Why autotransformer start inrush can exceed DOL current

Motors and motor starters Published 6 min read By Current Intel engineering team

Short answer

An autotransformer start that measures above the DOL figure usually has a comparison problem, not a failed starter. On an 85 percent tap the supply current should be about 72 percent of the across-the-line value; the worked example below shows the arithmetic for a 3.6 MW motor and the checks that explain a reading above it.

On this page
  1. What an autotransformer tap does to the current
  2. Worked example: 3.6 MW motor on an 85 percent tap
  3. Check the tap connection first
  4. Read the meter on a single basis
  5. Watch the transition to full voltage
  6. Weigh the feeder, the sag and the capacitor bank
  7. The checks to run, in order
  8. The decision, reading by reading
  9. Questions asked

A start current that reads above the direct-on-line figure on an autotransformer starter almost never means the starter failed to reduce current. At an 85 percent tap the idealized supply current is 0.85 squared, about 72 percent of the across-the-line value, so a reading near or above the DOL number points at five places: the tap connection, the meter basis, the first-cycle DC offset, the transition to full voltage, or the source behind a sagging feeder. This article works a real 3.6 MW commissioning case end to end and ends with the decision for each kind of reading you can get.

What an autotransformer tap does to the current #

Locked-rotor current in an induction motor is roughly proportional to the voltage at its terminals. The autotransformer splits that proportionality in two. The motor winding sees the tap fraction k of the applied voltage and draws about k times its across-the-line locked-rotor current. The supply sees the transformer, and its idealized line current is k squared times the across-the-line value, because the transformer scales current with its ratio. Torque falls the same way, with k squared, so the tap sets your breakaway and acceleration margin as much as it sets the current. The same relationship is worked numerically for the starter's kVA draw at a neighboring tap in.

Worked example: 3.6 MW motor on an 85 percent tap #

Inputs, all from the commissioning record of the case:

  • Manual DOL locked-rotor current: 1140 A, manufacturer data at rated voltage from a stiff source.
  • A calculated across-the-line estimate of about 850 A circulated before the start; it was never measured.
  • Tap connection: 85 percent.
  • Field reading during start: 1050 A recorded at the starter input, with a 15 percent dip on the feeder.
  • Supply: at the far end of a long 70 mm² overhead line, with 5 MVAr of switchable start capacitors holding the feeder up.

Rule in words: line current is roughly the tap fraction squared times the across-the-line locked-rotor current, and motor-terminal current is roughly the tap fraction times it.

Arithmetic:

  • I_line = 0.85² × 1140 A = 0.7225 × 1140 A = 824 A
  • I_motor = 0.85 × 1140 A = 969 A

Result: from a stiff source this start draws about 824 A from the line and 969 A at the motor terminals.

Decision: a supply-side reading near 824 A says the starter is doing its job, and a motor-side reading near 969 A says the same. The recorded 1050 A sits 27 percent above the ideal line figure and 8 percent above the ideal motor-terminal figure, yet still below the datasheet across-the-line value — the reduction is present but weaker than the model predicts. Work the four checks below in order before condemning the starter; the first one found the fault in the real case.

Check the tap connection first #

A tap label is not a measurement. Miswired autotransformer leads have put motors on full voltage, or on the boost side of the winding, and the crew in the worked case suspected exactly that until a ratio test settled it. Lock out the starter, verify absence of voltage at its terminals, then measure the ratio between line side and motor side and compare it with the connection diagram — a short commissioning step that the real crew wished it had taken. During the next start, confirm the motor-terminal voltage is the tap fraction of the applied voltage, measured line to line, as set out in. If the motor receives more than the intended fraction, every other number above is invalid; fix the connection before reading another amp.

Read the meter on a single basis #

A locked-rotor table value is a steady-state RMS number. The first cycles of an energized start carry a decaying DC offset that pushes the instantaneous peak well above that RMS figure, and the size of the offset depends on where in the voltage wave the contacts close and on the circuit X/R. A clamp meter or recorder reporting peak current, or a capture window that includes the first asymmetric cycles, reads noticeably higher than the RMS table value — the same RMS-versus-peak distinction that governs how instantaneous trip settings are calibrated, covered in the MCCB RMS versus peak trip calibration guide. Ask for a current time waveform rather than a single number, and compare RMS trend lines once the first few cycles have decayed. The datasheet figure and the field figure must also agree on line versus phase and on which voltage they assume.

Watch the transition to full voltage #

If the starter jumps to across the line while the motor is still well below speed, the current at that instant reaches or briefly exceeds the across-the-line value: the reduced-voltage interval never got to do its work, and the tap, the transformer and the meter are all exonerated. An open-transition changeover adds a brief switching transient on top. Record current, voltage and the speed or time signal that commands the transition on one time base, and check where in the acceleration the changeover actually fires. If the excess appears only in the final second of the start, adjust the transition threshold, not the starter.

Weigh the feeder, the sag and the capacitor bank #

The datasheet DOL figure assumes an infinite bus, and the worked case sits at the far end of a long overhead feeder. Starting load drags the terminal voltage down; a sagged voltage lowers both current and torque, which stretches acceleration and shifts when the changeover fires. Sag by itself is not evidence that the autotransformer is boosting or has failed — the arithmetic works the other way, as the sag estimation in shows, and a sag that follows the motor into running points at the feeder or the upstream source, the pattern described in. Measure voltage at the source and at the motor terminals simultaneously, with the start bank in and out. The bank in this case is a circuit element, not a trim: it lifts the feeder by about 1000 V during the start and switches out at speed, and a bank that switches late or stays closed can push terminal voltage above the motor's rating, which raises current. If terminal voltage ends up above nameplate, stop and sort the tap and bank switching before another attempt.

The checks to run, in order #

  • Ratio-test the autotransformer with the starter locked out and verified dead; compare against the connection diagram, never the tap label.
  • Pull the manufacturer's test sheet for the motor, especially any reduced-voltage locked-rotor measurement, and note for every figure whether it is RMS or peak, line or phase.
  • Record synchronized current and voltage waveforms at the starter input and the motor terminals, with the same instruments and ranges on every start.
  • Log the capacitor-bank state and the changeover instant on the same time base as the current trace.
  • Compare nameplate voltage with the actual system voltage; a nominal system above the nameplate pushes locked-rotor current above the datasheet value.
  • Move to a lower tap only after confirming its reduced torque still breaks the load away and accelerates it inside the motor's and starter's thermal limits.

The decision, reading by reading #

  • Supply-side reading near the idealized squared figure: the starter is correct; close the ticket.
  • Motor-side reading near the linear figure: also correct; you were comparing at the wrong point in the circuit.
  • Reading modestly above both, still below the across-the-line value: the position the worked case landed in; work the tap ratio, the meter basis and the changeover in that order.
  • Reading at or above the across-the-line value during the reduced-voltage interval: suspect a full-voltage or boosted tap connection; stop starting until the ratio test passes.
  • Excess only at changeover: the transition fires too early; move the speed or time threshold.

Questions asked

Where do we get a locked-rotor figure we can actually trust?

Ask the motor manufacturer for the type test or performance test sheet. For a machine this size the sheet usually includes locked-rotor current measured at reduced voltage, which lets you verify the tap proportionality with one real measurement instead of trusting a datasheet headline value or a calculated estimate. Request it before the purchase order on a future machine, since the factory test exposes any unacceptable inrush for your system.

How long does the DC offset last in a motor start?

Only the first few cycles. It decays with the circuit's time constant, set by the ratio of reactance to resistance, and it is largest when the contacts close near the point that produces maximum asymmetry. Compare RMS trend lines after those cycles have passed, and let the waveform capture show the offset rather than letting a peak reading decide the case.

Should we drop to a lower tap to cut the current?

A lower tap cuts supply current and torque as the square of the fraction, and torque is the binding constraint, not current. Before changing taps, confirm the reduced torque still breaks the load away and accelerates it to speed inside the motor's and the starter's thermal limits, and expect a longer start to consume more of that thermal capacity.

Keep reading

  • How-to

    Estimating voltage sag from motor inrush current

    Do not divide the motor's asymmetrical first-cycle peak by √2; screen the dip with RMS locked-rotor current as dip % = transformer Z% × I_start ÷ I_rated. On a 750 kVA, 480 V, 6% transformer, a 50 HP motor at 395 A locked-rotor dips the bus about 2.6%, to roughly 467 V — start it across the line.

    Motors and motor starters

  • Explainer

    What IEC 60034-12 actually limits on motor starting current

    IEC 60034-12 sets a maximum locked-rotor apparent power, not a starting-current ratio. A motor declaring a starting-to-rated current ratio of 7.3 can comply while failing a purchase requirement of less than 6.5. Run both acceptance checks: the table limit qualifies the design, the customer's ceiling decides the order.

    Motors and motor starters

  • Troubleshooting

    Why a single-phase motor growls and pulls 5-6x FLA but won't start

    A growl with slight shaft movement at roughly 5-6 times FLA means the motor is energized but has no starting torque, so the start circuit is not in circuit or the stator is damaged. The decisive test is a lead-to-lead resistance matrix on the isolated motor, because external capacitors and relay wiring create continuity paths that mislead.

    Motors and motor starters