Troubleshooting
Why servo ground fault lights track a shared DC supply
Short answer
On servo drives fed from one DC supply, a ground-fault lamp reports what its detection circuit sees on the shared supply and chassis reference, so leakage anywhere on that circuit lights lamps on healthy axes and the fault appears to follow whichever drive is unplugged. Replace no capacitors or resistors yet: isolate one branch at a time, power off and bus discharged, from the transformer terminals outward. Here the path was carbon dust inside a brushed servo motor, confirmed by a motor repair shop.

On this page
- A ground-fault lamp reports a circuit, not an axis
- Decoding the plug combinations
- The 3000 ohm resistor across the capacitor is collateral damage
- Worked example: a 240 V service on a machine wired for 208 V
- Isolate from the transformer terminals outward
- What the carbon dust settles
- Decision for each case
- Questions asked
On a multi-axis servo drive line-up fed from one DC supply, a ground-fault lamp reports what its drive's detection circuit sees, and those circuits share the supply conductors and the chassis reference. Leakage anywhere on that shared circuit lights lamps on drives whose own motor circuits are clean, which is why the fault seems to move when you unplug combinations: with one drive connected the other two light up, with all three connected all three light. The decision: stop replacing capacitors and resistors, and isolate one branch at a time — power off, bus discharged — from the transformer terminals outward. On the machine worked through here, the path was carbon dust inside a brushed servo motor, confirmed by a motor repair shop.
A ground-fault lamp reports a circuit, not an axis #
Servo amplifier documentation for one mainstream drive family lists a ground fault as detected either by a hardware detection circuit or by a software detection function. Either way, the lamp is the output of a detector comparing currents and voltages against a threshold, and on drives fed from a common DC bus the detector's supply and reference conductors are shared. The wiring that produces this behavior is the wiring described in DC bus sharing on servo drives: one supply, one filter group: one supply and one reference tie the axes together electrically, and their fault indications come along for the ride. So never map lamp position to fault position until the plug tests say you can.
Decoding the plug combinations #
- All three power plugs in, all three lamps on. The leakage sits on the common bus, on the shared reference network, or on an auxiliary branch that every drive monitors.
- One plug in: the connected drive dark, the two unplugged drives lit. The connected drive completes its normal local circuit; the unplugged ones report the shared fault condition through the conductors they still share. This pattern clears every output stage and points upstream.
- One axis's motor power leads off, nothing changes. That axis's power circuit is not the path. Move to the auxiliary transformer branch and to the feedback wiring.
- A new DC-link capacitor, lamps unchanged. The repair restored one component; the conductive path to chassis survived it. Resets do not remove a path either — the same reason an intermittent VFD ground fault returns after reset.
The working rule: if the lamp jumps to whichever drive is unplugged, the leakage is upstream of the drives — supply, reference network or auxiliary branch — and no axis is proven guilty.
The 3000 ohm resistor across the capacitor is collateral damage #
Those resistors are bleeders. Once the supply is removed, they drain the charge stored in the DC-link capacitors so the bus decays to a safe level; with a failed, shorted capacitor the bus voltage sat across its bleeder and cooked it, which is why one of the pair showed heat damage. Identical low readings on both, taken in circuit, prove nothing, because an in-circuit measurement includes every parallel path; lift one end after verified discharge and compare against the marked value and tolerance.
Two decisions follow. Replace the damaged bleeder after the ground fault is cleared, not before — a new resistor cannot extinguish a lamp that carbon or a pinched conductor keeps lit. And never pull the bleeders, or the connection between DC negative and chassis, as a diagnostic shortcut: on this class of machine that connection can be the discharge path, the voltage reference, or part of the monitoring circuit, and only the machine schematic says which. Remove it blind and the bus holds its charge with nothing left to drain it.
Worked example: a 240 V service on a machine wired for 208 V #
Inputs, with sources:
- The machine was wired for the previous shop's 208 V single-phase service, and the new shop supplies 240 V single-phase (both from the service history of this case).
- The bridge rectifier measured serviceable on the bench (a check made in this case).
- The actual DC bus voltage was not recorded; it depends on transformer links, rectifier drop and load, so this example computes the input-side mismatch only.
The rule, in words: percentage change equals the change divided by the original value, times one hundred. A rectifier feeding a capacitive bus tracks the transformer secondary — the peak of a sine scales with its RMS value — so until the transformer links are changed for the new service, the bus runs high by roughly the same percentage.
Arithmetic: (240 V − 208 V) = 32 V; 32 V ÷ 208 V = 0.154; 0.154 × 100 = 15.4%.
Result: the incoming supply sits 15.4 percent above what the machine was connected for — an estimate of the mismatch, not a measured bus voltage.
Decision: re-link the machine transformer for the new service, per its wiring diagram, before judging any bus measurement or commissioning the replacement capacitor, because sustained overvoltage is a standard way to destroy an electrolytic capacitor — and the rectifier that measured good stays in the cabinet. On this machine the correction brought the bus down and the lamps stayed lit: the two faults were independent, and only the isolation below found the second one.
Isolate from the transformer terminals outward #
Lock out the incoming supply, verify absence of voltage at the work point, and confirm on a meter rated for the bus voltage that the DC bus is flat before any connection comes apart. On a machine with a ball-screw Z axis, secure the head against gravity before disturbing that motor or its brake, because a vertical Z axis back-drives with servo power off.
- Photograph and label every connector, then identify on the machine schematic the DC supply, motor power, feedback, protective earth and auxiliary branches. Wire color and connector position are not identification.
- With power off and the bus confirmed flat, disconnect one motor power cable at a time and re-test only in a configuration the manufacturer permits, noting which lamps change. If one axis's cable coming off clears the lamps, that cable or its motor is the path.
- Test cable and motor separately so the result distinguishes cable insulation from motor insulation. Never apply an insulation tester through an amplifier, encoder or tachometer interface; take test voltage and acceptance limits from the component documentation or hand the motor to a repair shop. A path can pass a low-voltage continuity check and still conduct under working voltage — one reason a drive trips ground fault with good megger readings.
- If the motor branches pass, work the 110 VAC auxiliary branch: remove its loads a few at a time — on the machine in this case, the items fed from terminals 1 and 2 — until the lamps drop out. On this class of machine, a typical ground fault is a short in that control circuit or in a motor or its cable.
- A continuity reading to chassis on a pulled pair of control conductors — here the pair numbered 34 and 35 at the transformer terminals — locates a branch, not a verdict. Check the drawing for an intentionally grounded conductor before condemning it, then split the branch at accessible points until the path is cornered.
What the carbon dust settles #
The leak in this case was inside a brushed servo motor: brushes and tachometer shed carbon for nineteen years, and packed dust bridged to the frame — a path found only after the DC leads were cut, and verified as current leakage to chassis by a motor repair shop. Cleaning the interior and re-testing cleared it.
Three things that finding settles. A fault that vanishes when you cut a motor's leads proves the path lies beyond the cut; it did not heal. Re-test after cleaning, because the brushes keep shedding, and dust left where you cannot reach — under a tachometer rotor still on the shaft — keeps the path ready to return. And insulation this old gets replaced as a cable, not spliced: here the encoder insulation had hardened until the tie wraps crumbled, and feedback conductors share the motor's flex points with the power leads.
Decision for each case #
- Lamps follow whichever drives are unplugged: leakage on the shared supply, the reference network or an auxiliary branch. Isolate at the transformer terminals; no drive is proven bad.
- Lamps tie to one drive only when its motor cable is reconnected: the path is that cable or that motor. Test them separately.
- New capacitor, lamps unchanged: the conductive path survived the repair. Return to branch isolation.
- Hot bleeder beside a failed capacitor: collateral damage. Replace it after the fault is cleared, tested out of circuit.
- Bus high after a move between services: correct the transformer configuration first, then judge everything downstream.
Questions asked
How long do you wait for a shared DC bus to discharge before touching it?
There is no fixed safe time to quote. The decay time is set by the bleeder and capacitor values, and an open or removed bleeder leaves the capacitors holding charge indefinitely. Treat the bus as live until a meter rated for that DC voltage reads near zero at the documented test points, and re-check before each new step rather than once at the start.
Is the alarm code by itself enough to order parts?
No. An alarm number means what that control version's documentation says it means, and the same cabinet carries relay lamps and diagnostic indicators whose meaning comes only from the machine drawings. Record every lit code and lamp, then let the isolation tests pick the branch. Here the code, the ground-fault lamps and a serviceable bridge rectifier all coexisted with a carbon-dust leak that no replacement part would have fixed.
Should the bridge rectifier be replaced on suspicion?
No. Measure it and the bus instead. In this case it checked serviceable, and rectifier failures rarely hide: a shorted diode usually clears the input fuse or trips the breaker, while an open one leaves the bus low or absent. A ground-fault lamp on its own does not implicate the rectifier, and swapping it ahead of the isolation steps only delays finding the real path.
Does a ground-fault lamp that relights after a motor cleaning mean the repair failed?
Not necessarily. Carbon-dust paths return when the brushes shed again or when the cleaning missed a pocket of dust. The shop re-test is the arbiter: a motor that shows no leakage to chassis after cleaning is done, so a lamp that relights afterward points back to the cable, the connectors or another branch, and the isolation order starts again before the motor is opened a second time.


