Why transformer primary to secondary insulation resistance fails

Power distribution and transformers Published 6 min read By Current Intel engineering team

Short answer

A two-winding transformer has three separate insulation paths, and passing primary-to-ground and secondary-to-ground does not clear the third. For the 3000 kVA, 20 kV/90 V example, the 191 MΩ interwinding reading fails the minimum of roughly 6,300 to 11,000 MΩ, computed from the primary voltage.

On this page
  1. The three insulation paths
  2. The minimum and the worked example
  3. Why the two readings cannot both be true
  4. Retest procedure
  5. What the retest should show
  6. Common calculation errors
  7. Questions asked

Yes, you have to test the primary-to-secondary path separately, and on the 3000 kVA, 20,000 V / 90 V unit in the example the 191 MΩ reading fails. The minimum for that interwinding test uses the primary winding voltage in E, not the secondary voltage: with C of 30 for untanked coils and core, the minimum is about 10,954 MΩ for a delta primary (20,000 V) or 6,325 MΩ for a wye primary (20,000 V divided by 1.732, which is 11,547 V). The 191 MΩ result sits a factor of about 33 to 57 below the minimum, so treat it as failed or invalid until a guarded retest says otherwise.

The three insulation paths #

A two-winding transformer has three separate barriers, each measured with its own connection:

  • Primary winding to ground (the core and tank), tested with the secondary shorted to ground.
  • Secondary winding to ground, tested with the primary shorted to ground.
  • Primary to secondary, tested with the core or tank connected to the megohmmeter guard terminal so only the interwinding path is measured.

The primary field stresses two of them: the primary-to-core insulation and the interwinding barrier. Because the secondary winding sits near ground potential relative to the primary, the full primary winding voltage appears across the interwinding insulation. That is why E for the primary-to-secondary minimum comes from the primary.

The minimum and the worked example #

The minimum follows the form Rmin = C × E / √kVA, where E is the winding rated voltage in volts, kVA is the transformer rating, and C is 30 for untanked coils and core. The square-root term divides. E is the line-to-line rating for a delta winding and the line-to-line rating divided by 1.732 for a wye winding; the nameplate connection decides which case applies.

For the 3000 kVA unit, the divisor is the square root of 3000, which is 54.77. The primary-to-secondary minimum is 30 × 20,000 / 54.77 = 10,954 MΩ for a delta primary, or 30 × 11,547 / 54.77 = 6,325 MΩ for a wye primary. The measured 191 MΩ fails both. Substituting the 90 V secondary rating instead would give about 49 MΩ and would let 191 MΩ pass; that is a calculation error, not a result. Confirm the C factor for your construction against the tables in EASA AR200-2021, the repair guide for dry-type transformers, which lists recommended minimums and test levels for dry-type windings, and against IEEE C57.125 for core and coil condition assessment; verify the requirement with the transformer manufacturer and the authority having jurisdiction.

Path E used Minimum, delta primary Minimum, wye primary Measured Result
Primary to ground (secondary grounded) Primary winding voltage about 10,954 MΩ about 6,325 MΩ 13,200 MΩ Passes both
Secondary to ground (primary grounded) Secondary winding voltage (90 V delta, 51.96 V wye) about 49 MΩ about 28.5 MΩ 2000 MΩ Passes both
Primary to secondary Primary winding voltage about 10,954 MΩ about 6,325 MΩ 191 MΩ Fails both

For core and coil inspection practice behind these limits, the guide to transformer core and coil inspection under IEEE C57.125 walks through the same assessment framework.

Why the two readings cannot both be true #

With the secondary shorted to ground, the primary lead sees the primary-to-secondary insulation and the primary-to-core insulation in parallel. A parallel combination is never higher than its smallest branch. If the interwinding resistance were truly 191 MΩ, the primary-to-ground reading with the secondary grounded could not have reached 13,200 MΩ. One of these is the explanation:

  • The secondary short was not bonded to ground during the primary-to-ground test (open or high-resistance ground lead), so that reading saw the primary-to-core path only.
  • The 191 MΩ reading includes surface leakage across dirty or damp bushings, terminal boards or cable stubs, which a guarded connection would have removed.
  • The two tests ran at different temperatures, moisture states, or electrification times.

A continuity check from the secondary shorting bar to ground, followed by a guarded retest, decides between them.

Retest procedure #

De-energize, isolate, and discharge the unit, then test for absence of voltage before touching any terminal. Disconnect all external cable, bus and connected equipment from both windings.

  1. Short all terminals of each winding together, all three phases per winding. Never apply the DC test voltage across the 90 V winding terminals; the winding is tested as one electrode.
  2. Record winding temperature and correct readings to the reference temperature of the standard you test to.
  3. Clean and dry bushing and terminal surfaces before the first reading.
  4. Verify with an ohmmeter that the secondary shorting bar has continuity to ground, then measure primary to grounded secondary.
  5. Short the primary and ground it, then measure secondary to grounded primary.
  6. Connect the core or tank ground to the megohmmeter guard terminal and measure primary to secondary, so only the interwinding path is measured.

Use the same test voltage and reading time for all three tests, as set by the standard and the manufacturer, and log every value with its temperature.

What the retest should show #

  • The guarded primary-to-secondary reading at or above the primary-referenced minimum, about 10,954 MΩ for delta or 6,325 MΩ for wye. A result still near 191 MΩ confirms contamination or moisture in the insulation system, not a test-lead artifact.
  • The primary-to-ground reading not greater than the guarded interwinding reading, because the two paths run in parallel when the secondary is grounded.
  • The secondary-to-ground reading at or above about 49 MΩ for delta or 28.5 MΩ for wye; the 2000 MΩ result is well clear of both.

Common calculation errors #

  • Multiplying by the square root of kVA instead of dividing, which produces tens of millions of megohms.
  • Using the secondary voltage for the interwinding minimum, which understates it by more than two orders of magnitude here.
  • Using the line-to-line value for a wye winding: divide by 1.732 (11,547 V here) and confirm the connection on the nameplate rather than assuming.
  • Applying C of 30 to a tanked or oil-filled unit; that constant is for untanked coils and core, and the standard's table gives the value for your construction.
  • Running the interwinding test unguarded, which lets bushing surface leakage corrupt the reading in both directions.
  • Comparing readings taken at different temperatures, moisture states or electrification times.

The decision: test all three paths on every insulation resistance campaign, take the interwinding minimum from the primary winding voltage, and on the example unit the 191 MΩ reading is a fail or an invalid measurement. Confirm the secondary ground bond, retest with the guard terminal, and keep the transformer out of service until the guarded interwinding reading clears the minimum for its winding connection.

This article describes insulation testing on a de-energized, isolated and discharged unit only; it is not a go-ahead for energized work, and the de-energize, lockout and absence-of-voltage steps come before any terminal box or connection is opened, under NFPA 70E, 2024 edition, confirmed with your authority having jurisdiction.

Questions asked

Can I skip the primary-to-secondary test when both winding-to-ground tests pass?

No. The interwinding insulation is a separate barrier stressed by the full primary winding voltage, and it can fail while both winding-to-ground readings pass. On the 3000 kVA example, 13,200 MΩ and 2000 MΩ pass their minimums while the interwinding reading of 191 MΩ sits far below its own minimum of roughly 6,300 to 11,000 MΩ.

Which voltage goes into the formula for the primary-to-secondary minimum?

The primary winding rated voltage: 20,000 V for a delta primary, or 20,000 divided by 1.732, which is 11,547 V for a wye primary. With C of 30 for untanked coils and core and a 3000 kVA rating, that yields about 10,954 MΩ for delta and 6,325 MΩ for wye.

Can a primary-to-ground reading be higher than the primary-to-secondary reading?

Only if the secondary was not actually bonded to ground during that test. With the secondary grounded, the primary-to-secondary path and the primary-to-core path are in parallel, so the combined reading cannot exceed the smaller branch. Verify continuity from the secondary shorting bar to the ground point, then retest.

Does the square root of kVA multiply or divide in the minimum formula?

It divides: Rmin equals C times E, divided by the square root of the kVA rating. For 3000 kVA the divisor is 54.77, so 30 times 20,000 V gives 10,954 MΩ. Writing the term as a multiplication gives tens of millions of megohms and makes every sound transformer look failed.

Keep reading

  • Explainer

    Reverse feeding a step-down transformer on a high leg delta

    Yes — feed the 240 V wye winding from your 240 V 4-wire delta service, leave X0 insulated and floating, take 480 V from the delta and corner ground it. Never tie X0 to the grounded center tap: it applies 0.50 per-unit zero-sequence voltage across windings rated 138.6 V and can circulate 25 per-unit current in a 2% impedance delta.

    Power distribution and transformers

  • Explainer

    When transformer secondary conductors count as taps

    Connecting both MCC feeders inside the transformer's secondary enclosure decides nothing: NEC 240.21(C) in the 2023 NEC governs each run by route, length and termination. With the transformer outside the building, each run may be unlimited in length if it ends in a single breaker or fuse set within its ampacity. Move the transformer indoors and runs past 25 ft fail, so a low-voltage switchgear main at the transformer becomes the path; size conductors from calculated load, never the 2,800 A of MCC bus ratings.

    Power distribution and transformers

  • How-to

    Calculating voltage drop through step-up and step-down transformers

    Yes. A primary voltage drop passes through the turns ratio almost one-for-one in percent — 5% low at 12 kV is 5% low at 480 V — so the study must run every segment from the generator terminals to the farthest branch outlet, combining drops as percentages.

    Power distribution and transformers