Troubleshooting
Aerial bundled cable voltage drop on a 350 m 415 V run
Short answer
Your arithmetic is right: 150 A over 350 m at 1.43 mV/A/m gives about 75 V, and that coefficient behaves like a unity-power-factor figure at 90 °C. At 0.8 power factor the phasor calculation gives about 66 V line-to-line, 15.9% of nominal, leaving roughly 349 V at the load. This 50 mm² aluminum run fails continuous voltage limits; upsize to about 185 mm² aluminum, which holds the drop near 4.5%.

On this page
- Is my 75 V voltage drop calculation wrong?
- What does the 1.43 mV/A/m coefficient actually assume?
- How do I calculate the real voltage drop on this run?
- Is a 15.9% drop acceptable for a motor start or for running?
- Can a 50 mm² aluminum aerial bundled cable carry the full-load current at all?
- What actually fixes the voltage drop on this feeder?
- How do I confirm the run after the change?
- Questions asked
Nothing is wrong with your arithmetic: the full-load current over that route at 1.43 mV/A/m really does give about 75 V, and that number is not the odd one out. At the load's 0.8 lagging power factor a full phasor calculation trims it, but the run still ends far outside any voltage limit. The real mistakes are trusting one tabulated coefficient without checking its basis, and asking 50 mm² aluminum to carry the full-load current over that route at all. Here are the numbers, the standards that judge them, and the fix that clears both.
Is my 75 V voltage drop calculation wrong? #
No — running current × route length × 1.43 mV/A/m ÷ 1000 = 75.1 V line-to-line, the multiplication is sound, and the same run through a phasor calculation at 0.8 power factor still lands near 66 V, about 16% of nominal.
Drop scales linearly with current and with route length, so no rearrangement of those three inputs changes the verdict. The open question is whether 1.43 mV/A/m belongs to this cable, this conductor material, this temperature and this load power factor. A copper figure will not answer an aluminum question: a 53 mm² copper conductor at 0.39 Ω/km gives roughly 35 V line-to-line on this same run at unity power factor, so swapping materials swaps the answer. And the basis cuts the other way too: if the table value were per conductor, line-to-neutral, the true line-to-line drop would be about 130 V, not 75. Interrogate the table before you trust its output.
What does the 1.43 mV/A/m coefficient actually assume? #
Back-calculate it: 1.732 × 0.822 Ω/km = 1.42 mV/A/m, so 1.43 behaves like √3 times the resistance of 50 mm² aluminum at 90 °C — a three-phase line-to-line figure taken hot, with no power factor or reactance term.
That reading fits how a unity-power-factor load behaves on this cable: run the phasor formula at pf 1 and the coefficient's figure comes back to within a volt. Four footnotes decide whether the value transfers to your job:
- Temperature basis: the example cable's 0.641 Ω/km at 20 °C rises about 28% to 0.822 Ω/km at the 90 °C XLPE limit, so a cold-cable coefficient understates a hot, fully loaded feeder.
- Stranding: a plain resistivity calculation for 50 mm² aluminum gives 0.566 Ω/km; the datasheet's 0.641 Ω/km is the stranded figure and is the one that governs.
- Power factor: the coefficient carries no pf term; at 0.8 lagging the real drop comes out lower than the table suggests, never higher.
- Line-to-line or per conductor: the header or footnote must say which, because the two bases differ by a factor of 1.732.
Whichever basis the footnote declares, this run lands between about 64 and 75 V, so the coefficient argument cannot rescue the installation.
How do I calculate the real voltage drop on this run? #
Use the three-phase phasor relation ΔV_LL ≈ √3 × I × (R cosφ + X sinφ) with AC resistance at operating temperature: on this run it returns about 64 V, and the exact expression returns 66 V line-to-line at full-load current and 0.8 power factor.
Worked example, every input stated: 415 V, 50 Hz, 150 A, 350 m, 3 × 50 mm² aluminum XLPE, reactance about 0.08 Ω/km, load power factor 0.8:
- R at 90 °C: 0.641 × (1 + 0.004 × 70) = 0.641 × 1.28 = 0.822 Ω/km, which is 0.288 Ω over the route.
- Reactance: 0.08 Ω/km × 0.35 km = 0.028 Ω.
- IR = 150 × 0.288 = 43.2 V; IX = 150 × 0.028 = 4.2 V.
- Quick estimate: ΔV_LL ≈ 1.732 × (43.2 × 0.8 + 4.2 × 0.6) = 1.732 × 37.1 = 64.3 V.
- Exact phasor: with V_s = 415 ÷ 1.732 = 239.6 V per phase, the full expression V_s + IR cosφ + IX sinφ − √(V_s² − (IX cosφ − IR sinφ)²) gives 38.1 V per phase, which is 66.1 V line-to-line — 15.9% of 415 V, leaving 349 V at the load.
The 2 V spread between the two methods is the second-order term the estimate drops; use either and call the result an estimate, checked against any drop limit the governing code or local amendment sets and against the equipment documentation. The resistance-at-temperature step follows the approach the IEC 60287 series standardizes for cable conductor resistance, and your datasheet's own resistance and reactance columns override every number above. Power factor is the input people most often mispick — which power factor to use in a motor current calculation works through that choice for motor loads.
Is a 15.9% drop acceptable for a motor start or for running? #
For running, no: this drop leaves about 349 V at the load, while IEC 60034-1:2017, the rotating-machine rating and performance standard, keeps continuous motor operation inside ±5% of rated voltage in its Zone A — roughly 394 to 436 V at the terminals of a motor of that rating.
The Zone A band hangs off the nameplate, not the bus: a 400 V motor fed from the switchboard must hold 380 to 420 V at its terminals, a tighter window than the supply's nominal suggests. NEMA MG-1 (2021 edition) lets general-purpose AC motors run within ±10% of rated voltage at rated frequency, and even that wider band does not rescue 349 V. Confirm the band that governs your machine against its nameplate and documentation, and with your local authority having jurisdiction where a local rule sets a feeder drop limit. A start is a separate test: the dip is transient and is judged on accelerating torque, which falls with the square of the voltage — at 84% of rated voltage the motor delivers about 70% of rated torque — and on what the contactor and control supply can hold through. Those checks are their own calculations with the source impedance included: what decides acceptable voltage drop for MV motor starts walks the acceptance logic, and motor starting voltage dip with the utility short-circuit capacity shows how the source shares the shortfall. An across-the-line start draws several times the running current, so the dip at start is proportionally deeper than anything computed at that load.
Decision: reject this run for continuous service at full load on voltage grounds; for starting, run the dip study first, because the start current multiplies the drop several-fold.
Can a 50 mm² aluminum aerial bundled cable carry the full-load current at all? #
It is right on the line: that example cable's admissible current is stated near 149 A in 40 °C ambient air without sunshine, so the load already exceeds it before any derating for sun, grouping or support spacing.
Ampacity is a separate gate from voltage drop, and no voltage-drop arithmetic justifies exceeding it. Outdoors the generous assumptions fade: sun on the bundle, ambient above 40 °C and the details of the fixing arrangement all reduce the allowable current — aerial bundled cable installation for in-plant 480 V power distribution explains how installation conditions reshape an aerial run's numbers. Take the ampacity from your cable's own table at your conditions, never from a different construction's datasheet.
Decision: even where the ampacity table passes, this run already fails on voltage; where the sun is on the bundle or the ambient is hotter, it fails twice.
What actually fixes the voltage drop on this feeder? #
A larger conductor is the fix: at the running current and 0.8 power factor over 350 m, 185 mm² aluminum gives about 18.6 V line-to-line (4.5%), 120 mm² gives about 26 V (6.4%), and no 50 mm² arrangement survives.
Check the 185 mm² figure from a generic stranded-aluminum resistivity of 0.0283 Ω·mm²/m: R at 20 °C ≈ 1000 × 0.0283 ÷ 185 = 0.153 Ω/km, which at 90 °C is 0.196 Ω/km, or 0.069 Ω over the route. Then ΔV_LL ≈ 1.732 × 150 × (0.069 × 0.8 + 0.028 × 0.6) = 259.8 × 0.072 = 18.7 V, which is 4.5% of 415 V. Confirm against the datasheet of the size you actually buy; the resistivity above is generic and reactance moves a little with conductor diameter and bundle geometry. Read that datasheet the way the 33 kV 240 mm² aluminum aerial bundled cable specifications guide lays its data out: resistance, reactance and ampacity, each under stated conditions.
The levers, in the order they pay:
- Upsize the conductor — about 185 mm² aluminum holds 4.5% at full load on this route.
- Shorten the route — drop scales with length, and half the route halves the drop: this cable at 175 m still gives about 33 V (8%), which fails on its own, so a length cut needs a moderate upsize with it.
- Trim the load current — at 100 A the drop is about 44 V (10.6%) and at 75 A about 33 V (8%): no realistic load reduction puts 50 mm² inside a 5% band.
- Move the transformation point — stepping down beside the load shortens the low-voltage section; calculating voltage drop through step-up and step-down transformers shows how to count the transformer's own drop before assuming the move pays.
Decision: upsize to roughly 185 mm² aluminum, or cut the route far enough that a mid-size conductor clears 5% at full load, then re-check ampacity at the real ambient.
How do I confirm the run after the change? #
Measure source and load line-to-line voltage together with the running current and compare against the prediction: the upsize cable should read around 19 V of drop at the running current, and the two ends should be read at the same moment under the same load.
Use a true-RMS instrument for voltage and current and read from panel meters or closed-door test points where the panel provides them. Expect a small spread: a lightly loaded new cable runs cool, its resistance sits nearer the 20 °C figure, and the measured drop lands a little under the calculation — re-read at full load before signing off. A reading well above the prediction points to an underestimated route length, a copper-aluminum mix-up in the cable schedule, or a joint: at the running current, just 0.01 Ω of contact resistance adds 1.5 V at a single terminator.
Before any enclosure is opened to reach a terminal, de-energize, lock out and prove absence of voltage — NFPA 70E (2024 edition) sets that sequence for electrical work in US practice, and your local authority having jurisdiction and site rules govern the details everywhere else.
Decision: the change is proven when the measured drop at full load matches the prediction within a few volts and the ampacity table passes at your conditions; until both close, keep the load at the level the measurements support.
Questions asked
What does mV/A/m mean on a cable voltage drop table?
Millivolts of drop for each ampere of load current over each metre of route: multiply by current and length, then divide by 1000. A three-phase line-to-line value is used as printed; a per-conductor value needs the 1.732 factor; a single-phase circuit uses the out-and-back loop length. The header or footnote of the table you are reading states its basis — never assume it.
Does the starting dip use the same mV/A/m arithmetic?
No. While a motor accelerates it draws several times its running current, and the cable, the motor's own impedance and the source all share that current, so the dip is far deeper than the running-current table value suggests. A start study combines the three impedances, which is why the tabulated coefficient only sizes continuous service.
Does copper at the same cross-section rescue this run?
No. A 53 mm² copper conductor at about 0.39 Ω/km at 20 °C drops roughly 35 V line-to-line on the same 150 A run at unity power factor, close to 8.5% of 415 V. Copper's conductivity helps but the cross-section is still far too small for this length; the conclusion is a bigger conductor either way.
Why does my measured drop come out lower than the calculation?
The calculation assumes the conductor at its 90 °C XLPE limit. A lightly loaded cable sits near ambient, where resistance is close to the 20 °C value — about 22% lower than the hot figure — so the measured drop lands under the prediction. Judge the run at full-load temperature, which is the condition the feeder has to survive.
Is 1.43 mV/A/m wrong because 66 V and 75 V disagree?
Neither number is wrong; they answer different questions. The coefficient's arithmetic is the hot-conductor, unity-power-factor drop, and 66 V is the same run at 0.8 lagging, where the reactance term trims the total. Both are 16-18% of nominal voltage, so whichever figure your table intends, the run fails the continuous limits and needs more copper.