Why a worn shaft does not stop a 5.5 kW RPC idler motor
Short answer
A badly worn output shaft does not disqualify a 5.5 kW, 220 V, 4-pole motor from idler duty in a rotary phase converter: the idler carries no mechanical torque and capacitor/potential-relay starting never touches the shaft. What decides is size against your largest load, no-load current, bearing condition and generated-leg balance under load.

On this page
- Why the shaft never enters the job
- Reading the nameplate on a salvaged pump motor
- The real sizing limit: your largest load motor
- Starting it without a shaft
- Sizing the worn-shaft idler against a 5 hp lathe
- What to measure before you trust the converter
- Getting a salvaged pump motor ready
- The decision, case by case
- Questions asked
A badly worn output shaft does not disqualify a pump-duty motor from idler duty. A rotary phase converter idler delivers no mechanical power, so no torque ever passes through its shaft, and the capacitor and potential-relay starter that spins it up never touches the shaft. What actually decides the job is the size of your largest three-phase load, the no-load current the idler draws from your single-phase service, the condition of its bearings, and the balance of the generated leg measured under load. This article works the sizing rule through the arithmetic for the worn-shaft case, lays out the two starting methods, and ends with the decision for each one.
Why the shaft never enters the job #
An idler is an ordinary three-phase induction motor with two terminals connected across the single-phase lines. Once the rotor is turning, its field induces a voltage in the third winding, and that third terminal becomes the generated leg of a rough three-phase supply. The shaft's only job is to let the rotor spin freely. It carries no belt, no coupling and no torque, so journal wear that would scrap the motor for pump work costs an idler nothing.
That settles the tempting fixes at once. Scrapping throws away a stator and rotor set whose condition the shaft says nothing about: winding, rotor bars and bearings are separate items, each checkable on the bench. Rebuilding or metalizing the journal pays money to restore a surface the idler never uses. Leave the shaft intact. A worn journal can still be turned to a clean, concentric undersize for a pulley or sleeved for future machine duty, and an intact shaft costs the converter nothing.
Reading the nameplate on a salvaged pump motor #
The plate on these motors carries facts that matter. The winding is rated 200 V and 220 V at both 50 Hz and 60 Hz, with speeds of about 1450 rpm on 50 Hz and 1750 rpm on 60 Hz, the signature of a 4-pole induction machine. The face mount that bolted the motor to its pump casing means you will fabricate a rigid base or adapter plate so it sits solidly without vibration.
Use the terminal-box connection diagram that matches your measured supply voltage, and read the speed and frequency figures for your own service. A winding held above its rated voltage saturates and pulls excess magnetizing current, and that current heats an idler that is doing no work at all. A 575 V plate raises different questions entirely; using a 575 volt motor as a rotary phase converter covers that conversion.
The real sizing limit: your largest load motor #
The rule shop builders and converter sellers use is simple: the idler should be at least as large as the biggest three-phase motor it will run. Published sizing guidance puts it the same way and adds that easy-starting loads need only modest oversizing, while hard-starting, high-inertia or across-the-line loads need more. Oversizing past your actual loads buys a stiffer generated leg, and it carries a standing cost: a bigger rotor pulls more magnetizing current from the single-phase service hour after hour, machine running or not. That standing draw is why rotary phase converter idle current runs so high, and it is the honest price of the steadier voltage a large idler gives you.
Starting it without a shaft #
Capacitor and potential-relay starting is the usual choice. Start capacitance connected across the generated leg gets the rotor turning from standstill; a voltage-sensing relay watches that leg and drops the capacitance out once its voltage climbs close to the supply legs. Nothing ever attaches to the shaft, so the worn section is never in the circuit. The same circuit that turns a 5 hp motor into a self-starting rotary phase converter bolts onto this frame unchanged.
Size the capacitance from a published horsepower-based method rather than by guesswork, then trim it against measured leg voltages. One relay failure is worth knowing before you wire it: if the relay re-closes after shutdown, the capacitance reconnects with the unit stopped, which is why a rotary phase converter start capacitor reconnects on shutdown.
Pony-motor starting is the fallback when you want no starting capacitance at all. A small motor belts the idler up to speed, then switches off. This path does use the shaft: turn the worn journal to the next clean, concentric undersize, bore a pulley to fit it or sleeve the journal, and check runout with a dial indicator before the first run, because an eccentric pulley shakes the bearings for as long as the converter runs.
Sizing the worn-shaft idler against a 5 hp lathe #
Inputs, with their sources: the idler plate gives 5.5 kW, a 220 V winding, 4 poles and 1750 rpm at 60 Hz. The load, assumed here as a typical small shop, is a single 5 hp lathe motor started across the line. Published builder guidance supplies the pairing rule: a 5 hp lathe is commonly paired with a 7.5 hp converter, and an idler is chosen at least as large as the largest load. The conversion constant is 0.746 kW/hp.
The rule in words: convert the idler's kilowatt rating to horsepower and compare it with the largest load motor's rating; then confirm the speed class, because a converter should spin near the speed class its loads expect.
The arithmetic:
- Idler rating: 5.5 kW ÷ 0.746 kW/hp = 7.37 hp, in practical terms a 7.4 hp class machine.
- Speed class: (120 × 60 Hz) ÷ 4 poles = 1800 rpm synchronous. The plate's 1750 rpm full-load speed gives a slip of 1800 rpm - 1750 rpm = 50 rpm, and 50 ÷ 1800 = 2.8%, a normal full-load slip for this class; unloaded, the idler sits just under synchronous.
- Margin: 7.4 hp against the lathe's rating leaves 2.4 hp, and the rule only asks the idler to be at least as large as its biggest load.
Result: the worn-shaft motor works out as a 7.4 hp class idler.
Decision: for a shop whose biggest machine is that lathe, run it as the idler, with no shaft work of any kind. The same rule caps comfortable connected load at roughly 7 hp. Past that ceiling, or with a hard-starting machine close to it, keep this motor and add a second idler beside it rather than scrapping it, and confirm the pair with the under-load measurements in the next section.
What to measure before you trust the converter #
One safety note belongs here. Before you open the terminal box or the capacitor enclosure, follow the shutdown and verification sequence of NFPA 70E, 2024 edition, which covers establishing an electrically safe work condition: de-energize, lock out, and verify absence of voltage at the terminals, and confirm the details with your authority having jurisdiction and the equipment documentation. Capacitors hold charge with the power off, so discharge them through a suitably rated resistor and verify before touching anything.
Then measure before you adjust anything, in this order:
| Measurement | Where and how | What it tells you |
|---|---|---|
| Supply voltage at the idler terminals | Meter at the idler's line terminals, load connected | Above the rated range: idle overheating. Below it: hard starts and stalling loads. |
| No-load current in each lead | Clamp meter on each idler lead, nothing running | Currents far apart or excessive: wrong voltage connection or a winding fault. |
| Generated-leg voltage, no load | Third terminal to each supply leg | Well above the supply legs: too much capacitance. Well below: too little, or a failing winding. |
| Leg-to-leg voltage, largest load running | Output terminals while the load motor runs | A wide spread overheats the load motor and must be tuned out. |
| Shaft speed | Tachometer at the shaft end or pulley | Well below the nameplate speed: the supply or the rotor is dragging. |
| Frame and bearing temperature | Contact thermometer after an hour unloaded | Still climbing after an hour: worn bearings or overvoltage. |
Record the no-load numbers first, then repeat the leg-to-leg readings with the largest motor running, and compare them against the load motor's rated voltage tolerance. Tune the generated-leg capacitance only after those readings show where the imbalance sits. A wide leg-to-leg spread under load is also what shuts machines down on the converter's third leg, so treat it as the gate the converter has to pass. Keep in mind that balanced voltages with badly split currents point at wiring or a failed capacitor, not at tuning.
Getting a salvaged pump motor ready #
Bearings first. Pump duty, with the rotors mounted directly on the shaft end, is exactly the duty that wears bearings along with the journal. Spin the rotor by hand and listen for roughness, check radial and axial play, and replace both bearings before service. An idler turns whenever the shop has power, so its bearing hours accumulate faster than on a motor that runs a few hours a year.
Then the winding. Test insulation resistance with an insulation-resistance tester at 500 V DC, tied winding leads to the frame; IEEE 43 is the standard that defines this test method and its voltage selection, and the acceptance limit for your machine comes from its documentation. A dry, clean stator on a low-voltage machine reads tens of megohms or more, while single-digit readings mean moisture or contamination: dry the winding and retest before energizing. Compare the DC resistance of the three windings against each other; one winding clearly off from the other two has shorted or high-resistance turns. Look inside the terminal box for moisture staining if the pump handled liquids.
Mount and protect it. Fabricate a rigid base for the face-mount flange so vibration cannot work connections loose, and enclose the capacitors and every live terminal. Put overcurrent protection on the single-phase feed sized from the idler's rated input, and set the overload from the nameplate full-load current, the way overload relays are set from motor nameplate full-load current.
The decision, case by case #
- Relay-and-capacitor start, connected load at or under roughly 7 hp: mount it and run it. No shaft work of any kind.
- Pony-motor start: turn the worn journal to a clean, concentric undersize and bore the pulley to fit.
- Connected load past that ceiling, or a hard-starting machine near it: keep the motor and add a second idler beside it.
- Rough bearings or a failed insulation test: repair those first. The electrical machine is worth the bearing set, and the shaft was never the problem.
Questions asked
How much start capacitance does a 5.5 kW idler motor need?
No single microfarad number fits, because capacitance scales with the idler's rating and interacts with the relay's pickup point. Sized too small, the idler hums without breaking away; sized too large, the generated leg sits above the supply legs and the relay may never drop out. Take the value from a published horsepower-based sizing method, then trim it against the measured generated-leg voltage.
Can I cut the worn shaft off instead of leaving it?
Plenty of finished converters run idlers with the shaft cut down and nothing on it, and the machine neither knows nor cares. The argument against cutting is only about the future: a cut journal can no longer take a bored pulley or a sleeve, so the motor is locked into idler duty for good. Leave it intact until the converter is proven.
Why does the idler run warm before any load is switched on?
Two of the three windings are fed straight from the single-phase lines, and the magnetizing current that builds the rotating field flows whether or not a machine is running, so the frame warms at idle and stays warm while the shop is powered. If the frame is too hot to rest a hand on after an hour, suspect supply voltage above the nameplate value or bearings on their way out.
The plate shows two speeds and two frequencies, so which figures apply?
Match the column to your service: 60 Hz figures on a 60 Hz supply, 50 Hz on a 50 Hz supply, because a 4-pole field turns near 1800 rpm synchronous at 60 Hz and near 1500 rpm at 50 Hz. The winding connection itself follows the supply voltage, not the frequency, so pick the terminal diagram that matches your measured service voltage.
Can I run two of these motors as parallel idlers?
Yes, and it is a common way to grow a converter: two idlers of similar rating on the same three-leg bus add starting reserve and hold the generated leg steadier when a big machine starts. Each idler keeps its own overload protection, the start circuit is sized for the motor it starts, and you confirm the pair with the same under-load leg voltage measurements you would apply to one.