Troubleshooting
Why a VFD output relay setting contradicts the manual
Short answer
On the reported spindle inverter the coolant relay closed with the spindle running at PD052 = 2 while the manual called function 2 fault condition, and value 1 held the contact closed continuously. The measured states decide: keep PD052 at 2, wire the pair that reads open at stop, and switch any pump above the contact's 3 A ceiling through an external relay.

On this page
On the reported spindle inverter, the mist-coolant relay closed when the spindle ran with a speed command at PD052 = 2, even though the manual described function 2 as fault condition, and a setting of 1 held the contact closed continuously. The contact-state test outranks the label: on that unit, value 2 is the running indication, so PD052 stays at 2. Wire the screw pair that reads open with the drive stopped, and treat the contact's reported current ceiling as a hard limit: a pump below it switches direct, a pump above it gets an external relay. The test below proves which value and which screw your own drive is using.
What the reported drive actually did #
The installation in question ran a CNC spindle on a small inverter and wanted mist coolant on with the spindle. Two values were tried on the relay output the manual assigns to PD052, with these reported results:
| PD052 value | Contact, drive stopped | Contact, drive running | Verdict for coolant |
|---|---|---|---|
| 1 | closed | closed, on all the time | no state change, cannot sequence coolant |
| 2 | open | closed once running with the speed command raised | matches coolant-on-with-spindle |
Those rows are one install's report, not a bench measurement of your drive; the test below turns them into evidence on your own unit. Against that behavior stand two written descriptions: the manual supplied with the drive showed value 1 as run and value 2 as fault condition, while a second description for the same drive family lists function 01 as "VFD running" and function 05 as "set frequency reached" on outputs it numbers 3 and 4. The reported drive follows neither table cleanly, and that is the whole problem.
Why the label loses to the meter #
Four things explain a table that disagrees with the contact, and all four point the same way:
- Documentation drifts. Production runs and manual revisions within one drive family can map the same parameter number to a different function, so a printed table may describe another hardware revision than the one on your bench.
- Fault functions read inverted. Fault-status outputs commonly energize while the drive is healthy and drop only on a trip, so a contact that stays closed on a healthy drive, exactly what value 1 did, is consistent with a fault-healthy function.
- The display settles it. A contact that closes on a run command while no fault code is shown cannot be reporting a fault, whatever the table calls that value.
- The screw inverts the reading. An at-rest relay shows continuity on its normally closed screw and an open on its normally open screw, so one function reads opposite on the two. There is also a second relay: PD053 controls the KA/KB pair, an independent contact whose setting does not follow PD052.
The function of a contact is the state it holds at each drive condition on your unit; every table is a hypothesis until a meter confirms it.
The contact-state test #
Take the readings without probing inside an energized drive:
- Lock out the drive's input feeder and verify absence of voltage at the terminals you will touch, with a meter rated for that circuit. The relay contacts are dry, but the neighbouring power terminals sit at line and DC-bus potential, so the terminal area opens only de-energized and verified.
- Disconnect the coolant wires at the pump or external-relay end and leave them on the drive's control terminal strip, so the contact can be read from the free wire ends with everything closed up.
- Note which position the wires occupy, normally open or normally closed, from the terminal markings.
- Restore power, set PD052 to 1, and read continuity across the free ends with the drive stopped, then running with a speed command raised; the relay's click is a useful cross-check.
- Set PD052 to 2 and repeat the same two readings.
- Power down and lock out again before moving any wire. Keep the value and the screw that read open at stop and closed at run.
PD052 and PD053 are the numbers on this reported inverter; other drives name and number their relay functions differently, so nothing transfers by number, only the test does.
Choosing the setting and load path for the reported spindle drive #
The case: a CNC spindle inverter whose coolant must run with the spindle, a manual whose labels disagree with the contacts, and a pump that may or may not fit the relay.
Inputs, with where each comes from:
- PD052 = 2: contact open with the drive stopped, closed once running with a speed command (the reported installation).
- PD052 = 1: contact closed continuously, stopped and running (the reported installation).
- Written tables: value 1 labeled run and value 2 labeled fault condition in the supplied manual; function 01 "VFD running" and function 05 "set frequency reached" in a second description for the drive family.
- Contact ceiling: 3 A, as reported for this drive's relay output; confirm the figure on your unit's own label or manual before loading it.
- Interposing-relay capacity, one documented example: the V7 T3 control relay catalogue sheet rates each main pole at 40 A up to 300 V AC.
The rule, in words: keep the value whose measured states match the wanted sequence, open with the spindle stopped and closed with it running, and pick the load path by comparing the pump's nameplate current with the contact ceiling: direct at or below it, an interposing relay above it.
The arithmetic:
- State changes across stop and run: value 1 gives 0, value 2 gives 1, at the run command. The sequence needs exactly that 1 change, so value 2 is the coolant function on this unit.
- Headroom if the pump exceeds the ceiling: 40 A ÷ 3 A ≈ 13, so one pole of the interposing relay carries roughly thirteen times what the drive contact is reported to handle, and the drive contact then carries only the relay coil, whose sealed current the relay's datasheet lists far below the ceiling.
Result: PD052 stays at 2, on the pair that reads open at stop; the pump sits directly on the contact only within the ceiling, otherwise behind the interposing relay.
Decision: above 3 A of pump current, fit an interposing relay; at or below 3 A, the drive contact may switch the pump directly.
Wiring the coolant circuit #
- Wire the pair that reads open at stop, so the pump cannot run with the spindle idle.
- Within the ceiling, the pump can sit straight across the contact, with margin: a motor pushes several times its nameplate current through the contact during start.
- Above the ceiling, put the drive contact in series with an external relay coil matched to a control supply you already have, and let that relay's pole carry the pump, so the contact stays out of the motor inrush entirely. The same NO-versus-NC choice and signal routing come up when wiring a 0-10 V speed reference and fault relay to a VFD.
- If the pump needs a contactor and its own overload, the drive contact pilots that coil instead; the signal chain is the one in wiring a three-phase coolant pump starter from a 120 V signal.
- Where this circuit sits inside an industrial control panel, UL 508A, the Standard for Industrial Control Panels, governs the panel's construction, meaning component ratings, spacing and wiring methods; confirm the edition in force and any local amendments with the authority having jurisdiction and the panel's documentation.
If no setting moves the contact #
- Confirm which relay you are on: PD053 controls the KA/KB pair, and no value placed in PD052 will ever move those screws.
- If your unit's table lists a frequency-reached function, test it the same way; it is the right event when mist must wait for commanded speed.
- Watch the display while the contact moves; closure on a run command with no fault code shown is a run indication on your unit, whatever number the table gives it.
- If no documented value changes the state at either screw, the output itself is suspect. Get the documentation for the exact nameplate model from the supplier before replacing anything; the parameter map of that revision is the missing piece.
The decision for each case:
- Contact closes on run and opens at stop: keep that value, wire the open-at-stop pair, keep the load within the ceiling.
- Contact closed at rest and running: you are on the wrong screw or on a fault-healthy function, so meter the other screw and retest.
- Contact never moves: wrong relay, so check the KA/KB pair and PD053, or a failed output; document the exact model and escalate.
- Pump above the ceiling: the contact drives an interposing relay or a starter coil, never the pump itself.
Questions asked
Can I move the coolant to PD053 instead of PD052?
Yes, if you rewire to the KA/KB pair that PD053 controls; it is a second, independent relay. Leave it untouched while unused, never copy a PD052 value into it by assumption, and set the function only for the pair your wires actually land on, then repeat the stopped-and-running continuity check on that pair before connecting the pump.
Will the relay open if the drive trips while the coolant is running?
That state was never recorded in the reported installation, so treat it as unproven on your unit. If mist must stop on a trip, assign a fault function to the second relay on KA/KB and wire that contact as a dedicated cut-off, or prove the main contact's response under a controlled, safe trip condition before relying on it.
Why did value 1 hold the relay closed all the time?
A contact closed on a healthy drive, stopped or running, fits a fault-healthy function, since fault outputs commonly energize while healthy and drop only on a trip. That supports a by-one shift in the reported manual's table, with value 2 acting as run and value 1 as fault status, which only a meter at both screws, stopped and running, can confirm on your unit.
Is the relay contact rating enough for a mist pump?
Compare the pump's nameplate current with the contact's 3 A ceiling and remember that a motor draws several times its nameplate current at start. A pump near the ceiling is better served through an interposing relay or a starter coil, which also gives the pump its own overload protection.
Should coolant wait for commanded speed instead of any run command?
If mist must begin only near commanded speed, look for the set-frequency-reached function in your unit's table and test it the same way; it closes when the output reaches the commanded frequency, later in a ramp than a plain running indication. The reported drive already closed on a raised speed command rather than at standstill, which behaves close to that.