20 kV versus 6.6 kV: two transformer configurations compared

Power distribution and transformers Published 10 min read By Current Intel engineering team

Short answer

The direct path wins: two 2000 kVA step-down transformers feeding the LV boards in one transformation lose less power and drop less voltage than any layout that keeps the 6.6 kV stage in series. Keep the four standby units only as the genset-backed second source, and parallel the intermediate-voltage pair only when ratio, vector group and impedance match.

On this page
  1. Read the genset nameplates first
  2. The two layouts side by side
  3. Checking 2 MW at 0.8 PF against one 2000 kVA transformer
  4. Paralleling the two intermediate-voltage transformers
  5. What the second transformation costs
  6. Neutral earthing at the changeovers
  7. Commissioning the first transfer
  8. The decision, case by case
  9. Questions asked

The direct transformation wins. Two 2000 kVA step-down transformers feeding the four 400 V boards in a single step lose less power and drop less voltage than any arrangement that keeps the intermediate stage in series between the grid and the load, so the four standby transformers you already own belong behind the generators as a standby path, not in the utility path. Two checks settle the rest. The generator nameplate voltage decides whether that intermediate layer has a job at all, and a 2 MW design load works out to 2500 kVA at an assumed 0.8 power factor, which no single 2000 kVA transformer can carry. On those numbers, Option 1's four manual changeovers beat Option 2's parallel intermediate-voltage pair on losses, idle losses and switchgear scope, and the parallel pair only works at all when ratio, vector group and impedance match.

Read the genset nameplates first #

Every other choice hangs on one nameplate entry: the generators' rated voltage.

LV-rated generators. Connect them straight to the LV bus the step-down transformers feed. The four standby units then have no function in this plant, because an LV-rated set has no use for that intermediate step-down, and Option 2 becomes two transformations for no benefit. The money already spent on those transformers should not keep a second transformation in the design; redeploy them elsewhere or leave them out of this layout.

6.6 kV generators. They reach the LV boards only through the standby transformers, or through new step-up equipment to the 20 kV connection, which adds hardware rather than removing it. Option 1 then works: each panel changes over between the utility feed and its own generator-fed standby transformer. Option 2 instead makes the intermediate side the backbone for everything.

A priority order that lists the utility feed first, the standby feed second and the generators third only holds together when the generators land on the standby winding. Confirm that topology on the single-line drawing before ordering switchgear.

The two layouts side by side #

Reading Option 1 as you describe it: each utility step-down transformer carries two of the four panels in normal service, and each of those panels changes over to its own standby transformer fed from the generators. If your single line splits the panels differently, the checks below run in the same order.

Point to compare Option 1: two step-down transformers plus four changeovers Option 2: two intermediate-voltage transformers in parallel plus an intermediate bus
Transformations, grid to load one two
Standby-voltage equipment energized in normal service none until the generators run six transformers and the bus, around the clock
Loss of one 20 kV transformer its two panels fall back to their standby sources, generator-dependent the survivor carries the whole bus, capped at its own rating
Second-source transfer four manual break-before-make changeovers, one per panel bus-level switching on the intermediate-voltage gear, fewer operations on higher-voltage equipment
Transformer paralleling none; each unit feeds its own two panels required: matched ratio, vector group, impedance and X/R
Idle losses the four standby cores sit dead while the utility is healthy every core energized, continuous no-load loss
New switchgear scope 20 kV incomers and LV changeovers only adds an intermediate-voltage switchboard and bus to rate, protect and maintain

Option 2 buys fewer switching operations and a stiffer source; Option 1 buys one transformation and lets the whole intermediate-voltage scope sit idle. Option 2 also concentrates risk: both parallel units or the bus itself out of service means all four panels down, where Option 1 fails in halves.

Checking 2 MW at 0.8 PF against one 2000 kVA transformer #

Inputs, and where each comes from:

  • Design load 2 MW: the total rating of the grouped generators the plant was built around, so 2 MW is the load the layout must carry until your panel schedules say otherwise.
  • Load power factor 0.8: an assumption, to be replaced with the measured value from a power-quality logger at the LV boards.
  • Transformer rating 2000 kVA per unit in both options, 0.4 kV line-to-line secondary, three-phase.

The rule in words: apparent power in kVA equals real power in kW divided by the power factor, and the full-load line current of a three-phase transformer equals its kVA rating divided by √3 (1.732) times the line-to-line voltage in kV.

The arithmetic:

  • Apparent power: 2000 kW ÷ 0.8 = 2500 kVA.
  • Load current at 0.4 kV: 2500 ÷ (1.732 × 0.4) = 2500 ÷ 0.6928 = 3609 A.
  • One transformer's full-load current at the LV terminals: 2000 ÷ 0.6928 = 2887 A.
  • Loading ratio: 2500 ÷ 2000 = 1.25, so 125 percent.

The same load seen at the other voltage levels:

Voltage level Full-load current, one 2000 kVA transformer Line current at the 2500 kVA design load
20 kV 57.7 A 72.2 A
6.6 kV 175 A 219 A
0.4 kV 2887 A 3609 A

Result: carrying the whole plant, one transformer runs at 125 percent, 3609 A through a winding rated 2887 A.

Decision: no single transformer carries the full site, so both options are right to split the load across two units, and nothing in either layout may let the whole site land on one, not the one-unit-out case in Option 2 and not a jammed changeover in Option 1. The LV switchboards, busbars and changeover contacts each carry their share of that LV full-load current, and their short-circuit rating must exceed the fault current each transformer can deliver, computed from the impedance on its nameplate and test certificate. The 20 kV incomers follow from the 57.7 A full-load and 72.2 A design figures, sized the way the 2500 A incomer check against a 1600 kVA transformer demonstrates. All of these are estimates from an assumed power factor, so log the real value and recompute before ordering equipment.

Paralleling the two intermediate-voltage transformers #

Option 2 hangs the whole plant on a parallel pair, and paralleled transformers only behave when three nameplate entries match:

  • Same voltage ratio, on the same tap position. A ratio mismatch drives a circulating current between the units even with the bus unloaded, which shows up as current in both transformers at no load.
  • Same vector group, read from the nameplate. Winding arrangements with different phase displacement cannot share a bus at all; a mismatch here ends the paralleling idea before any other check matters.
  • Same percentage impedance on the same kVA base, with a similar X/R ratio. Parallel units split the load in inverse proportion to their impedances, so a lower-impedance unit runs above its share while the other coasts; only matched units divide the load evenly.

Energize both units onto the bus and measure the current in each before hanging load on it: near zero in a well-matched pair, a standing circulating current in a mismatched one.

Plan the one-unit-out case too. When one transformer trips or comes out for maintenance, the survivor carries the entire bus and needs an overload and load-shedding path sized before commissioning, which the guide to calculating paralleled transformers after a phase loss works through step by step.

Decision: if the two nameplates disagree on ratio, vector group or impedance, do not parallel them. Split the intermediate bus into two sections or fall back to Option 1, where the two utility transformers each feed their own panel pair and never tie together.

What the second transformation costs #

Every kVA that crosses two transformers pays twice.

Losses add. Overall efficiency is the product of the two stages' efficiencies, so at the same delivered load the intermediate stage's load loss stacks on the standby units' load loss. Take both figures from the test certificates, not from catalogue typicals, because the certificate carries the measured values the nameplate guarantees.

Voltage regulation adds. Each transformer's under-load voltage drop, set by its impedance and the load's power factor, stacks on the other's, and the combined figure decides whether the far panel still sees its nominal LV voltage inside the tolerance band. Both layouts' transformers carry taps, so re-center them once the real load current is known.

Option 2 also keeps four standby cores energized around the clock, so their no-load loss runs whether or not the generators are turning, a standing burden Option 1 avoids by leaving those cores dead until the utility fails.

The stacked drop matters most when a large motor is started across the line at the far end of the chain with the grid impedance behind it: that case, worked with real numbers, is the motor-starting voltage drop calculation with utility short-circuit capacity.

Decision: on losses and regulation, one transformation beats two at every load point. The intermediate stage in series is a burden the layout pays only when the generators force it to be there.

Neutral earthing at the changeovers #

A changeover that switches only three poles leaves the two source neutrals tied together across the open transfer. That builds a parallel neutral path, lets current circulate through the two transformers' neutral-earth connections, and residual or earth-fault protection then reads that circulating current as a fault. Two arrangements work:

  • Four-pole changeover: each source keeps its own neutral and its own earth link, and only one link is closed at any moment.
  • Three-pole changeover: the neutrals join through a single common earth link both sources share.

Nuisance earth-fault trips are the classic symptom of getting this wrong, the same failure pattern behind nuisance ground-fault tripping on paralleled gensets. Confirm the earth-link scheme with the local authority having jurisdiction and the transformer documentation, then specify four-pole changeovers for Option 1.

Commissioning the first transfer #

Work these checks in order, and let each pass before the next:

  1. De-energize, lock out and verify absence of voltage before opening any board or transformer terminal box. NFPA 70E, the 2024 edition, covers the electrical safe work practices for establishing an electrically safe work condition; confirm what applies on your site with the local authority having jurisdiction.
  2. Interlock each changeover so both sources cannot close together, and prove it: with the first source closed, the second must not move.
  3. Check phase rotation at each 400 V source with a rotation meter; both must read the same sequence before any transfer.
  4. Read each transformer's vector group off the nameplate and record the displacement between the two sources; an open transition needs both LV supplies in phase at the boards.
  5. Energize one utility transformer alone, measure line-to-line voltage at each panel and compare it with the site tolerance band, adjusting taps if the boards sit off-center. Expect a magnetizing inrush several times full-load current at every energization, and read why the 12-times rule only screens transformer inrush current before relying on that estimate.
  6. Load each panel, record its current, and compare it with the feeding transformer's full-load figure from the worked example.
  7. Transfer one panel to its standby source and repeat the voltage and rotation readings.
  8. With the neutral arrangement in place, measure neutral-to-earth current on each source at balanced load; it should read near zero. Compare each standby transformer's energized no-load current with its test certificate, and inspect any unit that draws clearly more than the certificate value before it carries load.

The decision, case by case #

  • LV-rated generators: run the two step-down transformers as the single transformation, land the generators on the LV bus, and take the four standby units out of this plant. Option 2 then buys nothing but a second set of losses.
  • Generators rated at the intermediate voltage, with each panel's standby load within its standby transformer's nameplate rating: Option 1. Two utility transformers feeding panel pairs, four-pole manual break-before-make changeovers, and the generators behind their transformers as the second source. One transformation in normal service, no paralleling, and no intermediate-voltage switchboard to buy, protect and keep energized.
  • Option 2 only when the plan genuinely needs all four standby transformers in continuous service behind one common bus, and then only with a matched pair: identical ratio and tap position, same vector group, matched impedance and X/R ratio, intermediate-voltage switchgear rated for the parallel fault contribution, and a shed-load plan ready for the one-unit-out case, when the bus is capped at the survivor's rating.

Whichever branch you take, the loading rule from the worked example holds: the design load exceeds what one transformer can carry, so the layout must keep the load split across two units in every normal and standby condition.

Questions asked

Can the four standby transformers be back-fed from their LV side if that helps the layout?

Some two-winding transformers tolerate energization from either winding, but back-feeding moves the magnetizing inrush and the protection duty to the winding built as the secondary, and the taps may not give the expected adjustment in reverse. Build a layout around back-feeding only if the manufacturer's documentation for those specific units permits it, and rework the protection settings for the reversed direction.

Do the generators need synchronizing equipment in Option 1?

No. Each panel transfers with a break-before-make changeover, so the generator-fed source never closes in parallel with the 20 kV feed and there is nothing to synchronize; phase rotation must match, but the sources never run tied together. Synchronizing gear, governor and voltage matching enter only if you later want the generators to run in parallel with each other or with the grid.

What happens to the site in Option 2 if one intermediate-voltage transformer trips?

The survivor holds the bus alone at its 2000 kVA rating. At the assumed 0.8 power factor that is 1.6 MW, so roughly 0.4 MW of the 2 MW design load must be shed until the second unit returns. In Option 1 the equivalent failure drops only two panels onto their generator-backed transformers, a smaller and more local event.

Which figures set the ratings of the new switchgear?

Continuous ratings come from the worked example: 57.7 A full-load at 20 kV, 175 A at the intermediate voltage and 2887 A at the LV side for each transformer, scaled by your real design load. Short-circuit ratings come from the transformer's impedance: divide its rated secondary current by the impedance fraction on the nameplate and test certificate, add motor and generator contributions, and rate the switchboard above the result.

Is the 0.8 power factor assumption worth refining?

Yes, because every kVA figure in the comparison scales with it. Measure the power factor at the 400 V boards with a power-quality logger under normal production load. If the plant measures 0.9 instead, the design load works out to 2222 kVA, still above one transformer's rating but with a thinner margin; if it measures lower than assumed, the overload on a single unit gets worse.

Keep reading

  • Selection guide

    Replacing a 45 kVA 12 kV pole-mount three-phase transformer

    Order a 12.47 kV-class three-phase pole-mount and run it on its 2.5% below-rated tap: that holds the secondary about 1.3% low at a typical measured bus. If your reading sits lower, use the 5% tap, or build the bank from three 15 kVA 7200/12470Y-120/240 V single-phase units in wye at 125 A per phase.

    Power distribution and transformers

  • Selection guide

    Sizing a 22/6.6 kV transformer for sequential motor starts

    The 3,500 kW recycle-air compressor's 1,737 A start is about 19.9 MVA, which dips a 7% transformer's secondary roughly 9.3% at 15 MVA, 8.2% at 17 MVA and 7.0% at 20 MVA. With the two running air compressors and the IEC 60076 impedance tolerance counted, only the 20 MVA rating stays inside a 10% ceiling, so that is the unit to specify.

    Power distribution and transformers

  • How-to

    Transformer sizing from the highest leg current on a panel

    Size the transformer from the highest recorded leg current, never the sum of the legs: 240 V x 50 A is a 12 kVA load, the 1.25 continuous factor points at a 15 kVA standard unit, and the panel main becomes 80 A. First measure line-to-line, because about 240 V confirms a single-phase source while about 208 V means two legs of a wye and a different transformer.