Troubleshooting
Why motor current is missing from a drive telegram over PROFIBUS DP
Short answer
A drive on standard telegram 20 returns six PZD words carrying only what p2051 maps, so missing motor current over PROFIBUS DP is a mapping, addressing or scaling problem, not a bus fault. Read the current at the drive, confirm the p2051 assignment, then address the word at base + 2 × (position − 1) and convert the percent value against the drive's reference current.

On this page
A CPU C315-2PN/DP controlling SINAMICS G120 drives over PROFIBUS DP on standard telegram 20 receives six process data words back from each drive, and those six words carry exactly the signals that parameter p2051 maps into them, nothing else. When motor current will not show up in the PLC, the cause is one of three: the current actual value is not in the transmitted telegram, the PLC is reading the wrong input word, or the word is converted with the wrong scale. A working run command proves the command path, not the feedback path. Work the checks in order: the current the drive itself reports, the assignment in p2051, the input word address, then the percent-to-ampere conversion.
Check the current the drive itself reports #
Run the motor at a steady load and read the current actual value from the drive's operator panel or commissioning software before touching the telegram. The value should be a real ampere figure that follows the load.
Three actual-value signal names sit behind this question: IAIST is the current actual value, MIST the torque actual value and PIST the power actual value. They are different quantities in different units, and all three move with load, so a changing word is not proof that the word is current. Decide too which current you expect: the telegram value is the motor-side output current, and a drive's input current is a different number that can run higher — see why a drive's input current can run higher than its output current.
Record, before going further:
- the local display reading in amperes and the load it was taken at;
- the signal name the drive shows for the quantity you want (IAIST, MIST or PIST);
- the control unit and firmware version you are reading, so the telegram documentation you check matches;
- whether the local value is smoothed, because the drive's display and the raw word update at different rates.
If the local reading is missing or implausible, fix the drive side first: no telegram mapping can repair a measurement the drive is not making.
Read the local value from the panel or the commissioning tool while the machine runs under its normal guarding. If any check needs the cabinet open, de-energize and verify absence of voltage first, and confirm the applicable rules with your authority having jurisdiction and the machine documentation.
Check what p2051 transmits #
The six feedback words are a contract fixed by the selected telegram, not six self-describing values. p2051 shows, index by index, which signal the drive puts into each transmitted word on the interface in use. The first transmitted word is the status word, so when the telegram carries the current actual value, it sits at one of the later indices. Open p2051 on the drive, compare what it shows with telegram 20's documented layout in the operating instructions for your control unit and firmware, and note the index where IAIST appears.
The observation decides the next move:
- IAIST present at some index, for example index 1, which is transmitted word 2 → the mapping is fine; go to the address step.
- The index you have been reading holds MIST or PIST → the PLC has been displaying torque or power all along; point the PLC logic at the right word instead of rescaling it.
- No current signal anywhere in the transmitted telegram → the telegram selection is the problem, not one entry. A standard telegram fixes what controller and drive exchange, so look in the telegram documentation for a documented configuration that includes current rather than writing an arbitrary signal into a single index.
For the drive-side configuration steps, walkthrough on mapping telegram PZD words through p2051 interconnections shows the parameter side end to end.
Worked example: one G120 on telegram 20 with IAIST in transmitted word 2 #
The inputs, and where each comes from:
- Standard telegram 20, PZD-2/6 — the configuration in the question; the telegram list documents it as two words to the drive and six words back, so six feedback words per drive.
- Word width — a PZD word is 16 bits, that is 2 bytes; six feedback words occupy 12 bytes.
- Assignment —
p2051[1]shows IAIST in this example, so the current is transmitted word 2, because index 0 is the status word. - Input base — 512 in this example; the real value comes from the address assigned to that drive's DP station in the PLC hardware configuration.
- Raw word — 8192, an example reading taken at the computed address while the motor runs.
- Percent encoding — the drive's telegram documentation encodes these values as percent, with hex 4000, decimal 16384, meaning 100 percent.
- Reference current — 10.0 A in this example; read yours from the drive's reference parameters, not from memory.
Two rules in words: the transmitted word for position k, counting from 1, begins at byte offset base + 2 × (k − 1); and the ampere value is the raw count divided by 16384, multiplied by the reference current.
The arithmetic:
- Address: 512 + 2 × (2 − 1) = 512 + 2 = 514, so the current word occupies input bytes 514 and 515, read as one 16-bit word.
- Area check: 6 words × 2 bytes = 12 bytes, so this drive's feedback spans bytes 512 to 523 and word 2 lands inside it.
- Conversion: 8192 ÷ 16384 = 0.5, and 0.5 × 10.0 A = 5.0 A.
Result: with these inputs, the current word lives at bytes 514 and 515 and should read 8192 counts, which converts to 5.0 A. Decision: if the drive's local display shows about 5 A at that load, the mapping and the conversion are both proven; if the raw word stays frozen at every load, fix the position or the assignment before rescaling anything; if the word follows the load but the amperes disagree, reread the percent base and the reference current from the drive's parameters.
Tell a mapping problem from a bus problem #
Watch the raw word and the station diagnostics together:
- Status word changing, current word steady: the cyclic link is alive, and a steady current at a steady load is a steady word. Watch the word through a start or a load change before calling it broken.
- Current word frozen through every start and load change: the position you are reading is not carrying the current actual value — go back to
p2051. - Station diagnostics active: clear the reported configuration or bus fault first. Counts received while a diagnostic is pending say nothing reliable about mapping.
- Four drives on one CPU: check that every DP station has its own input area. Two stations sharing a base address put one drive's feedback where the logic expects another drive's, and the value looks plausible because it is a real measurement from a different motor.
Watching one raw input word follow the load is the same word-level check used when reading actual speed from a SINAMICS drive into an S7-1200.
The decision, in order #
- Read the current at the drive. If that value is invalid, repair the drive side first.
- Read
p2051for the interface in use. IAIST present → note its index and compute the byte offset, base + 2 × (k − 1). IAIST absent → choose a documented telegram configuration that carries it; do not rewrite a single index under a standard telegram. - Monitor the raw word at the computed address. Frozen at every load → mapping or addressing problem; fix it before touching the conversion.
- Convert with the documented percent base and the drive's own reference current, then confirm the result against the local display at a known load.
- If the current only feeds an alarm and the mapping is not otherwise wanted, a hardwired current transducer is the simpler path — measuring three-phase motor current for a PLC alarm input covers that wiring.
Questions asked
What is the difference between IAIST, MIST and PIST?
IAIST is the current actual value in amperes, MIST the torque actual value and PIST the power actual value. All three follow the load, so a moving word is not proof that you are reading current. Check the p2051 assignment to see which signal sits in each transmitted word; if the index you read holds MIST or PIST, the PLC has been showing torque or power, and no amount of rescaling turns that into current.
Can a different signal be written into p2051 while a standard telegram is active?
Not as the first repair. A standard telegram defines what the controller and the drive exchange, and the drive configuration and the PLC hardware configuration both assume that layout. If the current actual value is not part of the selected telegram, use the telegram documentation for your control unit and firmware to choose a documented configuration that carries it, and update the drive and the PLC side together.
Do the torque and power words convert the same way as the current word?
The percent encoding is the same, hex 4000 or decimal 16384 for 100 percent, but each quantity references its own reference parameter, so one multiplier will not convert current, torque and power correctly. Read the reference current, reference torque and reference power from the drive's parameters and convert each word against its own reference.
Why does the value in the PLC look like a command instead of a measurement?
Cyclic feedback arrives in the PLC input area and commands leave through the output area. If the logic points at an output word, it reads back what the PLC itself sent, which looks plausible but is not a measurement. Check the address given to the drive's DP station in the hardware configuration and read the feedback from the input area at the computed byte offset.


