Troubleshooting
Why F07900 motor blocked torque plateaus at the current limit
Short answer
A torque plateau that matches the configured current limit times the motor's torque constant is proof of current saturation. F07900 reports a motor held at the torque limit below the blocked-speed threshold for more than 0.2 s; in the worked case the computed ceiling lands within two percent of the traced plateau. No parameter raises what the hardware cannot deliver, so the fix is a larger Motor Module selected from the motor's torque-current curves.

On this page
The trace settles it: when actual torque climbs to a flat plateau and the drive signals F07900, compare that plateau with the torque your configured current limit can produce. If the two match, the Motor Module is the ceiling and no parameter will move it. The calculation below uses the nameplate data from a real commissioning case: an 18 A module on a torque motor whose standstill point demands roughly three times that current. The decision follows directly — resize the hardware from the motor's torque-current curves, and use the parameters only to verify.
What F07900 tells you before anything else #
The fault text is "Motor blocked/speed controller at its limit." The drive's fault table defines it precisely: the motor has held the torque limit for longer than 0.2 s while actual speed stays below the blocked-speed threshold set in p2175. That makes F07900 a symptom, not a cause. Something is holding torque at the limit, and the fault simply reports it. Your task is to identify what set that ceiling — a mechanical load above the torque available, or a current limit the power unit cannot pass. The trace distinguishes the two in one capture.
Worked example: compute the torque the current limit can deliver #
Nameplate data for the motor in question, a 1FW6230-xxB10-5Gxx (the x positions carry factory option codes):
- Standstill torque M0 of 1680 Nm at a no-load current I0 of 54 A
- Rated current I-N of 48 A, maximum current I-MAX of 100 A
- Rated speed 120 rpm, maximum 250 rpm, 49 pole pairs
Drive side: a Motor Module rated 18 A, with the motor current limit p0640 set to 36 A — twice the module's rating, a setting that presumes an overload duty the hardware can sustain only briefly.
Torque constant from the nameplate ratio:
Kt = M0 / I0 = 1680 Nm / 54 A ≈ 31 Nm/A
Torque available at the configured limit:
T_limit = 31 Nm/A × 36 A ≈ 1120 Nm
The Device Trace showed the plateau at about 1100 Nm, within roughly two percent of the estimate. That agreement is the confirmation: the drive reached its configured current ceiling, and the connected load needs more torque than that to break away. Treat the estimate as a check, not a replacement for the manufacturer's torque-speed diagram for the exact variant, where the continuous, overload and speed boundaries are actually drawn.
Why no parameter can lift the ceiling #
- Torque limits (p1520/p1521). Raising them authorizes a larger torque command, but the speed controller still cannot request more current than the motor current limit permits. The command rises; the delivered torque does not.
- Motor current limit (p0640). The parameter is itself clamped. The drive documentation states that the resulting motor current limit cannot exceed the power unit's current limit, held in r0209, and the effective value after all clamps reads out in r0067. Asking p0640 for more than the hardware permits simply saturates at the hardware value. For contrast, the way a different product family caps the same kind of setting is covered in why the V20 motor overload factor stops at 100 percent.
- Blocked-motor thresholds (p2175/p2177). These shape only the detection: the speed threshold and the timing around it. Changing them alters when the fault appears, not how much torque exists.
- Ramp times. A longer ramp reduces acceleration torque demand, which helps a marginal load. It cannot help when the load's breakaway torque already exceeds the torque available at the current limit — the motor stalls at the same plateau either way.
- Encoder path. Encoderless operation or encoder re-checks address feedback faults, not current limits. In this case the encoder chain was already proven: an earlier F07412 commutation-angle fault had been cleared by correcting the U-V-W phase sequence, and pole position identification through p1982 ran successfully. If you are re-verifying that chain after hardware changes, the procedure in commissioning a replacement servo encoder with its motor ID data applies directly.
The decision for each case #
| What the trace shows | What it means | What to do |
|---|---|---|
| Plateau matches the computed torque within a few percent | Drive is at its current limit; the hardware is the constraint | Select a larger Motor Module from the motor's torque-current curves |
| Plateau sits well below the computed value | Scaling, measurement or configuration issue | Check current scaling, the p0640 setting against r0067, and the trace configuration |
| No plateau; the fault appears immediately | Detection or feedback problem, not saturation | Verify the encoder and the blocked-speed threshold before touching sizing |
For the matching case, the sizing rule is concrete. Read the currents the motor's curves require at breakaway, through acceleration and at continuous duty, then choose a Motor Module whose continuous rating and documented overload duty cover all three for the required durations. In the worked case, the module was already driven to twice its rating and still could not reach the motor's standstill torque; that margin is not recoverable in software, so the module is at least one frame size too small. The same discipline used to size a drive from load data applies here, as laid out in sizing a VFD from load torque and motor current, and the distinction between a drive's rated current and the current a motor needs for breakaway is treated in VFD rated current vs motor full-load starting torque.
Verify the fix #
- Archive the drive project and export the trace capture that shows the plateau; keep both with the commissioning record.
- Before opening the Motor Module, the motor terminal box or encoder cabling, de-energize the cabinet, lock out, verify absence of voltage, and wait the drive's documented DC-bus discharge time.
- Pull the torque-speed diagram for the exact motor variant and mark the current required at breakaway, through acceleration and at continuous duty.
- Select the Motor Module whose continuous rating and documented overload duty cover all three currents for the durations the machine cycle demands.
- Reconnect the verified U-V-W phase sequence and encoder wiring, then re-run pole position identification and confirm the fault history stays clear of commutation faults.
- Set the motor current limit and the torque limits within the new module's documentation, and read back the effective value in r0067 before the first enable.
- Enable and trace again: torque should pass the old plateau, speed should cross the blocked threshold, and F07900 should not return.
If the second trace still plateaus at the same torque, the new module is clamping too — re-read r0067 and the load's true breakaway demand before changing anything else.
Questions asked
Why does the trace plateau so close to the calculated torque?
Because the plateau is the current limit made visible. With the nameplate ratio of 1680 Nm at 54 A, the torque constant is about 31 Nm/A, and a configured limit of 36 A gives roughly 1120 Nm. A measured plateau within a few percent of that value is current saturation, not a mechanical or feedback problem.
Will longer ramp times or different p2175 settings clear F07900?
Not when the load torque exceeds what the current limit can produce. Ramp times change how quickly torque is commanded, and p2175 together with p2177 sets the speed threshold and timing of the blocked-motor detection. None of them raises the current the power unit can deliver; they only change when the fault is declared.
Can an 18 A Motor Module ever run this motor?
Not for this duty. The motor's no-load current alone is three times the module rating, and with the limit pushed to twice the module rating the available torque still sits well below the motor's standstill torque. A module chosen from the motor's torque-current curves must cover breakaway, acceleration and continuous current; this one covers none of them.
Where can I read the current limit the drive is actually using?
In the signal r0067, which shows the resulting motor current limit after every source has had its say: the setting in p0640, the power unit ceiling held in r0209, and any temperature or duty-based reductions. If the displayed value is lower than what you set, the hardware or a protective function, not your parameter, is deciding.