Why a VFD motor overload current setting takes nameplate FLA

Variable frequency drives Published 8 min read

Short answer

Enter the motor's nameplate full-load current — for a 2 hp, 460 V motor, 3.4 A — in every drive field that asks for motor rated or overload current. The drive's thermal model applies its own margin and trip curve on top, so pre-multiplying by 125% stacks a second margin and pushes the effective pickup near 156% of nameplate. NEC 430.32's 125% and 115% figures cap separate overload devices; they are not data-entry instructions.

On this page
  1. What current goes in a VFD motor overload setting?
  2. Why do people set motor overload at 125% of FLA?
  3. What does NEC 430.32 actually cover?
  4. What happens if you enter the multiplied current instead of the plate value?
  5. How much extra heat does that stacked pickup let a motor absorb?
  6. Can a current-based drive model catch a blocked cooling fan?
  7. Why are nameplate FLA and overload current the same number in a new drive?
  8. What is the decision for each case?
  9. Questions asked

A drive field that asks for the motor's rated or overload current wants the number on the motor plate, not a percentage of it. Set that entry to nameplate full-load current exactly as stamped — for a 2 hp, 460 V three-phase motor that is 3.4 A — and let the drive's thermal model add the margin it was designed with. The percentage figures in NEC Article 430.32 are selection ceilings for a separate overload device, not instructions for drive data entry. Scale the plate value up by any fraction of itself before entry and you have told the thermal model the motor is a bigger machine than its plate declares; the sections below run the arithmetic and end with the decision for each case.

What current goes in a VFD motor overload setting? #

Enter the motor's full-load current exactly as the nameplate states it — nothing added — in every drive field defined as motor rated current, motor FLA or motor overload current, because that field is the base of the drive's thermal model, not a trip point you get to raise.

Every motor-current field on a setup screen is read as a description of the motor. The drive builds its thermal estimate from that declared base, then applies its own pickup level and time-current curve on top, and that internal curve is where the protective margin is supposed to come from. The margin is the drive's job; the entry is only the truth about the motor. The worked example below shows what the model does when the entry itself carries the margin.

Why do people set motor overload at 125% of FLA? #

The habit comes from NEC Article 430.32, which caps how a separate overload device may be selected, and installers carry that ceiling into drive parameters where it does not belong.

The origin is legitimate. On an across-the-line starter, the overload relay is a separate device selected in amperes, and hard-starting loads sometimes justify deliberately turning its dial toward the ceiling, a practice covered in setting overload relays for high-inertia motor starts. The error is carrying that move into a drive's motor-data field. A field defined as motor rated current does not select a trip level; it declares what the motor is, and the drive's protection algorithm builds its curve around that declaration. Raising the declaration raises the whole curve.

What does NEC 430.32 actually cover? #

NFPA 70, the National Electrical Code, 2023 edition, Article 430.32(A)(1) caps a separate overload device at 125% of nameplate full-load current for a motor marked with a service factor of 1.15 or greater or a temperature rise of 40 °C or less, and at 115% for all other motors.

The article governs the selection of overload devices that protect the motor itself — the relay beside a contactor, an electronic overload, the thermal element of a breaker applied for motor protection — not conductor sizing, not short-circuit protection and not any drive's data entry. The percentages are ceilings: a device is selected at or below them, and the next lower standard heater or dial size is compliant. For the separate-relay case the plate value is still the base, as setting overload relays from motor nameplate full-load current explains. Confirm the adopted edition and any local amendments with your authority having jurisdiction.

What happens if you enter the multiplied current instead of the plate value? #

Entering the multiplied value tells the thermal model the motor is a larger machine than its plate declares, and the model then leaves current uncounted until it reaches a pickup far above what the copper survives continuously.

A worked example, with every input stated. Motor: 2 hp, 460 V, three-phase, TEFC enclosure, nameplate full-load current 3.4 A. Wrong entry: 3.4 A × 1.25 = 4.25 A. Assume, for illustration only, that the drive's thermal model reads that entry as the motor's rated current and begins accumulating heat at an internal pickup above the base; the manual's overload description is the authority for your drive's actual figure. Stacked pickup: 4.25 A × 1.25 = 5.31 A, which is 1.5625 times the plate value — about 156% of nameplate full-load current. The model now treats as ordinary operation a current the copper cannot carry continuously, and the code conclusion — the plate value belongs in the field — holds whatever the drive's real pickup turns out to be.

Quantity Example value Basis
Nameplate full-load current 3.4 A Motor plate, 2 hp, 460 V, three-phase example
Multiplied drive entry 4.25 A Plate value scaled by the code percentage; not a valid entry
Effective pickup with stacked margins 5.31 A, about 156% of the plate value Illustrative model assumption; verify the pickup in the drive manual
Heating rate tolerated at that pickup about 2.44 times rated Current-squared calculation, constant winding resistance assumed
Code ceiling, motor marked service factor 1.15 or higher or temperature rise 40 °C or less 125% of nameplate full-load current NFPA 70 (NEC), 2023 edition, 430.32(A)(1)
Code ceiling, all other motors 115% of nameplate full-load current NFPA 70 (NEC), 2023 edition, 430.32(A)(1)

The same wrong base spreads beyond protection. On many drives the motor-data set also feeds the control side — flux estimates, torque limits, speed calculations — so an inflated rating skews those too. And when the model does exhaust its thermal margin, the drive announces the result as its motor overload fault, which why a VFD reports a motor overload fault covers in detail.

How much extra heat does that stacked pickup let a motor absorb? #

Winding heating rises with the square of current, so a pickup at about 156% of nameplate tolerates roughly 2.4 times the rated copper-loss rate — a sustained overload the correct plate entry would have caught in minutes.

The squaring works twice. The multiplier that produced the stacked pickup, squared, is 1.5625 — 25% more current means 56% more copper heat. The stacked ratio then squares in turn: 1.5625² ≈ 2.44, so the model sits idle while the winding dissipates about two and a half times its rated loss. Both figures assume a constant winding resistance; resistance climbs with temperature, and a shaft-driven fan moves less air exactly when a slow, heavily loaded motor needs cooling most, so the true margin is worse than the arithmetic shows. A motor parked at that operating point cooks on a schedule the model cannot see, and the aftermath — insulation at end of life with an empty trip history — is a diagnosis of its own, worked through in why motors burn up with no overload trips on 480 V.

Can a current-based drive model catch a blocked cooling fan? #

No — the model estimates heat from the current it measures, and it has no way to see a cardboard box pressed against a TEFC motor's fan intake, a fan that slipped on its shaft or a shroud packed with dust.

A motor at exactly its plate current with its cooling air blocked or its fan loose is overheating while the model reads a healthy load, and it will reach the end of its insulation life with a protection history that shows nothing unusual. Airflow is one fix: keep intakes clear, keep the shaft fan secure, and put shroud and dust checks in the maintenance round. Winding temperature is the other: wire the motor's PTC thermistor or embedded sensor to the drive's temperature-sensor input, where the drive provides one, so the trip follows measured winding heat instead of an estimate. Long low-speed running is the same trap in slow motion, because shaft-driven airflow falls with speed while the model still counts only amperes.

Why are nameplate FLA and overload current the same number in a new drive? #

Because both entries feed the same thermal model: the setup screen collects the motor's rating once, the overload function derives its curve from that base with its margin applied internally, and the correct value in both places is therefore the plate value, identical by design.

The equality is the design, not a missing step. Some drives keep a single motor-data set and expose no separate overload entry at all; some expose one, and their manuals still define it as the motor's rated current, which takes the plate value again. The one legitimate home for a factor is a parameter the manual defines as a pickup multiplier or a service factor applied on top of rated current — set that parameter once, deliberately, and never fold the factor into the motor data itself. The manual's definition of each field decides; the plate value goes wherever the field asks what the motor is.

What is the decision for each case? #

Enter the plate full-load current in every drive field defined as motor rated, nameplate or overload current; reserve the NEC percentages for selecting a separate overload device; and fix nuisance trips on the time side — the ramp, the trip class or the drive sizing — never by inflating the motor's declared current.

Hands-on parameter work means the drive's cover comes off, so de-energize, lock out and verify absence of voltage before opening the enclosure; NFPA 70E, 2024 edition, treats energized work as the exception that requires an approved permit, and your authority having jurisdiction and the drive documentation govern the details.

  • A drive field asking for motor rated current, motor FLA or motor overload current: the plate value, unmodified, in every one.
  • A separate overload relay beside a contactor: select at or below the applicable 430.32 percentage for the motor's markings; the next lower standard size is compliant, because the figure is a ceiling, not a target.
  • Long or slow starts tripping the overload: extend the acceleration ramp, select a heavier trip class if the drive exposes one, or resize the drive and motor for the duty; the trip-class logic behind that choice is the same as a relay's, covered in reading overload relay trip classes and curves.
  • Blocked intake, slipped fan, dust-caked shroud or heavy low-speed duty: housekeeping plus winding-temperature sensing, because no current entry can cover those.
  • A motor tripping on load it should carry: recheck the entered motor data against the plate first, measure the drive's output current under load, then look at cooling — in that order.

Questions asked

Does the NEC overload percentage rule apply to the motor current entered in a drive?

No. The percentages in NEC Article 430.32 (NFPA 70, 2023 edition) cap how a separate overload device is selected or rated, not what goes into a drive's motor data. A field defined as motor rated current takes the nameplate value, and the drive's thermal model applies its own margin. Confirm the adopted code edition with your authority having jurisdiction and the field's definition in the drive manual.

Is a separate overload relay still needed when a VFD supplies the motor?

For a single motor on its own drive, NFPA 70 (NEC), 2023 edition, Article 430 Part X recognizes overload protection provided by the drive's own protective system under the conditions it sets, so a separate relay is often not required. A separate device returns when several motors share one drive or the design calls for it. Confirm the arrangement with your authority having jurisdiction and the drive documentation.

What protects a TEFC motor that runs for long periods at low speed?

Shaft-driven cooling falls off at low speed while a current-based model still sees only amperes, so the motor can overheat inside its declared current. Check whether the drive offers a thermal model that reduces allowable current at low output frequency and enable it, shorten the low-speed duty, or add winding temperature sensors that trip on actual winding heat.

How do I stop nuisance overload trips during long accelerations without changing the motor current entry?

Work on the time side, not the current base. Extend the drive's acceleration ramp, select a heavier trip class if the drive exposes that setting, check the driven load for changed inertia or a mechanical bind, and confirm the drive and motor are sized for the duty. Raising the declared motor current only moves the whole curve and removes protection the motor was counting on.

Should winding temperature sensors be added even when the drive's motor data is entered correctly?

Yes, whenever cooling can fail without an overcurrent: blocked fan intakes, a slipped shaft fan, dust-caked shrouds, high ambient heat or heavy low-speed duty. Many drives accept a PTC thermistor input that trips directly from winding temperature, which is the one measurement a current-based model can never make. Wire the sensor per the drive documentation and test the trip path at commissioning.

Keep reading

  • Troubleshooting

    Why a pump makes less pressure on a VFD than a starter

    At 16 A against a 12.5 A nameplate FLA, with 40 psi instead of 80 at a full-frequency command, the motor is slipping heavily rather than running at full speed. Check pump rotation first, then the drive's motor-data and volts-per-hertz settings against the nameplate. The drive's frequency and rpm displays are commanded and calculated values, not measurements of the shaft.

    Variable frequency drives

  • Troubleshooting

    Why a VFD reports a motor overload fault

    A motor overload fault on a VFD means the drive's electronic thermal model accumulated heat from current above the motor's entered rated current. Compare measured current with both the nameplate full-load current and the drive's entered value before changing any setting: the fix is the load, supply, cooling, or the typed-in number, almost never a raised limit.

    Variable frequency drives

  • Troubleshooting

    Finding a 113 V drop between a VFD and the motor terminals

    The drop is real, it lives in the path between the drive lugs and the terminal box, and it works out to about 0.36 Ω per phase — enough to dissipate roughly 11 kW per phase if it is resistance. Verify the reading with a drive-rated meter, then find it with an infrared scan under load and a micro-ohmmeter on every joint; the motor is downstream of both measurement points and is not the cause.

    Variable frequency drives