Sizing a VFD from load torque and motor current
Short answer
Size the drive so its continuous output rating covers the motor's sustained load current and its documented overload rating covers the peak torque current for the peak's duration. Nameplate full-load current, not horsepower, is the reference, and a 150% for 60 s class drive covers most pump, fan and conveyor peaks.

On this page
- What current should you size a VFD from, the motor nameplate or horsepower?
- How do you turn load torque into motor current?
- What continuous and overload ratings does the drive documentation need to show?
- What numbers do you collect before choosing a drive?
- How does the worked example go at 460 V?
- How do you verify the choice on the running machine?
- When does the sizing rule change with motor type and duty?
- Questions asked
Size the VFD from current, not horsepower: the drive's continuous output-current rating must equal or exceed the motor's sustained load current, and the drive's documented overload rating must cover the peak torque current for as long as the cycle holds it. For most pump, fan and conveyor duty that means a drive rated at least at the motor nameplate full-load current with 150% overload for 60 s. The method below takes you from load torque to those two numbers, with a worked example at 460 V, and ends with the decision rule for each comparison.
What current should you size a VFD from, the motor nameplate or horsepower? #
Size from motor current: the motor nameplate full-load current is the reference value, and horsepower alone never settles the choice. Two motors with the same horsepower rating can differ in current by 20% or more depending on speed, poles and efficiency, so a horsepower-matched drive can end up one frame small.
The nameplate full-load current is the current the motor may carry continuously at its rated voltage, frequency and service factor. It is a motor limit, not a load description: your driven machine may demand less than that continuously, and it may demand more for short intervals during acceleration or a lump in the material. The drive must cover both demands, which is why the selection compares two numbers against two ratings, not one against one. This is also the principle behind matching a drive frame to motor FLA even when the horsepower looks right, covered in the knowledge-base article on sizing a VFD by motor FLA rather than horsepower.
If the motor is much smaller than the drive's minimum motor size, the drive's own overload model loses resolution and current feedback becomes coarse; that constraint is separate and covered in the article on why a VFD still needs a minimum motor size below its rating.
How do you turn load torque into motor current? #
Above a motor's magnetizing current, shaft torque is approximately proportional to the in-phase component of stator current, so a load torque expressed as a percentage of rated torque translates to roughly the same percentage of full-load current. That approximation is the working tool; refine it with the motor's own data where the margin is tight.
The sequence:
- Define the load torque over the whole speed range, from the machine's process data, the gear ratio and a torque calculation, or from commissioning measurements with a torque transducer.
- Split it into the continuous torque, held for the whole duty period, and each short-term peak torque, with its duration.
- Express each as a percentage of the motor's rated torque, using the motor's rated torque from its power and speed, then read that percentage across to current using full-load current as the 100% reference.
For example, a torque that is 120% of rated for 8 s is treated as roughly 120% of full-load current for 8 s. The approximation is safe-side for induction motors on a drive because the drive's flux regulation holds magnetizing current fairly flat; verify against a measured current trace during commissioning, since the real peak depends on the drive's torque-limit parameter and the acceleration ramp.
What continuous and overload ratings does the drive documentation need to show? #
Two ratings, both printed in the drive's rating tables: the continuous output current, available indefinitely, and a short-time overload, typically stated as a percentage of continuous output for a defined interval, commonly 110% for 60 s on light-duty frames and 150% for 60 s on heavy-duty frames. Match the class of the frame to the machine, then match the numbers to your load.
The light-duty rating is sized for fans, centrifugal pumps and similar loads whose torque rises with speed and never exceeds the continuous rating after the ramp. The heavy-duty rating covers conveyors, mixers, compressors and hoists that hit real torque peaks. A frame sold at the same horsepower in both classes carries different current numbers for the two classes, so read the current column, not the horsepower column. Note that the drive's overload figures are its own documented limits; they are not the same thing as the motor's thermal overload protection setting, which the article on setting overload relays from motor nameplate full-load current covers from the motor side.
For the motor circuit itself, NFPA 70 (the National Electrical Code, 2023 edition) governs conductor sizing and overload protection for motor circuits, and its rules are stated in terms of the motor's full-load current from its tables and the nameplate. Confirm the installation requirements with your local authority having jurisdiction and the equipment documentation, because editions and local amendments differ.
What numbers do you collect before choosing a drive? #
Six values decide the selection, and every one comes from a document or a measurement rather than a rule of thumb.
| Quantity | Where it comes from | What it decides |
|---|---|---|
| Motor nameplate FLA, voltage, frequency | Motor nameplate | The 100% current reference for the torque-to-current conversion |
| Continuous load torque | Process data or load calculation | The sustained drive current the continuous rating must cover |
| Peak load torque and duration | Machine cycle analysis | The short-time current the overload rating must cover |
| Rated motor torque | Motor power and rated speed | The reference that turns torque percentages into current percentages |
| Drive continuous output current | Drive rating table | Must be greater than or equal to the continuous load current |
| Drive overload rating and duration | Drive rating table | Must cover peak current for the peak's measured duration |
Keep the continuous and peak values separate all the way through the comparison. Averaging them hides the sizing failure that actually trips drives in the field.
How does the worked example go at 460 V? #
Take an illustrative case: a 460 V, three-phase, 60 Hz, 10 HP, four-pole induction motor, nameplate full-load current 14.0 A at service factor 1.0, driving a heavily loaded belt conveyor with gear reduction. The motor's rated torque is about 10 HP times 5252 divided by 1800 rpm, roughly 29.2 lb-ft. The load study shows continuous demand of 22 lb-ft, about 75% of rated, and an acceleration and lump peak of 44 lb-ft, about 150% of rated, lasting 10 s each cycle.
The current conversion gives:
- Continuous load current: 0.75 times 14.0 A = 10.5 A, held indefinitely.
- Peak current: 1.50 times 14.0 A = 21.0 A, held for 10 s per cycle.
Now the drive comparison. A heavy-duty frame with a continuous output rating of 16.5 A and an overload rating of 150% of continuous output for 60 s gives a short-time capability of 1.50 times 16.5 A = 24.8 A. Check both: 10.5 A is below the 16.5 A continuous rating, so the sustained duty passes; 21.0 A for 10 s is below the 24.8 A short-time capability and well inside the 60 s window, so the peak passes. The decision: that heavy-duty frame is adequate, while the light-duty sibling of the same horsepower, rated 14.0 A continuous with 110% for 60 s (short-time capability 15.4 A), fails on the peak and is the wrong frame for this conveyor. All figures in this example are illustrative inputs, not a rating you can carry to your machine; rerun the arithmetic with your own nameplate and load data.
One more check at the input side: drive input current can exceed output current because the rectifier draws a pulsed current at a poorer power factor than it delivers, so size the input fuses, breaker and conductors from the drive's documented input current, not from the output numbers. The article on why VFD input current can be higher than output current works through that ratio.
How do you verify the choice on the running machine? #
Run the machine through its full cycle with a clamp meter or the drive's own output-current trace, record the sustained current and the peak current with the peak's duration, and compare each against the drive ratings you used. A successful light-load run proves nothing about the peak.
A true RMS clamp meter on the drive output reads the drive's pulsed output waveform correctly; a meter without true RMS response underreads it. Compare the measured sustained current against the drive's continuous rating and the motor's nameplate full-load current, and compare the measured peak and duration against the overload rating's percentage and window. If the trace shows the peak ending inside the overload window and the sustained current settled below the continuous rating, the selection is verified for that load. Repeat the measurement after any change to the load, the acceleration ramp, the torque-limit setting or the motor.
When does the sizing rule change with motor type and duty? #
The rule holds but the numbers move: motors on reduced-speed duty, high-slip loads and applications that regenerate change one or both comparisons, and each case keeps the same structure of continuous current versus continuous rating and peak versus overload window.
A motor run for long periods at low speed cools less, because its shaft-mounted fan slows with it; the drive's electronic motor overload model accounts for this only if its overload class and duty parameters are set to match the application, so reduce the allowable continuous current for sustained low-speed duty per the drive and motor documentation. A load that overhauls and regenerates, such as a downhill conveyor or a centrifuge, adds braking current the drive must absorb or dissipate, and the article on frequency converter sizing when a single-phase load regenerates extends the method to that case. And if the load current turns out to sit below the drive's minimum motor current, resize before energizing rather than letting the drive nuisance-trip on motor-phase imbalance.
The decision rule, in full: read the nameplate full-load current, convert the continuous and peak load torques to currents, pick a drive whose continuous rating covers the first and whose documented overload rating covers the second for the peak's duration, then verify both on a true RMS trace of the running cycle. When any input is missing or a comparison fails by a small margin, move up a frame size or get the missing load data before energizing.
Questions asked
What overload rating should the drive have for a conveyor or mixer with short torque peaks?
For most general-purpose machines, a drive rated 150% of its continuous output for 60 s covers the acceleration and lump-load peaks, provided the peak current you calculated stays inside that limit for the measured duration. Heavy-duty applications such as crushers or positive-displacement pumps may need 160% to 200% for shorter intervals, so read the exact duty figures in the drive's own documentation and match them to your cycle.
Can I use the same VFD on a motor rated 50 Hz if the nameplate shows 460 V 50 Hz data?
Use the nameplate full-load current for the voltage and frequency you will actually run. A 460 V 50 Hz motor carries different full-load current than the same frame at 60 Hz, and running below rated frequency reduces the motor's self-cooling, so the overload settings in both the drive and any separate overload relay must be revisited for the reduced-speed duty.
Does the drive's motor overload protection replace a separate overload relay?
The drive's electronic motor overload function protects the motor while the drive is the only supply path, and it is set from the same nameplate full-load current. Where the machine standard or the local installation rules require a disconnecting means or backup short-circuit protection, the drive still needs correctly rated fuses or a breaker upstream. Confirm the protection scheme for your installation with NFPA 70 and the authority having jurisdiction.
Why do some sizing guides say to use twice the motor full-load current?
A fixed multiplier such as two times full-load current is a crude stand-in for an actual load study. Some fans and centrifugal pumps run near nameplate current continuously, so doubling wastes money on an oversized frame; some crushers and presses need genuine peaks well above nameplate for several seconds, where doubling still may not be enough. Calculate the continuous and peak currents for your cycle instead of applying a universal ratio.
How much margin should I leave between the load current and the drive rating?
Once the continuous load current fits inside the drive's continuous rating and the peak fits inside the overload rating for its duration, no extra margin is required by the sizing method itself. Adding a frame size costs little and helps with future load growth or hotter ambients, but the drive's own derating table for elevated ambient temperature is the check that matters, not an arbitrary percentage.