Why a transformer tap chart shows 173 percent rated voltage

Power distribution and transformers Published 5 min read By Current Intel engineering team

Short answer

A 173 percent entry on a delta-wye transformer tap chart is the square-root-of-three factor between line-to-line voltage and the rated voltage of one wye phase winding. It is a voltage basis, not a stress figure: the windings sit within rating, and the entry alone calls for no tap change.

On this page
  1. Where the 173 percent comes from
  2. The worked numbers
  3. Why the line ratio and the turns ratio differ
  4. Reading the rest of the tap chart
  5. Checking it at the transformer
  6. The decision
  7. Questions asked

A 173 percent entry on a transformer tap chart reads like an order to run the windings far above rating. It is nothing of the kind. On a delta-wye unit with tap 2 delivering 600 V line-to-line from a 4160 V primary, that percentage is the square-root-of-three factor between the tabulated line-to-line voltage and the rated voltage of one wye phase winding, about 346 V. IEEE C57.12.00, General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers, defines transformer voltage ratings at no load and based on the turns ratio, so the winding's own voltage — not the system line voltage — is the basis the chart divides by. Nothing on the plate is asking for a tap change or a wiring change.

Where the 173 percent comes from #

In a wye connection, each phase winding runs from one line terminal to the common neutral point, and the three winding voltages are displaced 120 degrees from each other. Two voltages displaced 120 degrees add vectorially to √3 — about 1.732 — times either one, which is why a wye side's line-to-line voltage is 1.732 times its winding voltage. In a delta, the winding is connected directly across a pair of line conductors, so winding and line voltage are equal and no factor appears.

A "percent rated voltage" column on a wye secondary therefore compares the tabulated line-to-line tap voltage with the winding's rated voltage, and the connection fixes the result on every tap row. Ratings practice in North America comes from IEEE C57.12.00; the exact basis printed on a given plate is the manufacturer's, so read the plate's column heading, footnotes and connection diagram, and confirm the interpretation with the equipment documentation and your authority having jurisdiction.

The worked numbers #

Worked example, with every input stated: 60 Hz, no load, primary 4160 V line-to-line in delta, secondary 600 V line-to-line in wye, taken at the tap 2 row.

  • Winding voltage on the wye side: the tabulated secondary voltage divided by 1.732 gives 346.4 V across each phase winding.
  • The chart's percentage: 600 V over 346.4 V, times 100, gives 173.2 percent.
  • Line-to-line ratio: 4160 V over the tabulated secondary voltage gives 6.93.
  • Winding turns ratio: 4160 V over 346.4 V gives 12.0.

These are nameplate-based estimates; check them against the plate and the manufacturer's printed tap table before acting on them.

Why the line ratio and the turns ratio differ #

A ratio of 6.93 between lines and a turns ratio of 12.0 differ by exactly the √3 sitting on the wye side: multiply 6.93 by 1.732 and the turns figure comes back. The two numbers describe different things. The line ratio is what you measure between bus conductors on each side; the turns ratio is what the winding construction actually is, and it matters when you connect test sets, current transformers or protection to individual windings. The delta primary windings sit at full line voltage, each one directly across a pair of incoming conductors, so no reduction factor applies on that side.

The same line-versus-winding distinction shows up elsewhere: a motor nameplate lists line current rather than the current in each winding, and the article on why motor nameplate current is line current, not winding current, walks through that basis in detail.

Reading the rest of the tap chart #

The √3 factor belongs to the connection, not to the tap, so every row of a chart built this way shows about the same 173 percent: moving a tap scales the line-to-line figure and the winding figure together. Use the pattern to classify the column:

  • The same figure on every wye row: line-to-line voltage over winding rating. Nothing is being overdriven.
  • Small equal steps between rows: the column describes tap position or correction relative to the nominal tap, not a voltage basis.
  • One odd row among consistent ones: suspect a column shift, a misprint or a footnote tied to that entry. Read every heading, note and the connection diagram before interpreting a single row.

A tap itself only moves the secondary voltage in proportion to the primary turns it switches in or out — the same mechanism that makes a -5 percent tap overshoot secondary voltage at light load, covered in the article on why a -5 percent transformer tap overshoots voltage at light load. And if the chart's per-leg link patterns look inconsistent rather than the percentages, the article on why a machine transformer tap chart shows one leg's connections covers how those patterns read.

Checking it at the transformer #

De-energize the transformer and verify absence of voltage with a tester rated for the circuit before anyone opens a connection compartment, and treat the medium-voltage side as qualified-personnel work under the site's switching and grounding procedure. After the unit is restored through the approved switching sequence, measure all three primary phase pairs and all three secondary phase pairs with an instrument rated for the circuit. Near-nameplate primary voltage with each secondary line-to-line pair reading near 600 V, balanced across the three pairs, confirms the tap is performing as the chart states. Where the wye point is accessible, each line-to-neutral reading should sit near 346 V; a balanced line-to-line set with unbalanced line-to-neutral readings points to neutral continuity, grounding or load problems, which no tap change corrects.

The decision #

The 173 percent on this chart is the wye connection factor between line-to-line voltage and winding voltage, not a stress order: at nameplate tap and nameplate voltages the windings operate within rating, and the entry alone calls for no tap change, no tap-link move and no wiring change. Record the column basis, the link positions and the line-to-line and line-to-neutral readings in the maintenance log, so the next reader does not stop at the same number.

Questions asked

Why does a delta-wye transformer's line ratio differ from its turns ratio?

Only the wye side carries the square-root-of-three factor. In the worked example the line-to-line ratio is 6.93 and the winding turns ratio is about 12.0; multiplying 6.93 by 1.732 recovers the turns figure. On a delta-delta or wye-wye unit the two ratios would be equal, because both sides share one connection.

Should a percent rated voltage column make me change taps or wiring?

No. Select taps from the manufacturer's printed table to match the measured primary voltage, and only with the transformer de-energized, locked out and proven dead. The percentage records which voltage basis the chart used, so on its own it calls for no action at the transformer.

What if each tap row shows a different percentage?

Roughly the same figure on every row of a wye winding is the line-to-winding basis. Small equal steps between rows point to a tap-position or correction column, and one odd row among consistent ones suggests a column shift or a plate misprint. Read the column headings, footnotes and the connection diagram on the plate before drawing any conclusion.

What can I verify when the wye neutral point is not accessible?

Measure the three line-to-line pairs and judge balance among them; the winding voltage is implied at the line figure divided by the square root of three. Materially different line-to-line readings point to supply unbalance, mismatched tap links, loose connections or a winding problem, and none of those is corrected by moving a tap.

Keep reading

  • How-to

    Calculating voltage drop through step-up and step-down transformers

    Yes. A primary voltage drop passes through the turns ratio almost one-for-one in percent — 5% low at 12 kV is 5% low at 480 V — so the study must run every segment from the generator terminals to the farthest branch outlet, combining drops as percentages.

    Power distribution and transformers

  • Explainer

    Sizing a neutral grounding transformer on a 22 kV feeder

    A wye-delta bank that creates a neutral on a 3-wire 22 kV feeder is sized by the duty that neutral carries. A continuous 10 A single-phase load puts 127 kVA on one primary winding, so the three-phase nameplate lands near 381 kVA — take the next common rating, 500 kVA. A grounding-only neutral is sized from phase-to-ground voltage × fault current × a duration factor K.

    Power distribution and transformers

  • Explainer

    Reverse feeding a step-down transformer on a high leg delta

    Yes — feed the 240 V wye winding from your 240 V 4-wire delta service, leave X0 insulated and floating, take 480 V from the delta and corner ground it. Never tie X0 to the grounded center tap: it applies 0.50 per-unit zero-sequence voltage across windings rated 138.6 V and can circulate 25 per-unit current in a 2% impedance delta.

    Power distribution and transformers