Why feeder 51N protection misses an open phase to motors

Protection: breakers, fuses and SCCR Published 8 min read By Current Intel engineering team

Short answer

The feeder protection did not fail: an open 15-25 A branch on a 300 A feeder lowers current and produces near-zero residual behind a delta primary, so it sits below every pickup. Fit negative-sequence (46) or phase-loss detection at each motor with the delay below the motor's thermal limit, and repair the branch joint.

On this page
  1. Why doesn't the feeder's ground or phase overcurrent trip when a branch phase opens?
  2. How much residual current does an open phase put into the feeder ground element?
  3. What does the open phase do to a running motor?
  4. Which protection functions detect single-phasing and which miss it?
  5. How do you confirm single-phasing at the motor terminals?
  6. How do you set and prove the 46 protection at each motor?
  7. What do you repair on the branch, and can feeder-level detection ever work?
  8. Questions asked

A loose connection that opens one phase on a small branch of a 13.8 kV feeder damages motors while the feeder's own protection records nothing, because nothing it measures moved far enough to trip. The branch carried only 5% to 8.3% of the feeder load, opening it lowers current instead of raising it, and behind a delta-primary branch transformer the residual current is approximately zero. The protection that should have operated belongs at the motor: negative-sequence (46) or phase-loss detection. Here is the analysis, the checks and the decision.

Why doesn't the feeder's ground or phase overcurrent trip when a branch phase opens? #

Because the branch carried only 5% to 8.3% of the feeder load before it opened, and opening it lowers current rather than raising it: an open conductor is a series interruption, not a fault, so it produces no fault current at all. A phase overcurrent element (50/51) is set to carry the whole feeder, so its pickup sits several times the largest branch, and an open branch moves current downward, away from every pickup. A recloser's phase and ground minimum-trip settings behave the same way. The feeder protection behaved exactly as designed: the protection gap is real, but no change to those settings closes it.

How much residual current does an open phase put into the feeder ground element? #

With a delta or ungrounded-wye primary on the branch transformer the residual current is approximately zero, because the two remaining line currents sum to zero; with a grounded-wye primary it is at most the current the lost phase was carrying.

Branch transformer primary Residual current (3I0) after the phase opens Ground element outcome
Delta or ungrounded wye Approximately zero: the two remaining line currents sum to zero No pickup at any setting
Grounded wye Up to the lost phase's load current, at most the branch current No pickup if the 51N sits above normal feeder unbalance

Worked example with illustrative settings: the feeder 51N pickup is 60 A primary after the CT ratio, and the branch is 20 A. The residual reaches at most 20 A, one third of the pickup, so the element never moves, even in the grounded-wye case that produces the most residual. Lowering the pickup below that level on a feeder this size invites nuisance operations from normal load unbalance; the mechanism is the one behind why an earth fault setting trips without a fault. Decision: leave the pickup where it is. On a delta primary no setting at any level sees the event, so the remedy lies downstream.

What does the open phase do to a running motor? #

A fully loaded motor keeps delivering its power through two lines, so each remaining line current rises to about 1.73 times the three-phase value, and the negative-sequence current settles near the running current the motor carried before the phase opened. That ratio assumes equal voltage, power factor and efficiency before and after; real slip and power factor shift, so measure rather than assume. The relation that the negative-sequence component equals the running current before the open is documented in the descriptive bulletin for a negative-sequence overcurrent relay. The induction motor's negative-sequence impedance is close to its locked-rotor impedance, which is why current unbalance is severe while the terminal voltages can look mild. The negative-sequence field rotates against the rotor and induces rotor currents at twice line frequency, so heating runs well ahead of what the average stator current suggests. NEMA MG-1 Part 30 (Application Considerations for Constant Speed Motors, current edition) derives its derating on the assumption that voltage unbalance is negligible, and the US Department of Energy recommends keeping voltage unbalance at motor terminals at or below 1% and derating the motor above that.

Worked example: a motor with a 100 A full-load current runs fully loaded when a phase opens. The two live lines carry 100 A × 1.732 ≈ 173 A, above any overload pickup set near the nameplate current, so a healthy overload relay trips on its curve. At 40 A of load the same motor draws 40 A × 1.732 ≈ 69 A on the two lines, below the overload pickup, yet the negative-sequence current sits near 40 A and the rotor heats the whole time. Decision: overload-only protection misses light-load single-phasing. A motor already at rest is covered in why a single-phased three-phase motor cannot start from rest.

Which protection functions detect single-phasing and which miss it? #

Negative-sequence or current-unbalance protection (ANSI 46) detects an open phase at any load level; thermal overload (49) detects it only when the two-line current crosses its pickup, and fuses never do.

Function Detects the open phase? Limitation
Thermal overload (49), bimetal or electronic Only after the two remaining line currents exceed the pickup for the curve time Misses light-load single-phasing; slow on a heating curve
Negative sequence or current unbalance (46) Yes, at any load, because the negative-sequence current tracks the pre-event running current Needs the relay and its CT inputs on each motor
Voltage unbalance or phase loss (47) Yes, where it senses the bus or the branch ahead of regeneration A running motor back-feeds the open phase and can mask the loss at its own terminals
Fuses only No A fuse clears overcurrent; an open phase is an open, not a fault

Overload relays set correctly from the nameplate, as in setting overload relays from motor nameplate full-load current, still miss the light-load case by design.

How do you confirm single-phasing at the motor terminals? #

Measure all three line currents and all three phase-to-phase voltages on the running motor: one line near zero with the other two high and roughly equal is the signature, even when the voltages look close to normal. A running motor regenerates voltage on the open phase, so the terminal voltage alone proves nothing. Calculate current unbalance as the maximum deviation from the average divided by the average. Example readings of 0 A, 120 A and 120 A give an average of 80 A and a maximum deviation of 80 A, a 100% current unbalance; phase-to-phase voltages of 460 V, 470 V and 478 V give an average of 469.3 V and a maximum deviation of 9.3 V, a 2.0% voltage unbalance. Large current unbalance against small voltage unbalance points to a primary-side open phase; balanced currents point to a different damage mechanism such as overload or insulation failure.

One safety point where it belongs: open no terminal box or MCC compartment on the strength of this article. De-energize, lock out and test for absence of voltage first; any live measurement is made only under the site's electrical safety program with the rated meter, leads and arc-rated PPE. NFPA 70E, 2024 edition, sets the work-practice requirements in the United States; confirm with the local authority having jurisdiction and the site procedure.

How do you set and prove the 46 protection at each motor? #

Take the unbalance pickup and the delay from the relay manual and the motor's thermal limit data, keep the delay below the motor's negative-sequence withstand time, and prove the scheme with secondary injection before the motor returns to service.

  1. Read the motor's thermal limit curve from its datasheet, not from a generic table.
  2. Set the 46 pickup above the motor's normal current unbalance at run and below the unbalance a real open phase produces; set the delay below the thermal limit curve.
  3. Wire the trip output to the contactor coil circuit or the control-power interrupt so the motor stops without waiting for the overload element.
  4. With the motor locked out and the relay in test mode, inject balanced three-phase current near the normal running current and confirm no alarm.
  5. Remove one injected phase while holding the other two and confirm the trip within the programmed delay and that the contactor circuit opens.
  6. Repeat with one phase removed at a light injection level, for example 40% of the running current, and confirm the trip still occurs where the overload element would stay quiet.
  7. Restore the circuit, run the motor and record the three line currents; release it to service only with unbalance below the alarm level.

What do you repair on the branch, and can feeder-level detection ever work? #

Repair the failed joint and torque it to the manufacturer's value, and if feeder-level detection is required add a negative-sequence or voltage-based element at the branch point, because no feeder residual-current setting can be made to see this event.

  • Isolate and lock out the branch before any inspection.
  • Inspect jumpers, clamps, cutouts and tap connections for heat discoloration, pitting and arcing marks; an infrared scan under load shows a hot joint before it opens.
  • Replace the damaged hardware, torque to the manufacturer's value and apply the compound the connector requires.
  • Confirm each joint with a low-resistance measurement against an equivalent healthy joint before re-energizing.

Decisions, by case. Delta or ungrounded-wye primary: the feeder ground element is blind at any setting, so fit 46 or phase-loss detection at each motor and a voltage-sensing element at the branch. Grounded-wye primary: the residual is still a fraction of the pickup, so the same remedy applies. In both cases the feeder settings stay where they are, because they operated as set, and the motors stop being their own only protection.

Questions asked

Why does a motor on a variable frequency drive usually survive a lost input phase?

Most drives detect the DC-bus ripple a lost input phase causes and stop on a phase-loss fault, so the motor is switched off instead of running single-phased. Confirm the behavior in the fault table for the specific drive model and firmware revision. The exposure is mainly across-the-line motors and soft-started motors.

How long can a fully loaded motor run on two phases before it is damaged?

The withstand time comes from the motor's thermal limit curve, not a generic number. The two live lines carry roughly 1.73 times normal current, so a healthy overload relay trips on its curve; damage happens when the overload is bypassed, set too high, or the motor is lightly loaded and nothing trips while negative-sequence current heats the rotor.

Why is a blown branch fuse an open phase and not a fault?

A fuse clears when current exceeds its curve; once it opens, the circuit carries less current, not more. Downstream equipment sees an open conductor. Protection that responds to overcurrent or residual current therefore stays quiet, and only unbalance- or voltage-based elements respond to the event.

Can a phase-loss relay on the motor control circuit replace a 46 relay?

For across-the-line motors, yes: a phase-loss relay sensing at the motor controller drops the contactor coil when a phase opens, at any load level. A voltage-sensing type can be masked by a running motor regenerating the open phase at its own terminals, so place it ahead of the motor or use current sensing, and verify the sensing type in the relay datasheet.

Keep reading

  • Comparison

    Why induced voltage defeats simple phase loss protection

    A spinning motor regenerates roughly half its normal voltage onto an open phase, so a phase loss relay that watches voltage alone can hold the contactor in while the motor single-phases. Set the relay's dropout above your measured back-feed voltage — or drop voltage sensing for per-phase current, unbalance or phase-angle detection, which the back-feed cannot fool.

    Protection: breakers, fuses and SCCR

  • Comparison

    What current-only motor protection can and cannot detect

    Three per-phase current amplitudes support overload, phase loss, current unbalance, stalled acceleration and short-cycling protection, and nothing else. Undervoltage, ground fault, winding temperature and mechanical overloads such as high head pressure need their own inputs: a voltage measurement channel, a core-balance current transformer, and temperature or pressure sensors.

    Protection: breakers, fuses and SCCR

  • Explainer

    What happens when a three-phase motor loses one phase

    A running three-phase motor that loses one phase keeps spinning but drops torque, pulls elevated current in the two live lines and heats its rotor from a negative-sequence component. Stop it at once and find the open point with the circuit dead, and protect the machine with a phase-loss or negative-sequence (element 46) function set from the motor and relay documentation — a plain thermal overload acts too late.