Troubleshooting

Why a phase converter idler runs but will not start

Motors and motor starters Published 10 min read By Current Intel engineering team

Short answer

A rotary converter idler that spins and runs normally by hand but will not start on the button has an open starting-current path, not a bad motor. A switch that tests good and voltage at its terminals prove nothing, because one burned potential-relay contact or a loose bank common lead can cut the whole branch. Trace and test the branch link by link with the supply locked off and each capacitor discharged first.

On this page
  1. Why does the idler run when spun but not start on its own?
  2. Why is there power at the switch but no start?
  3. How much current does the start bank really carry?
  4. How do you make the start bank safe to work on?
  5. What is the fastest way to find the open in the start branch?
  6. When is the idler motor itself the problem?
  7. What repair puts the start back for good?
  8. Questions asked

An idler that spins up by hand and then runs normally has a sound motor; the fault is an open circuit in the starting branch that feeds the capacitor bank. That is why new capacitors and a bypassed pushbutton changed nothing: the break sits between parts that each test good — most often burned potential-relay points, a loose common lead on the bank, or an open return in the idler terminal box. Voltage at the switch clears none of these, because the meter proves only that one point is live. Below are the numbers the start branch carries and the test order that finds the open link with the supply locked off and the bank discharged. Stop hand-spinning the idler: the repair is usually one set of contacts or one lead, and the branch gives it up quickly once each link is tested alone.

Why does the idler run when spun but not start on its own? #

Because the starting-current path is open, not the motor: a three-phase idler that spins up and runs normally when turned by hand has healthy windings, and the fault sits in the branch that feeds the start capacitor bank or in the contacts that switch it.

A rotary converter's idler is an ordinary three-phase motor. Fed three-phase power it starts itself; fed only single phase it hums, pulls locked-rotor current and stays still, because it cannot make its own rotating field — the article on why an idler with no start circuit just hums covers exactly that behavior. The capacitor branch is the fix: it feeds current into the manufactured leg out of phase with the supply, and that phase difference is the breakaway torque.

The branch in a build like this runs supply, pushbutton, potential-relay points, capacitor bank, the manufactured-leg terminal at the idler, and back through the windings. The potential relay is voltage-sensing: it holds its points closed through the moment of acceleration and opens them as the generated-leg voltage rises. The run banks that keep the leg balanced at speed are a separate matter — they trim, they do not break a standing rotor away — and the article on why a rotary converter needs three capacitor banks keeps the two jobs apart.

Every link of that chain being closed while the machine runs by hand and nothing happening on the button is one coherent picture: the running circuit is healthy and one link in the start chain is open. A circuit that worked for years and then quit in a moment fits a contact that finally eroded through, not a design fault. The switch has already been cleared by three tests — the meter, the bypass and the new capacitors all point downstream.

Why is there power at the switch but no start? #

Because voltage at one point proves only that the point is live: a burned potential-relay contact, a loose bank common lead or an open return past the switch interrupts the whole branch while the switch still checks perfect on a continuity test.

Three facts from this machine say the button is not the fault: the switch opens and closes on a meter, the machine stayed dead with the switch bypassed, and new capacitors changed nothing. What none of them tested is the chain after the switch — the relay points, the bank's common lead, and the return through the manufactured-leg terminal.

Two meter effects deepen the trap. A high-impedance meter can read supply voltage through the idler's own windings even when the branch is open somewhere, so voltage at a bank terminal can be true and useless at once. And a continuity test passes milliamps, while a contact face burned enough to fail under the start current can still look solid at meter current. The only readings that locate the break are resistance readings taken link by link with the branch isolated, or watching the current during a real start — which is where the numbers in the next section come in.

How much current does the start bank really carry? #

Treat the bank as a short burst of roughly a hundred amperes: six 200 µF capacitors in parallel give 1200 µF, which at 240 V and 60 Hz presents 2.21 Ω of capacitive reactance and draws about 109 A across the line.

Worked example, taking the bank this 15 hp idler reportedly carries — a parallel bank on the order of 1200 µF, built here as six 200 µF cans:

  • Parallel capacitances add: C_total = 6 × 200 µF = 1200 µF.
  • Capacitive reactance at 60 Hz: X_C = 1/(2πfC) = 1/(2π × 60 Hz × 0.0012 F) = 1/0.452 S ≈ 2.21 Ω.
  • Branch current with the whole bank across the line: I = V / X_C = 240 V / 2.21 Ω ≈ 109 A.

The estimate assumes the full line-to-line voltage across the bank at the instant of connection, at the line frequency, from the basic capacitor reactance relation. In the running converter the bank hangs between one line and the manufactured leg, whose voltage is lower and shifting while the idler accelerates, so read that current as the order of magnitude the points, leads and terminations must survive at every start — and check the machine's own design documentation before trusting the figure further.

The same arithmetic sizes the failure modes. Losing one can drops the bank to 1000 µF: X_C = 1/(377 × 0.0010 F) = 2.65 Ω, so I = 240 V / 2.65 Ω ≈ 90 A — about 17 percent less, a weak crank that usually still starts. A loose common lead removes the whole bank at once. And a wiring error that strings cans in series collapses it silently: two equal cans in series act as half of one, 100 µF here. Read the actual connection, not the parts list. That burst is also why the relay points erode: every start drives the capacitor current through them, so the points are the wear part in this circuit.

How do you make the start bank safe to work on? #

Lock the supply off, verify absence of voltage with a meter rated for the panel, then discharge each capacitor through a resistor before touching a terminal: at full charge this bank stores about 69 J, enough to weld a screwdriver tip and wreck the capacitors.

The storage figure is E = ½CV²: with the whole bank at 1200 µF and the 339 V supply peak, E = 0.5 × 0.0012 F × (339 V)² ≈ 69 J. Discharge each can through a power resistor rated for the voltage and the energy, never a screwdriver blade across the terminals, which dumps the full charge into the tip and can damage the cans. Electrolytic start capacitors can creep back up in voltage after a discharge, so re-check each can before handling it.

The de-energize, lock and verify sequence comes first because every step that follows opens the terminal box or the converter panel: NFPA 70E, 2024 edition, is the standard covering safe electrical work practices of this kind, and the local authority having jurisdiction and the converter's documentation settle the details for your installation.

What is the fastest way to find the open in the start branch? #

Trace the branch and measure it one link at a time with the power off: supply, button or contactor, potential-relay points, every capacitor, the bank's common lead, and the return through the idler's manufactured-leg terminal.

First establish which arrangement this converter uses — the button either switches the bank through the relay points directly, or it drives a contactor coil whose contacts carry the bank. The bypass test cleared only the button. Then work down the list; each line carries its expected result:

  1. Sketch the branch as built. Mark the supply lugs, button, relay, every can and the idler terminal box. The manufacturer's connection diagram is normally on the motor nameplate or inside the junction-box lid — use it to identify the manufactured-leg lead before moving any wire. Expected: one page to test against.
  2. Ohm the conductive links with the bank leads lifted. From the line side of the button through the relay points to the bank's common terminal, and from the bank's motor-side terminal to the manufactured-leg lug at the idler. Expected: a few ohms or less on sound conductors; where it reads open, split the span at its midpoint and repeat until the joint is in hand.
  3. Measure each capacitor with a capacitance meter. An ohmmeter cannot see through a capacitor — a perfect bank still reads open across it — so the cans get their own test: lifted, discharged, then measured individually. Expected: each reading inside the tolerance printed on that can; log them, because one low can weakens the crank without killing it.
  4. Test the potential relay against its documentation. Points closed and solid at rest, coil resistance as the manufacturer lists, and the operate and release behavior the device sheet describes. Expected: no pitted or welded faces, coil within specification.
  5. Tug and look at every termination in the branch. Discolored copper, broken strands at a crimp, or a common lead hanging on its insulation are the classic finds. Expected: tight, bright, mechanically supported joints.
  6. Re-check the return through the idler. From the bank's motor-side lead through the manufactured-leg lug into the winding — a loose lug inside the motor terminal box breaks the circuit while every capacitor on the bench tests perfect. Expected: continuity from lug to winding.

A branch that passes every line leaves the relay's operating behavior as the suspect — that is the repair section below, not more parts.

When is the idler motor itself the problem? #

Almost never in this pattern: an idler that runs normally once spun by hand has sound windings for the running duty, and a dead start from standstill points at the branch — confirm with a hand-turned shaft check and an insulation-resistance test before ruling the motor out.

A three-phase idler carries no centrifugal switch, so there is no mechanical device inside it that can fail in a way that kills only the start. Two checks close the question. With the supply locked off, the shaft must turn freely by hand: a binding bearing holds the rotor against even a healthy start branch. Then a megohmmeter insulation-resistance test from the leads to ground, at the test voltage the motor manufacturer's documentation calls for, compared against the winding minimum that same documentation states — a reading far below it condemns the windings regardless of the start branch. The running evidence already leans the same way: this machine ran with normal current once spinning, and windings that are open or grounded do not run normally.

What repair puts the start back for good? #

Fix the open link you found and match the duty: replace burned potential-relay points with a relay suited to capacitor switching, remake a loose common lead back to bright copper with a supported joint, and fit capacitors that match the bank's capacitance, voltage rating and momentary start duty.

Decisions, case by case:

  • Relay points open or pitted: replace the potential relay, matched to this converter's generated-leg voltage per the device documentation — not just any relay that fits the socket. Never strap the points in permanently: the bank is momentary duty, and a bank held in circuit cooks start electrolytics and drags the leg out of balance.
  • Loose or burned common lead: cut back to bright copper, fit a new crimp or lug, and support the lead so vibration cannot work it loose again. Re-tightening a hot joint only buys one more failure.
  • One weak can: replace it with the same capacitance and an equal or higher voltage rating in start duty, keeping the bank at its design total. Adding capacitance because starts feel weak pulls more current through the same points — the branch current scales directly with capacitance in the worked example.
  • Everything passes and the button is still dead: the break is intermittent or in the relay's operate behavior. A qualified person, using the instruments and protective practices the live-work rules require, clamp-meters the branch during an actual start; the link where the current stops is the fault.

Then reassemble covers, grounding and guards, and give it one real test: the idler must accelerate promptly, and the relay must drop the bank as it comes to speed and keep it out at shutdown. A bank that comes back in when the machine stops has its own signature — the article on why a start capacitor reconnects on shutdown covers that tell-tale. The decision in one line: the motor is fine, the branch is open, find the link with everything dead and discharged, and put the bank back on momentary duty only.

Questions asked

What voltage rating do the replacement start capacitors need?

Each unit's rating must exceed the highest peak voltage the bank sees. A 240 V RMS supply peaks at 240 × 1.414, about 339 V, so parallel units on a 240 V converter all need a rating above that, and they all see the same voltage. Take the rating from the old cans and the converter's plan; horsepower alone tells you nothing about voltage.

Why did brand new capacitors not fix the no-start?

Because the capacitors were never the fault: every can can test perfect and still carry no current if the branch feeding it is open. Burned relay points or one loose common lead removes the whole bank at once, which is exactly this machine's pattern of instant start when spun and a dead button otherwise. Test the path link by link before buying more parts.

Is hand-spinning the idler an acceptable way to keep the shop running?

No. It works, but your hand is beside a rotor that can start electrically on its own the moment an intermittent joint re-makes, and one unexpected start can pull a hand or a bar into the rotation. Fix the branch instead; in this symptom pattern the repair is usually one set of relay points or one lead.

Do the run capacitors have anything to do with a no-start?

In a capacitor-start converter, no: the run banks trim the generated leg for balance once the idler is spinning, and they supply no breakaway torque of their own. A failed run bank shows up as unbalanced phase voltages and a hot idler while running, not as a dead button, so leave them out of this fault until the start branch is proven.

Keep reading

  • Troubleshooting

    Why a rotary phase converter with no start circuit hums

    A converter idler fed only by run capacitance starts like a permanent-split-capacitor motor, with almost no breakaway torque, so a hum with no rotation means that thin margin collapsed. Verify supply voltage and contact drop during the attempt, test the capacitor bank as a unit, confirm lead numbers after any bench run, then prove the fix with a momentary-duty start capacitor across the manufactured leg before suspecting rotor damage.

    Motors and motor starters

  • Explainer

    Why a worn shaft does not stop a 5.5 kW RPC idler motor

    A badly worn output shaft does not disqualify a 5.5 kW, 220 V, 4-pole motor from idler duty in a rotary phase converter: the idler carries no mechanical torque and capacitor/potential-relay starting never touches the shaft. What decides is size against your largest load, no-load current, bearing condition and generated-leg balance under load.

    Motors and motor starters

  • Explainer

    Why a rotary phase converter needs three capacitor banks

    A rotary converter needs three capacitor banks because they do three jobs: a switched electrolytic start bank of roughly 120 µF per horsepower spins the idler up, film run banks of about 12 and 8 µF per horsepower hold the generated leg, and an optional 4 µF per horsepower bank across the supply corrects power factor. Duty, connection point and size all differ, so one capacitor cannot replace them; size from these rules, then trim by measurement.

    Motors and motor starters

Why a synchronous idler will not balance a rotary phase converter