors and equipment, and its informational notes to 210.19(A) and 215.2(A) suggest holding branch-circuit voltage drop to 3% and the combined feeder-plus-branch drop to 5%. Judge a motor-start sag against that 5% budget, and confirm what applies to your installation with the local authority having jurisdiction and the converter documentation. For the speed check, synchronous rpm equals 120 times the frequency divided by the pole count.
Arithmetic:
- Drop budget: 0.05 × 220 V = 11 V.
- Measured sag: 4 V ÷ 220 V = 0.018, or 1.8%.
- Poles: 120 × 60 Hz ÷ 1200 rpm = 6.
Result: the sag uses about a third of the allowed budget, and the motor is a six-pole machine.
Decision: the supply, feeder and receptacle are cleared; open the converter and stop chasing ampacity. If this converter ran the mill for years and only now buzzes, the relay is the first replacement. If the converter is new to the mill, compare the installed start capacitance with the maker's figure for this motor before condemning anything, because converters are often specified around two- and four-pole motors, and a six-pole mill motor takes the value the maker lists for it, not one borrowed from a faster machine.
Match the symptom to the fault #
- Hums and creeps, catches when you tap: relay contacts pitted or the armature sticking. Power off, inspect and hand-exercise the relay.
- Catches only after several taps, and not every time: a loose joint in the start path, meaning the relay coil leads, start-capacitor terminals or the capacitor-to-converter lead. Pull-test every crimp and look for heat discoloration.
- Never gets past a crawl and tapping changes nothing: start capacitor weak or open. Measure the discharged capacitor with a capacitance meter. A motor that does not move at all is a different fault; see Why a static phase converter won't start a lathe motor.
- Ran fine for the previous owner, now stalls: relay wear. Compare the relay's nameplate with the converter's spec and replace it.
- New converter on this mill, never started well: start capacitance wrong for a 1200 rpm motor. Compare the installed microfarads with the converter's rating for this motor.
- Start capacitor hot or bulging after several tries: the relay is not dropping it out. Replace the capacitor and the relay together.
Inspect the start circuit with the power locked out #
Open the disconnect, lock it out and verify zero volts at the converter input before the cover comes off. Then discharge both capacitors through a bleeder resistor; never short the terminals with a screwdriver.
- Photograph the wiring before anything moves.
- Copy the relay nameplate: model, pick-up and drop-out voltages, coil terminals.
- Copy the microfarad marking on every capacitor.
- Look at the relay contacts: black pitting, burn marks or a visibly bent armature end the diagnosis.
- Press the armature by hand and let it go; it must travel freely and return crisply.
- Tug each crimped lead in the start path, meaning the relay coil, the start capacitor and the capacitor-to-converter lead, and reterminate anything that moves or shows heat discoloration.
Measure the start capacitor in microfarads #
With the capacitor isolated and discharged, read it with a capacitance meter and compare the value with the microfarads and tolerance printed on the case. A reading near zero means the capacitor is open; a reading outside its printed tolerance means replace it. Then check the relay against the capacitor it has to switch: potential relays carry a maximum capacitance rating that depends on voltage and frequency. At 240 V, one common HVAC relay series is rated to switch up to about 600 µF and another up to about 360 µF, so take the figure from the data sheet of the exact part you buy. If the installed start capacitance exceeds that rating, the contacts arc and fail early.
Replace the relay with a matched part #
With sound wiring and a capacitor inside tolerance, the relay is the replacement, the usual finding when a converter that ran fine for the previous owner starts stalling. Take the old relay or its nameplate details to an HVAC supplier; these are sold as motor-starting relays under the heating and air-conditioning headings, not under general control relays. Match five things: coil voltage, pick-up voltage, drop-out voltage, terminal layout, and the horsepower and capacitance ratings, which must cover your converter's start capacitance. If the capacitor shows heat damage or a bulged case, replace it in the same visit.
Prove the fix with ten cold starts #
Restore power and start the motor ten times in a row, cold, with no tapping. Listen for the relay changing state as the motor reaches speed; the buzz must end within the run-up. Clamp the motor legs once it is at speed: sustained current above the 3.7 A nameplate with the mill idle means the start capacitor is still in circuit, so shut down and recheck the relay. The start capacitor should be no more than warm after the series; hot or bulging means the relay is not dropping it out. If the converter now starts cleanly but shuts down after minutes of running, the fault has moved to the run side; see Why a static phase converter stops after a few minutes.
Questions asked
Can I check the start capacitor with a regular multimeter?
Only if it has a capacitance range. A voltage reading across the terminals tells you the capacitor holds charge, not how many microfarads remain, and a start capacitor can read normal voltage after losing most of its capacitance. Use a capacitance meter or an LCR meter on the isolated, discharged capacitor and compare the reading with the value and tolerance printed on its case.
Should I replace the run capacitors as well?
Not for this symptom. Run capacitors stay in circuit the whole time the motor runs, so their failure shows up as weak running, hot windings or high current after a clean start. A buzz that ends when you tap the box lives in the switched part of the circuit: the start capacitor, its wiring and the potential relay. Measure the run capacitors only if the motor starts cleanly but then runs badly.
Is cleaning the relay contacts an alternative to replacing the relay?
Treat cleaning as a stopgap. Pitting and spring wear change the contact for good, and the same high-resistance joint returns under the inrush of the next start. Potential relays are sealed, standardized parts carried by HVAC suppliers, and matching a new one to the old nameplate is quicker and more certain than filing contacts. If you need one start to move the machine, cleaning may buy it, but plan on the new relay.
Will a bigger start capacitor give the motor a harder start?
More microfarads raises the phase shift and the current the relay contacts must break. Past the relay's switching rating the contacts arc and the capacitor overheats; too little leaves the motor under-started. Set the value to the converter maker's figure for your motor's horsepower and speed. If the maker lists a different value for six-pole motors, that is the one to use.