Comparison
Written pole motor vs VFD for a single-phase supply
Short answer
For one load on a single-phase service, the line carries about 1.73 times the three-phase current — near 176 A rather than 102 A for an illustrative 50 hp at 240 V. That input current, the DC-bus ripple it causes and whether the drive maker publishes a single-phase rating decide between a written pole motor and a derated VFD with a standard three-phase motor, not horsepower.
On this page
- Why is single-phase current so much higher for the same horsepower?
- What does a written pole motor do that a VFD and standard motor do not?
- Can a large VFD really run on single phase, or only under 3 hp?
- How do I size the VFD and its supply for a 50 hp install?
- Which option handles starting and a weak service better?
- What is the downtime risk with each option?
- So which one should you choose?
- Questions asked
A large single-phase load — the 30 to 75 hp range where dedicated single-phase machines are sold — is decided by line current and DC-bus stress, not by horsepower. For the same shaft power a single-phase line carries about 1.73 times the three-phase current, and that one factor sets the conductor size, the transformer, the rectifier heating and therefore the choice between a written pole motor and a derated VFD with a standard three-phase motor. Both routes work. This article gives you the numbers that separate them and a decision for each case.
Why is single-phase current so much higher for the same horsepower? #
For the same shaft power at the same voltage and power factor, a single-phase line carries √3 — about 1.73 times — the three-phase current, roughly 176 A instead of 102 A for an illustrative 50 hp motor at 240 V. The two relations are:
- Single phase: I = P ÷ (V × PF × η)
- Three phase: I = P ÷ (√3 × V × PF × η)
Worked example — illustrative inputs only, to be replaced with your nameplate and drive data: shaft power 50 hp (37.3 kW), line voltage 240 V, power factor 0.95, combined motor-and-drive efficiency 0.93.
- Single-phase input current = 37,300 W ÷ (240 V × 0.95 × 0.93) = 37,300 ÷ 212 = 176 A
- Three-phase input current = 37,300 ÷ (1.73 × 240 × 0.95 × 0.93) = 102 A
- The same assumptions at 75 hp (55.9 kW): 264 A single phase, 153 A three phase
At these currents the service, the conductors and the upstream transformer become the constraint long before the motor does. The rectifier also conducts the same power in a narrower window: a six-pulse three-phase front end replenishes the DC bus 360 times a second at 60 Hz, a single-phase front end only 120 times a second, so the bus ripple voltage is far larger and the bridge and capacitors run hotter at the same output. That is why purpose-built single-phase-input drives cluster under about 3 hp, where the absolute currents are small and the design accounts for it.
What does a written pole motor do that a VFD and standard motor do not? #
A written pole motor is a single-phase machine that runs synchronously: its start control magnetizes, or writes, the rotor poles during run-up, after which the motor runs straight from the single-phase line with no drive, no rectifier and no DC bus to overheat. The starting control, described in the supplier's literature, limits inrush compared with a direct-on-line induction start of the same size.
The limits are those of any fixed-speed single-phase machine. There is no speed control, so it gives you no energy saving on variable-torque loads such as pumps and fans. Its running current is still single-phase line current, so every service-sizing number in the worked example above applies to it too. And the motor plus its start control is a patented, single-source design, which matters more than any electrical number — that is the next section's subject for downtime and the supplier's literature for the electrical specifics.
Can a large VFD really run on single phase, or only under 3 hp? #
A large drive can run on single phase only where its manufacturer publishes a single-phase input rating or an explicit derating for the exact model — one major drive maker's engineering handbook, for example, documents derating the output current to 50 percent and rules out single phase on SCR-based front ends entirely. Feeding a drive built for three-phase input from two of its three lines pushes the whole load through one rectifier pair at a time, and the elevated ripple and peak current described above overheat the bridge and bus capacitors and shorten their life. Drives marketed for single-phase input under about 3 hp are designed for it; a 30 to 75 hp drive usually is not, and this is where the converter stage caps what a given frame can deliver on single phase — why the converter stage caps single-phase input horsepower walks through that limit in detail.
Treat this as a hard rule of selection: if the manual for the specific model and firmware revision lists no single-phase input rating, single-phase operation is outside the rating. Ask the manufacturer for a written derating or choose a model that publishes one. A rule of thumb is not a rating.
How do I size the VFD and its supply for a 50 hp install? #
Size the installation from the drive's published single-phase input current, never from horsepower: for the illustrative 50 hp case that input current lands near 176 A, and the conductors, fuses, breaker and transformer all follow from that number. De-energize, lock out and verify absence of voltage at the drive terminals before wiring any of it. Then:
- Record the motor nameplate full-load amperes, the voltage and the load's real duty; a variable-torque load running at reduced speed draws far less than nameplate.
- Get the drive maker's single-phase input rating in writing for the exact model and revision. The walkthrough for sizing a VFD for a three-phase motor on single-phase input covers the selection step end to end.
- Calculate the input current with the formula above, using the drive's own efficiency and input data rather than the illustrative values.
- Size the conductors from that current. NFPA 70, the National Electrical Code, 2023 edition, in 430.122(A) requires conductors supplying power conversion equipment to have ampacity at least 125 percent of the equipment's rated input current: 1.25 × 176 A = 220 A, which 4/0 AWG copper at 75 °C (230 A, Table 310.16) covers. Confirm the requirement with your local authority having jurisdiction and the drive manual.
- Fit the input reactor or DC choke the manual calls for on a weak single-phase source; choosing a line reactor or a motor reactor for a VFD separates those two options.
- Check the utility transformer and service capacity against the drive's input kVA plus a starting allowance before ordering equipment.
Which option handles starting and a weak service better? #
The VFD ramps voltage and frequency together, so the motor starts near rated current instead of locked-rotor inrush; a written pole motor also limits starting current against a direct-on-line induction start, but both still draw full single-phase running current once the load is up. The difference shows up at the service during start. An across-the-line 30 to 75 hp start can pull several times running current, sag the line voltage and trip breakers — and a phase converter sized for the running load will not survive that start, which is why a VFD cannot power a whole machine as a phase converter. For the written pole machine, record the starting current and run-up time on the first starts and compare them with the supplier's published data; for the VFD, set the acceleration ramp long enough that the line voltage at the drive terminals stays inside the drive's input window.
What is the downtime risk with each option? #
A written pole motor and its start control come from a single supplier, so a failure can idle the load for that supplier's entire lead time unless you hold a spare, while the VFD route uses an off-the-shelf motor and a drive class you can substitute from any maker with a published single-phase rating. That makes the written pole choice a logistics decision as much as an electrical one: if your site is far from the supplier's warehouse and the load cannot wait, either stock a spare of every size you install or pick the route built from standard parts. Substituting a drive on the VFD path still means matching the published single-phase input rating and redoing the protection sizing — it is a procurement exercise, not an outage.
So which one should you choose? #
Pick the derated VFD and standard three-phase motor when you need speed control, local parts or energy savings on a variable-torque load, and pick the written pole motor when the load is fixed-speed, published single-phase drive ratings stop short of your horsepower, and you can hold a spare. The table compresses the trade:
| Criterion | Written pole motor | Derated VFD + three-phase motor |
|---|---|---|
| Starting current | Limited by its start control, fixed run-up | Near rated current, adjustable ramp |
| Speed control | None | Full range |
| Running line current | Single-phase at full load | Single-phase, per published input rating |
| Energy saving on pumps and fans | None | Yes at reduced speed |
| Parts source | Single supplier | Standard motor, substitutable drive |
| Selection limit | Supplier's horsepower range and lead time | Drive's published single-phase rating |
The decision by case: for a fixed-speed load on an adequate single-phase service with a spare on the shelf, the written pole motor is the simpler machine and the defensible choice. For any load needing speed control, or where the drive maker publishes a single-phase rating covering your horsepower, take the derated VFD and the standard motor. If neither a published single-phase rating nor an acceptable spare strategy exists, extend a three-phase service instead — at the input currents shown above, the supply is the real project either way.
Questions asked
What transformer kVA does a 50 hp single-phase load need?
Single-phase kVA equals line voltage times line current divided by 1000. With the illustrative 240 V figure from the worked example above, that is about 42 kVA before any starting allowance, continuous-load margin or future growth. Order the transformer and confirm the service with the utility using the drive's actual published input current, not a rule of thumb.
Can a rotary phase converter and a standard three-phase motor do this instead?
A converter solves the phase count but not the starting load. A direct-on-line start of a 30 to 75 hp machine can pull several times running current, sag the service and trip the converter or drop out contactors. If you go this way, size the converter for the motor's starting kVA, not its running kVA, and confirm the utility will accept the start.
How do I check the drive after commissioning on single-phase input?
De-energize, lock out and verify absence of voltage before opening any panel or terminal cover. Then, under real load, measure each input line with a true-RMS clamp meter against the drive's published single-phase input rating, watch the DC bus monitor for ripple or undervoltage warnings, and log heatsink temperature across a full duty cycle. A rising trend across repeated runs means the derating was too optimistic, so read the drive's fault history for any recorded codes.
What protects the drive's input on a single-phase service?
Use the fuse or breaker class and ratings the drive manual lists for its input terminals, selected for the drive's published single-phase input current, and keep the panel's short-circuit current rating at or above the available fault current at those terminals. Do not carry over protection sized for the three-phase rating: the single-phase input current is about 73 percent higher for the same load.