Troubleshooting
Why a VFD cannot power a whole machine as a phase converter
Short answer
A VFD is a motor controller, not a three-phase utility source: its output feeds only the motor wired directly to its terminals. No contactor, drum switch or machine feeder belongs on that output, and reversal happens through the drive's ramp, not a lead swap. Size the drive to the motor nameplate and add braking resistance when fast stops return more energy than the drive absorbs.
On this page
- The boundary: one motor, wired directly
- Why the output is not utility three-phase
- No switching on the output
- Tapping: floating or rigid, decided before you wire
- Why fast reversals stress the DC bus
- Example: braking energy for a 2 hp spindle stopped from 1,800 rpm in 1 s
- The decision, case by case
- Questions asked
A VFD can power exactly one motor: the one wired straight to its output terminals. It is a motor controller, not a three-phase utility source, so it cannot supply a whole machine as a rotary phase converter — the control transformer, servo drives, coolant pump and solenoids all need their own supply. The same boundary rules out the machine-shop habits that come with the idea: no contactor or drum switch on the drive output, no plug reversing by swapping leads, and no reversal at all except through the drive's own ramp. What works is simpler: feed the spindle motor only, command run and direction through the drive's low-voltage control inputs, and fit a braking resistor when fast stops and tapping cycles return more energy than the drive absorbs. The sections below draw that boundary, work the braking numbers, and end with the decision for each case.
The boundary: one motor, wired directly #
Trace the machine's incoming three-phase feeder and list what hangs on it. On a typical small CNC mill that list is long: the spindle motor, two axis servo amplifiers, a control transformer feeding low-voltage logic, a coolant pump, solenoid valves, a work lamp. The drive may take exactly one item off that list — the spindle motor — and everything else stays on a supply matched to its own nameplate:
- Spindle motor — the only load allowed on the output; three leads run directly from the drive's output terminals to the motor terminal box.
- Control transformer and machine logic — fed from the single-phase supply; verify the transformer's primary taps accept the shop voltage.
- Axis servo amplifiers — their own rated supply, per the machine's wiring diagram.
- Coolant pump — its own starter or a small dedicated drive sized from the pump nameplate.
- Solenoids, work lamp, heaters — never on a drive output.
Sizing follows the motor, not the machine: match the drive's permitted output current to the spindle motor's nameplate full-load current after applying the manual's single-phase input rules. If the machine's kVA figure is pulling your eye, what a machine kVA nameplate means for VFD sizing separates the two numbers, and sizing a VFD for a three-phase motor on single-phase input walks the matching itself.
Chaining the drive into an idler motor so the idler manufactures a third leg puts the machine's independently switched loads onto an output that must carry none of them; the separate article on feeding a rotary phase converter idler from a VFD takes up that arrangement and its limits.
One safety step belongs before any rewiring here: lock out and tag the panel, test for absence of voltage at the drive terminals, and wait the DC-bus discharge time printed on the drive before touching its output or bus connections — the capacitors hold a charge for minutes after the input is off.
Why the output is not utility three-phase #
A drive output is a pulse-width-modulated switching waveform. The output transistors chop the DC bus at a few kilohertz and the motor's inductance turns that chopping into usable current; voltage and frequency are synthesized moment to moment for one motor following a speed command. There is no stiff sine wave behind the output and no spare capacity for distribution. A control transformer connected across the output sees high-frequency pulses through its windings, contactor coils and solenoids buzz or chatter, and unfiltered electronics misbehave. That is why the rule is absolute: the output feeds the motor, and nothing that switches, transforms or rectifies shares those three leads.
No switching on the output #
An output contactor adds two failure modes the drive cannot defend against. Opening under load interrupts current the output bridge is actively synthesizing; reclosing with a bounce slams a train of transients into the output stage, and whether that ends in a nuisance trip or a dead output stage depends on the drive's internal gate-drive design — something no nameplate reveals. Drive manufacturers' application guidance states it plainly: do not use a contactor between drive and motor for routine start and stop, and keep any two-speed or reversing switch out of the motor leads entirely.
Direction changes live in the control wiring instead. Run, stop and reverse go to the drive's low-voltage control inputs — a selector switch, a relay output or a controller output all work, and choosing how a CLICK PLC commands VFD speed safely covers the safe ways to do that from a controller. The drive ramps down through zero speed and up in the new direction, in command the whole time; the original drum switch leaves the motor circuit, not the panel wall.
Switching belongs on the input side: a disconnect or contactor ahead of the drive, or the drive's documented control inputs, are the designed places to remove power or torque. Where functional safety is required, IEC 61800-5-2 defines Safe Torque Off, a drive function that removes torque-producing energy without opening the motor circuit; confirm any safety-function requirement against the machine's risk assessment, the drive manual and your local authority having jurisdiction.
The exceptions are the ones the manual prints. Some drive manuals approve an output changeover between motors with a defined sequence: a drive digital output signals zero speed, that signal permits the contactor, and the contactor's auxiliary contact feeds back before the drive re-enables. Bypass schemes in fan and pump service interlock the output and bypass contactors mechanically and electrically to the manual's diagram. If your drive manual prints no such sequence, the exception does not exist for your drive.
Tapping: floating or rigid, decided before you wire #
Reversing for tapping splits into two cases. Floating tapping tolerates a little axial pitch mismatch between spindle and tap: program the drive's deceleration, stop and reverse through the control inputs and keep the reversal inside the tooling's travel. Rigid tapping holds the Z axis electronically geared to spindle position, and that takes hardware rather than intent — a spindle encoder feeding position to a controller that closes the gear loop. A direction input only requests torque in the opposite direction; it never synchronizes anything. Without the encoder and the gearing controller the move is floating tapping by definition, so program it as one, and prove the sequence above the workpiece with the drive in command through deceleration, zero speed and acceleration in reverse.
Why fast reversals stress the DC bus #
Every stop — and a tapping reversal is a full stop plus a start in reverse — hands the spindle's rotating energy back to the drive's DC bus. With nowhere to go, bus voltage climbs until the drive trips on overvoltage or its braking chopper and resistor burn the energy off. Whether a resistor is needed is a number you can work out before the first fault; the example below does the arithmetic.
Example: braking energy for a 2 hp spindle stopped from 1,800 rpm in 1 s #
The inputs are illustrative — a typical small-mill tapping cycle, stated so you can substitute your own nameplate and machine data:
- Speed at the start of the stop: 1,800 rpm.
- Total inertia at the motor shaft (motor rotor, spindle, tooling, drawbar): J = 0.05 kg·m².
- Ramp: constant deceleration to zero in 1.0 s.
- Duty: one tapping stop every 10 s.
The rule in words: angular speed is ω = 2πn/60 with n in rpm; rotating energy is E = ½Jω²; average braking power is the energy divided by the ramp time; for a constant-torque ramp the instantaneous power peaks at twice that average, right at the start of the ramp.
The arithmetic:
- ω = 2π × 1,800 / 60 = 188.5 rad/s
- E = 0.5 × 0.05 kg·m² × (188.5 rad/s)² = 0.5 × 0.05 × 35,532 = 888 J
- Average braking power = 888 J / 1.0 s = 888 W
- Peak braking power = 2 × 888 W = 1,777 W ≈ 1.78 kW
- Duty average = 888 J / 10 s = 89 W
The result: the stop returns 888 J to the bus, arriving at 1.78 kW peak with an 89 W duty average. The physics fixes those numbers; the document that says how much of this the drive can absorb is that drive's own manual, and friction and windage return slightly less than the calculation, so treat the result as a conservative estimate.
The decision: the drive's built-in braking must be documented to absorb an 888 J pulse at 1.78 kW peak and that duty average. If the manual's braking figures for the model fall short, lengthen the ramp first — 2.0 s halves both powers to 888 W peak and 444 W average while the energy per stop stays 888 J. If the cycle time cannot grow, fit a braking resistor whose pulse-energy rating covers 888 J per stop, whose peak power covers 1.78 kW and whose continuous rating covers the 89 W duty. What moves the number: energy scales linearly with inertia and with speed squared, so the same stop from 3,600 rpm returns 3,553 J — four times the energy, and four times both powers for the same ramp.
The decision, case by case #
- Whole machine on one VFD output — no. Split the machine: the spindle on the drive, everything else on a supply matched to its nameplate.
- Machine fed through a VFD-driven idler — no; the drive still controls one motor and must not carry the machine's distribution.
- Spindle motor only, leads direct, commands on the control inputs — yes; that is the design that works.
- Contactor or drum switch interrupting the motor leads — no, unless your drive manual prints a zero-speed interlocked changeover with contactor feedback; then follow its sequence exactly.
- Plug reversing by swapping leads while the spindle spins — never; command reverse through the drive and let it ramp.
- Rigid tapping without a spindle encoder and a gearing controller — not available; run it as floating tapping or add the feedback hardware.
- Overvoltage trips on fast stops — work the braking numbers above, lengthen the ramp first, then fit a resistor sized to the computed pulse.
Questions asked
Can one VFD run the spindle motor and the coolant pump at the same time?
No. The pump starts and stops independently of the speed command, so the drive would see a load that changes without its knowledge, and neither motor gets correct protection. Give the pump its own small drive sized from the pump nameplate, or feed it from the machine's separate supply. Only motors that always start together and share the load evenly belong on one drive, and then only when the drive manual allows multi-motor output.
How do I verify the DC bus is discharged before touching the motor leads?
Apply lockout on the input, wait the discharge time printed on the drive's label or manual, then measure across the DC bus terminals with a meter rated for that bus voltage. Treat the output leads as live until the reading is below the threshold the manual states. The capacitors can hold a charge for several minutes, and a motor that coasts or is back-spun can also feed energy into the bus through the output stage.
Where should a spindle-running feedback signal come from?
From a drive digital or relay output programmed as a run or at-speed status, not from an auxiliary contact on a motor-lead contactor. Most drives let you assign a status relay to a run or zero-speed condition, which is also the feedback a documented output changeover needs to prove the drive is at zero before the contactor may switch. Wiring machine interlocks to these outputs keeps every switching decision inside the drive's own logic.
Does a drive's single-phase input rating differ from its three-phase rating?
Yes, usually. The input rectifier and DC bus see higher ripple current on single phase, so manufacturers publish a separate allowed-output figure or a derating table for single-phase input, and some models are not approved for it at all. Use the single-phase table for the specific model, compare its permitted output current with the motor nameplate current, and size the input branch from the manual's listed input current rather than assuming the three-phase figure.