Troubleshooting
Why F013 ground fault trips in auto but not on jog
Short answer
F013 in auto but not on a slow jog is the start transient crossing the ground-fault threshold, not an earth fault. On the documented mill, accel time parameter 41 was set to 0 s; entering 10 ms cleared the trip. A second documented case ties F013 to enabling A557 (Output phase loss En) on firmware 7.001, where only disabling A557 helped.

On this page
- What the F013 code actually reports
- Why the jog passes and the auto start trips
- Trip patterns and what each one means
- Isolate the power circuit first
- The zero ramp is the primary suspect
- Worked example: giving the mill's auto start a real ramp
- The second documented cause: A557 on firmware 7.001
- Restore and verify
- Questions asked
F013 on the automatic start while a slow jog runs clean is almost never an earth fault. The drive reports a ground fault when the sum of its three output currents stops balancing, and a hard start transient can cross that detection before the motor has moved. Two documented causes produce this exact pattern on the PowerFlex 525: accel time parameter 41 [Accel Time 1] left at 0 s, which turns the run command into a full-speed step, and the output phase-loss monitor A557 (Output phase loss En) enabled on firmware 7.001. On the rolling mill that showed this pattern, the jog ran at 15% of maximum line speed, the automatic start tripped 9 times out of 10, and entering 10 ms in parameter 41 cleared the trip. Work the power circuit first, then the settings, in the order below.
What the F013 code actually reports #
The manufacturer's fault table for the PowerFlex 525 defines F013 as a ground fault: a current path to earth detected at one or more of the drive output terminals. Read what that definition rests on. The drive infers an earth path from its own output-current measurement, so it cannot separate current genuinely leaving to earth from a transient that unbalances the measurement for a few milliseconds at the start of a run. Treat the displayed code as a symptom: pull the drive's fault history and check the fault table for your model and firmware before you assign a cause. Both documented cases behind this pattern passed that test as configuration problems, not insulation failures.
Why the jog passes and the auto start trips #
A jog is not a smaller automatic start; it is a different demand. On this mill the two commands differed in three ways:
- Speed reference. The jog ran at about 15% of maximum line speed; the automatic command asked for full line speed.
- Ramp. With the acceleration time at zero, the automatic command is a step to the full reference, while the jog's smaller step needs a fraction of the current.
- Control path. Both commands ran in vector mode here, so mode alone did not separate them, but one comparison run in V/Hz mode still tells you whether the trip depends on the motor model and its encoder feedback.
A jog that completes proves the power circuit can carry a small demand. It proves nothing about the full-speed step, and the full-speed step is the condition that trips.
Trip patterns and what each one means #
Where the fault lands in time tells you where to look:
- F013 on receipt of the run command: the launch transient or the monitoring configuration, not the driven load.
- F013 during acceleration, automatic command only: the ramp and the reference step, not the motor.
- F013 at steady speed under load: a real current problem; go back to insulation and terminal checks.
- The same F013 on a spare drive of the same type: a shared parameter set or command condition, not two failed drives.
- F013 appears when A557 is enabled and leaves when it is disabled: the phase-loss monitoring configuration.
- F013 with the motor leads removed at the drive output terminals: drive settings, current sensing or output hardware.
Isolate the power circuit first #
De-energize the drive, lock out the feeder and test for absence of voltage before you open the drive or a terminal box; the DC bus holds its charge, so follow the drive's discharge indication and your site's procedure. NFPA 70E, 2024 edition, covers the electrical safe-work-practice requirements behind that step, including verification of an electrically safe work condition; confirm the requirement with the authority having jurisdiction at your site and the drive's documentation.
Then change one condition at a time and log each result:
- Insulation test. The motor on this installation passed at 1000 V. A pass keeps the motor in the circuit but does not reproduce the PWM wavefronts the cable actually sees; if the megger passes and the trip still lands at start, the pattern is covered in a VFD ground fault at start with good megger readings.
- Substitution. Another motor with another cable produced the same F013 here, which demotes the original motor and cable together.
- Disconnect test. Remove the motor leads at the drive output terminals and issue a run in V/Hz mode with instruments suitable for PWM outputs. A trip with nothing connected points inside the drive; when a VFD trips ground fault with the motor disconnected works that branch.
- Shield states. Cable earth connected at both ends, at the motor end only, and fully disconnected all gave the same fault here. That was fault tracing only; restore the documented bonding before the machine returns to service.
The zero ramp is the primary suspect #
An acceleration time of 0 s tells the drive to move its reference with no defined rate: the speed regulator sees the whole step error at once and calls for maximum current in the first control cycles, and that spike is what the ground-fault detector measures. On drives that report the same transient as overcurrent, it shows up as an OC1 overcurrent fault during acceleration.
One detail from the mill matters for the decision. Its twin machine, set up with the same zero acceleration time, ran without trips. A zero ramp is a latent defect rather than a guaranteed trip: whether it trips depends on the motor's flux establishment and magnetizing current, so two motors of the same frame rating can behave differently on identical parameter sets. The setting belongs on every drive in the line-up, whether or not the sister machine happens to run.
Worked example: giving the mill's auto start a real ramp #
Inputs, all taken from the affected installation:
- Parameter 41 [Accel Time 1] read 0 s on the drive, confirmed in its parameter set.
- Jog reference: 15% of maximum line speed, as set for manual operation.
- Automatic reference: full line speed, the production command.
- Trip record: 9 automatic starts in 10 ended in F013.
- Motor insulation: passed at 1000 V.
- The change entered: parameter 41 set to 10 ms, in the unit the keypad displays for that parameter.
The rule, in words: the current a drive must deliver on a start scales with the size of the speed step divided by the time allowed for it, and the ground-fault detection trips on the transient that reaches the output terminals. A ramp of zero leaves the step size alone to set that current.
The arithmetic:
- Jog step = 15% of reference; automatic step = 100% of reference; the automatic step is 100 ÷ 15 ≈ 6.7 times the jog step.
- With the ramp entered, the full reference change spreads over 0.010 s, an average rate of 100% ÷ 0.010 s = 10,000% of reference per second: still fast, but finite and shaped by the current regulator.
- Trip rate before the change: 9 ÷ 10 = 90% of automatic starts.
The result: with the ramp in place, the initial current spike stayed below the detection threshold, the trip left the run transition, and the mill completed a short production run in a stable condition.
The decision: if the jog runs, the automatic start trips F013 at the run transition, and parameter 41 reads 0 s, fix the ramp before you replace hardware. Ten milliseconds is the value proven on this mill; enter the shortest ramp your process tolerates and prove the fix with repeated automatic starts under the production command.
The second documented cause: A557 on firmware 7.001 #
On drives running firmware 7.001, a second installation documented the other path to this symptom. Those drives ran normally until output phase-loss monitoring, A557 (Output phase loss En), was enabled; from then on F013 appeared on every run attempt. Adjusting A576 (Phase Loss Level) changed nothing, and disabling A557 restored normal running.
If A557 is enabled on a drive that trips F013 at the run transition, disable it for one comparison run. When the fault leaves, the monitoring configuration is the cause, and the decision becomes whether that protection is worth the trip: output phase-loss detection exists to catch an open output phase, a fault with its own signature, covered in tracing the broken phase in an output phase-loss fault. Where the protection is required, raise the interaction with the drive manufacturer's support for that firmware instead of living with the nuisance trip.
Firmware is not the first move on the primary case: the mill went from firmware 5.001 to 7.001 with no change in the trip. An update earns its place only after the ramp and the monitoring settings are right.
Restore and verify #
- Restore vector mode if the V/Hz comparison was run, and load back the parameter set you saved before testing.
- Restore the cable-shield and protective-earth bonding to the arrangement the drive documentation specifies; none of the three test states is a permanent condition.
- Verify with the command that failed: repeated automatic starts at production speed, then with material load. Watch where any returning fault lands: at the run transition it points back to the ramp and A557, at steady speed under load it points back to the motor circuit.
- Record the final value of parameter 41 and the firmware version on the machine's commissioning sheet, so the next start-up does not begin from zero.
Questions asked
Why can F013 trip with the motor completely disconnected?
With the output terminals open, the only paths left for current are inside the drive: the output transistors, the internal current sensing that feeds the ground-fault detection, and the monitoring configuration. A trip in that state is strong evidence for drive settings or drive hardware, which is why the motor and cable move down the suspect list and a spare-drive substitution becomes the informative test.
What does A576 do, and why did changing it not help?
A576 (Phase Loss Level) sets the detection level for the output phase-loss function that A557 enables. In the documented firmware 7.001 case the fault appeared whenever A557 was on, whatever value A576 carried, so the enable, not the level, gated the fault. Cycling the level burns test runs; toggle the enable for the comparison run instead.
Is a firmware update the fix for this F013 pattern?
Not as a first action. The documented mill went from firmware 5.001 to 7.001 with no change in the trip, and the fault cleared only when the acceleration time became nonzero. Remember that 7.001 is also the version in the A557 case: an update can introduce the second failure mode if output phase-loss monitoring is enabled afterwards.
Could the motor's encoder or case fan be causing the trip?
Neither is a likely source. The encoder feeds the speed feedback, not the output current path, so it cannot produce a ground-fault current by itself, and the 24 V case fan runs from its own supply. In the documented tests the fault stayed with the drive and its settings through a motor and cable substitution, which argues against the motor accessories.
Can the cable shield stay unearthed if the drive runs that way?
No. In the documented tests the earth state made no difference to the fault, so the unearthed condition bought nothing. Permanent installations keep the cable shield and protective earth bonded as the drive's installation manual specifies; an unbonded shield raises common-mode voltage stress on the motor winding and its bearings.