Explainer
Why an MV cable or bus duct has no separate overload rating
Short answer
No. A medium-voltage cable or bus duct has no separate continuous overload rating; the only limit is conductor and insulation temperature. The citable overload figure is a recalculated ampacity for the cable's real installation, or the manufacturer's written rating at site ambient for the bus duct, never a generic percentage.

On this page
- Does an MV cable or bus duct have a continuous overload rating built in?
- What actually limits the current: conductor temperature or insulation life?
- How much extra current does a cooler site actually buy?
- How do I calculate the real continuous margin on the cable run?
- What makes a bus duct overload figure citable?
- When is a short-time or emergency overload allowed?
- How do I confirm the feeder holds its limit at the higher load?
- What is the decision for each case?
- Questions asked
An MV feeder that reads above its nameplate current has no separate overload rating to fall back on: a cable and a bus duct are held to one limit only, the temperature of the conductor, insulation, joints and enclosure. Any continuous overload capability is the margin between the temperature your real installation produces and the temperature the published rating assumed. You can calculate that margin for a cable, get it in writing for a bus duct, and confirm it by measurement — but it is never a generic percentage applied to the nameplate. The sections below build the margin in the order you meet it, and each one ends with something you can record.
Does an MV cable or bus duct have a continuous overload rating built in? #
No. Neither a medium-voltage cable nor a bus duct carries a separate overload rating; the only limit is the temperature of conductor, insulation, joints and enclosure, and every amp above the rated current is justified against that temperature, not against a nameplate percentage.
The rated current is the current that brings the hottest point of the assembly to its maximum allowed temperature at steady state under a stated set of conditions: ambient, installation and loading pattern. Current above that value pushes the hottest point past the limit, given time. Continuous overload capability therefore exists in exactly two places: where your site conditions are better than the conditions the rating assumed, or where the manufacturer states a higher rating for your conditions in writing. First record the rating basis for each element — the cable datasheet or ampacity calculation, the bus duct nameplate and its temperature-rise test report. If you cannot state the ambient and installation assumptions behind the number, you do not have a margin yet.
What actually limits the current: conductor temperature or insulation life? #
Both, and they are one constraint: conductor loss heats the metal, the heat flows out through insulation, air or soil, and insulation ages faster as its temperature climbs, so a steady temperature above the limit spends cable life even when nothing trips.
At steady state the heat generated equals the heat removed:
I² × R_ac = (T_conductor − T_ambient) ÷ R_thermal
so the maximum current is:
I_max = √( (T_max − T_ambient) ÷ (R_ac × R_thermal) )
Every overload question is a question about the right-hand side. The aging side does not forgive: each excursion above the rated temperature spends insulation life, and the spend is cumulative — it is not reset when the load drops back.
| Element | What limits it | Where real margin comes from |
|---|---|---|
| MV power cable | Conductor and insulation temperature | Lower actual soil or air temperature, wider spacing, fewer loaded circuits in the same duct bank or tray, lower load factor |
| MV bus duct | Temperature rise of conductors, joints and enclosure, set by the type test | Ambient below the test basis, better ventilation, a manufacturer rating stated for your conditions |
How much extra current does a cooler site actually buy? #
Very little: current scales with the square root of the available temperature rise, so a cable or duct needs about 21 percent more rise to carry 10 percent more current, and a 10 percent overload produces 21 percent more heat in the conductors.
The loss side first: 10 percent more current means (1.10)² = 1.21, so 21 percent more heat must leave through the same thermal path, which means roughly 21 percent more temperature rise. The current side inverts it: I_new ÷ I_rated ≈ √(rise available ÷ rise assumed).
A worked example, stated as arithmetic rather than a rating. Hypothetical inputs: a 15 kV XLPE cable rated 550 A continuous with the conductor at 90 °C in 40 °C air; your tray run sees 30 °C air at the worst hour.
- Rise the rating assumed: 90 °C − 40 °C = 50 K
- Rise available on your site: 90 °C − 30 °C = 60 K
- Ratio: 60 K ÷ 50 K = 1.20
- First-pass current: 550 A × √1.20 = 550 A × 1.095 ≈ 602 A
That looks like (602 − 550) ÷ 550 = 9.5 percent of margin, but conductor resistance rises with conductor temperature, so the true gain is smaller. Treat this scaling as the test of whether a full calculation is worth doing; the citable figure is the recalculation below, and it will land below 602 A.
How do I calculate the real continuous margin on the cable run? #
Recalculate the ampacity for the installation as built — IEC 60287 gives the method, and its 60287-1-1:2023 edition provides the current-rating equations for 100 percent load factor — then compare that figure with the sustained load current on the worst segment.
The steps, in order:
- Collect the cable construction: conductor size and material, insulation type, and the maximum conductor temperature — read from your datasheet, not carried over from another cable type.
- Record the installation as built: direct buried, duct bank, tray or air; the number of adjacent loaded circuits; spacing; burial depth; soil thermal resistivity or ambient air temperature.
- Recalculate the ampacity for those inputs using the method your project specifies — the IEC 60287 equations, or the manufacturer's ampacity tables and correction factors for your exact cable.
- Compare the result with the sustained load current; the difference is the continuous margin. A recalculated value below the load current means the feeder is overloaded regardless of the nameplate.
- Use the worst segment — the buried run beside a heat source, a duct crossing, a bundled tray section — because the hottest segment sets the limit for the whole circuit.
The result is an estimate: check it against the governing code and the cable documentation before it goes into a justification. The same temperature basis is what sets the cable size for a 4160 V motor: ampacity against the installation first, voltage drop after.
What makes a bus duct overload figure citable? #
Only the manufacturer's written rating at your site's ambient and altitude, backed by the temperature-rise type test; that letter is the reference you cite in a design justification, because no general formula replaces the test.
A bus duct rating comes from a temperature-rise type test of one manufacturer's conductor, joint and enclosure design together, so a scaling rule borrowed from another duct proves nothing about yours. Ask the manufacturer for:
- the rated current and the ambient of the type test, from the nameplate and the test report;
- the temperature-rise limits for conductor, joints and enclosure — joints often govern;
- a written continuous-current rating at your actual ambient and altitude;
- the joint torque and condition, because a loose joint runs hotter than the tested design even at rated current.
A generic derating percentage is not a citable basis; the written figure, naming the ambient it applies to, is.
When is a short-time or emergency overload allowed? #
Only where the cable standard or the manufacturer defines the allowance, and then only inside its stated duration and annual cumulative hours; if no document gives you those two numbers, there is no emergency overload to claim.
Some cable standards and manufacturers publish an emergency allowance at a higher conductor temperature, with a permitted duration per event and a cap on cumulative hours per year. Read all three — temperature, duration and annual hours — from the document for your cable, and log the hours you use, because the aging they spend adds up across events. An overload inside such an allowance is a bounded, tracked event, never a standing operating point. Note what the breaker contributes: its long-time setting can sit above the cable's ampacity, but no trip setting raises the cable's temperature limit — coordination protects the conductor from faults, not from steady overcurrent.
How do I confirm the feeder holds its limit at the higher load? #
Log a full load cycle and compare the sustained current against the lower of the recalculated cable ampacity and the manufacturer's bus duct figure, because the lower of the two governs the whole feeder.
Pull a day's current record from the feeder relay or meter and separate the peak from the sustained level — thermal limits answer to the sustained level, with peaks covered only if a documented emergency allowance exists. Then scan the bus duct joints and the cable terminations with an infrared camera at peak load and compare each reading with the temperature-rise limits in the test report; a joint running hotter than its neighbors points to contact resistance, not to spare capacity.
One safety note, because that scan is done under load: use installed infrared windows, and install new windows with the feeder de-energized and verified dead. Any energized work is governed by your site's NFPA 70E (2024 edition) program — the standard that covers workplace electrical safety, arc-flash risk assessment and PPE — so follow that program and the local authority having jurisdiction, and do not treat a cover-off scan as routine.
What is the decision for each case? #
For a cable, the citable continuous overload figure is the recalculated ampacity of the worst segment; for a bus duct, it is the manufacturer's written rating at site conditions; where neither covers the sustained current, the overload is not justified and the hardware changes.
- Cable case: sustained current below the recalculated ampacity — run it, with the inputs recorded next to the figure. Above it, the feeder is overloaded whatever the nameplate says.
- Bus duct case: sustained current below the manufacturer's written rating at your ambient and altitude — run it. No letter, no overload above nameplate.
- Neither case: reduce the load, add a parallel circuit or upsize the conductor. Temperature monitoring on the worst segment tells you where you stand; it does not raise the limit.
Judging every conductor against its own temperature is also why a smaller incomer cable can feed larger sub cables: the incomer's rating caps the incomer, and each sub-cable is sized to its own load and installation.
Questions asked
Can the cable's short-circuit temperature rating be used as an overload limit?
No. The short-circuit rating covers a fault current flowing for the second or so before the protective device clears it, calculated as a single adiabatic event from the conductor's heat capacity. A continuous overload is a steady thermal state limited by heat escaping to the surroundings, so the short-circuit figure never justifies extra continuous current.
Does altitude change a bus duct's rating?
Yes. Air density falls with altitude, so convective cooling weakens and a duct type-tested at low altitude carries less current on a high site; thinner air also reduces the insulation strength the design was tested against. The written rating you request must name the site altitude along with the ambient, because a figure stated for a low-altitude installation does not cover a high one.
Does an infrared scan prove the feeder can carry more current?
No. A thermal image shows the temperatures at the load and ambient of that one moment, so it confirms a calculated margin under those conditions but never extends the rating. Record the feeder current and the ambient with every image, or the reading cannot be compared with the test-report limits later.
How much does soil thermal resistivity change a buried cable's ampacity?
Enough that it can dominate every other input: the soil is most of the thermal path from a buried conductor to ambient, and dry or backfilled soil resists heat flow far more than moist native ground. The recalculated ampacity must use the project's measured or specified soil value rather than a default, and soil drying around a heavily loaded cable makes the real margin shrink over time.