Autotransformer starter starting kVA at 80 percent tap

Motors and motor starters Published 8 min read

Short answer

At an 80% tap, an autotransformer starter draws about 64% of the motor's full-voltage locked-rotor kVA from the supply. With locked-rotor current between 5.5 and 9 times full-load current, that is roughly 3.5 to 5.8 times running kVA, so a flat 4× multiplier is plausible but not a safe upper bound. Electrical frequency stays at the supply frequency for the whole start.

On this page
  1. Why the kW rating alone cannot give starting kVA
  2. What the tap does to current, kVA and torque
  3. Example: supply starting kVA for a 110 kW pump on an 80% tap
  4. Where the 4× multiplier lands, and the losses on top
  5. Frequency during the start, and starts per hour
  6. Autotransformer starter versus soft starter
  7. The decision, case by case
  8. Questions asked

A flat multiplier of 4 × running kVA is in the right neighborhood for an 80% autotransformer tap, but it is not a safe upper bound. The rule that holds is this: the supply starting kVA of an autotransformer start equals the tap squared times the motor's full-voltage locked-rotor kVA, so an 80% tap draws 64% of the locked-rotor kVA from the supply. Locked-rotor current on general-purpose induction motors spans 5.5 to 9 times full-load current, which puts the supply starting kVA between roughly 3.5 and 5.8 times running kVA before starter losses. Electrical frequency never ramps: an autotransformer and an electronic soft starter both change voltage magnitude only, so the motor sees the supply frequency from the first instant to full speed. Below are the tap arithmetic, a worked example for the 110 kW pump, the losses to add, and where the two starter types differ.

Why the kW rating alone cannot give starting kVA #

Shaft power fixes running current only through the motor's efficiency and power factor, and it says nothing about the two numbers a start actually depends on: locked-rotor current and locked-rotor torque. On general-purpose induction motors those span roughly 5.5 to 9.0 times rated current and 60% to 300% of rated full-load torque. The spread exists because at zero speed the rotor sees the full supply frequency — reactance is at maximum and current is limited only by the motor's impedance, as why an induction motor draws heavy current at starting explains — so each design lands somewhere different in the range.

NEMA MG 1 defines the locked-rotor code letters, A through V, printed on the nameplate; the letter fixes the full-voltage locked-rotor kVA per horsepower, so a nameplate with a code letter hands you the starting kVA directly and the tap factor scales it down. Where the nameplate lists locked-rotor current instead, that number serves the same purpose. And a start that never accelerates leaves the motor sitting at locked-rotor current — troubleshooting a locked-rotor motor that stays energized walks through that failure case.

What the tap does to current, kVA and torque #

Let r be the tap written as a decimal, 0.80 for the case at hand. During reduced-voltage running the autotransformer holds four relationships, all measured against a full-voltage start:

  • motor terminal voltage: r × supply voltage
  • motor current: r × full-voltage locked-rotor current
  • supply line current: r² × full-voltage locked-rotor line current
  • starting torque: r² × full-voltage locked-rotor torque

The line current is the lower of the two currents because the autotransformer transforms: the motor pulls its reduced current from the tap winding while the supply furnishes only r² of it. Torque scales with the square of applied voltage too, so the tap that relieves the supply also cuts starting torque by the same factor — the current relief cannot be had for free. That coupling is why the tap must keep accelerating torque positive across the whole speed curve, not just at zero speed. Tap links live inside the starter: NFPA 70E, 2024 edition, requires an electrically safe work condition — de-energize, lock out and verify absence of voltage — before opening it to check the links, and you confirm the specifics with your authority having jurisdiction and the starter documentation.

Tap Motor voltage Motor current Supply line current Starting torque Supply kVA ÷ running kVA, at 5.5–9.0× locked-rotor current
50% 50% 50% 25% 25% 1.38–2.25×
65% 65% 65% 42% 42% 2.32–3.80×
80% 80% 80% 64% 64% 3.52–5.76×

The last column is the multiplier the question asks for: read the installed tap's row and multiply running kVA by it. That kVA is the number a motor starting voltage dip calculation on an 11 kV bus consumes, and it sets the transformer margin when the start shares a bus — the same arithmetic as sizing a transformer for a 200 HP across-the-line motor start, minus the tap factor.

Example: supply starting kVA for a 110 kW pump on an 80% tap #

Inputs, each with its source:

  • Pump motor: 110 kW shaft output — the case as asked.
  • Supply: 400 V, three-phase, 50 Hz — assumed, because the case gave no voltage; this is the standard industrial level for a kW-rated pump of this size.
  • Full-load current: 195 A — assumed nameplate value, typical for the rating.
  • Locked-rotor current: 6.5 × full-load current = 6.5 × 195 A = 1268 A (rounded) — assumed, mid-range of the 5.5–9.0 spread above.
  • Tap: 80%, so r = 0.80 — the case's assumption.

The rule in words: the supply furnishes tap-squared times the full-voltage locked-rotor kVA, and kVA from voltage and current is √3 (taken as 1.732) × line voltage × line current ÷ 1000.

  1. Running kVA: 1.732 × 400 V × 195 A ÷ 1000 = 135 kVA.
  2. Full-voltage locked-rotor kVA: 1.732 × 400 V × 1268 A ÷ 1000 = 878 kVA.
  3. Supply line current at the 80% tap: 0.64 × 1268 A = 811 A.
  4. Supply starting kVA: 1.732 × 400 V × 811 A ÷ 1000 = 562 kVA.
  5. Cross-check: 0.64 × 878 kVA = 562 kVA, and the multiplier against running kVA is 562 ÷ 135 = 4.16×, which is simply 0.64 × 6.5.

The supply sees about 562 kVA, 4.16 times running kVA, and the motor's own leads carry the higher motor current, 0.80 × 1268 A = 1014 A. The flat 4× guess would have said 4 × 135 kVA = 540 kVA, about 4% low for this motor — and at the top of the locked-rotor spread the same pump would pull 5.76 × 135 kVA = 778 kVA, so 4× is demonstrably not the worst case. These are budgeting estimates; final feeder, breaker and transformer choices get checked against the governing code and the starter's documentation.

Where the 4× multiplier lands, and the losses on top #

Back-solve the rule of thumb and you find its assumption: 4 ÷ 0.64 = 6.25, so 4× running kVA describes a motor that would draw 6.25 times full-load current at full voltage — mid-range in the spread, which is why the figure keeps circulating for pumps. As a mid-range sanity check it earns its keep; as an upper bound it fails, because a 9.0× locked-rotor motor on the same tap demands 5.76× before losses. To budget the supply side when only the rating is known, take 5.76× and add the autotransformer's own losses, typically quoted at 5% to 20% of line current, for a worst case near 6.9× running kVA at an 80% tap. The starter manufacturer's input-current or loss data replaces that allowance once you have the documentation, and the installed tap, read off the links rather than assumed, replaces the 0.80.

Frequency during the start, and starts per hour #

Neither machine in this case synthesizes a frequency. The autotransformer changes voltage magnitude only, so the motor's electrical frequency equals the supply frequency — 50 Hz in the example — from standstill through full speed. A soft starter's back-to-back SCRs phase-cut the sine wave to limit RMS voltage and current; the current waveform is chopped during the ramp, but the fundamental stays at the supply frequency. Only a variable frequency drive varies frequency and voltage together, which is how it produces usable torque at low speed. What ramps is rotor speed, from 0 rpm to rated speed over the acceleration time.

If starting frequency means how often the starter may start, that is a thermal duty rating set by motor heating, autotransformer heating and contactor duty. The installed starter's duty table governs, the allowances are short, and they shrink as the horsepower rises.

Autotransformer starter versus soft starter #

Characteristic Autotransformer starter Electronic soft starter
How it cuts voltage Fixed taps, commonly 50%, 65% and 80% Back-to-back SCRs phase-cut the voltage; ramp and current limit are programmable
Supply current vs motor current Line current is r² of the full-voltage value and lower than the motor current Straight-through power path: line current equals motor current
Torque per supply amp Best of the reduced-voltage methods, since torque and line current both scale with r² Less torque per line amp at a given motor current
Electrical frequency Supply frequency throughout Supply frequency throughout
Extras None beyond the three torque points Soft stop and pump ramp profiles that ease water hammer

For the pump in question: the autotransformer buys the lowest supply current for a given starting torque, which matters when the transformer or generator feeding the start is the constraint. The soft starter buys an adjustable current limit and a soft stop for the pipeline. One reported benchmark puts a typical centrifugal pump start near 3.5 × full-load current for about 15 seconds, roughly a 65% tap; treat that as a reported starting point and check it against the tap math above with the motor's actual locked-rotor data before adopting it.

The decision, case by case #

  • Nameplate shows a code letter: locked-rotor kVA = the letter's kVA-per-hp × horsepower at full voltage; supply starting kVA = tap² × that, so 0.64 of the figure at an 80% tap.
  • Nameplate shows locked-rotor current: supply starting kVA = tap² × multiple × running kVA — 4.16× running kVA for a 6.5× motor at 80%, 5.76× for a 9.0× motor.
  • Only the rating is known: budget 5.76× running kVA, allow up to 6.9× with autotransformer losses, and treat 4× as a mid-range sanity check, never the upper bound.
  • Frequency: state the supply frequency; neither starter type changes it.
  • Before any of it: read the actual tap off the starter, dead and verified, and let the starter's duty table cap the starts per hour.

Questions asked

How many starts in a row can an autotransformer starter make?

Repeat starting is a duty rating, not a judgment call. One starter manufacturer's published 65% tap duty allows 15 seconds on, 3 minutes off, repeated 14 times for 15 starts total, then 2 hours of rest; above 200 hp it drops to 3 starts total before a 1 hour rest. A 110 kW pump is about 147.5 hp, so the lighter row would apply — but the duty table for the installed starter governs, and motor thermal protection counts every start.

How do I get starting kVA from the nameplate code letter?

The code letter gives locked-rotor kVA per horsepower at full voltage. Code H, for instance, covers 6.30 to 7.09 kVA/hp: multiply the high end by the motor's horsepower for the full-voltage locked-rotor kVA — about 1046 kVA on a 147.5 hp machine — then multiply by the tap squared for the supply kVA. Use the low end of the letter's range when you want the smallest demand that motor could present.

The pump will not break away on the 80% tap. What now?

Lowering the tap moves the wrong way: torque falls with the square of the tap, so 65% gives less torque than 80%, not more. Start against a closed or throttled discharge valve to cut the pump's breakaway and acceleration demand, confirm the reduced-voltage torque still exceeds the load, and check the acceleration timer against the tap's permitted on-time. If the motor still stalls, a soft starter with a current-limit ramp or a VFD is the fix, not a different tap.

Which current should size the supply: the line current or the motor current?

During reduced-voltage running, the supply sees the line current and the conductors between the autotransformer and the motor see the higher motor current — in the worked case, 811 A on the line side against 1014 A at the motor. Size the feeder, the source transformer and the line-side protection from the line current, and size the motor-side conductors and overload from the motor current. After the transition to full voltage the two currents are the same.

Keep reading

  • Troubleshooting

    Fixing AC contactor chatter on a loaded 80 HP motor start

    Chatter with the motor connected but a clean pull-in with the motor disconnected is the supply sagging under locked-rotor current; the 750 VA and external-outlet tests already cleared the control transformer. At 6x the 81 A label the start draws about 486 A on a 271 A transformer, so limit the start to roughly 270 A with a soft starter and verify the coil holds above 102 V.

    Motors and motor starters

  • Selection guide

    Matching a soft starter current range to its power structure

    Match the power structure before anything else: a solid-state soft starter covers 90–520 A and an internal-bypass unit covers 108–480 A, both rated 200–690 V AC at 50/60 Hz. Size the starter so the motor's full-load current sits inside the span for the structure you actually have, then set the start modes.

    Motors and motor starters

  • Selection guide

    Selecting a modern IEC contactor for a burned lathe starter

    Size the replacement from the motor nameplate, not the old catalog number: a 5 HP, 230 V three-phase lathe motor at 15.2 A FLA takes a 25 A AC-3 frame — ordered as 3RT1025-1AC20 for a 24 VAC coil or 3RT1025-1AP20 for 24 VDC — plus a snap-on NC auxiliary block to rebuild the original 1 NO + 1 NC set, and a new 14–20 A overload relay set to FLA because the old one will not mount.

    Motors and motor starters