Explainer
Bus fault current vs arcing current in an arc flash study
Short answer
Bus fault current is the available short-circuit current at the bus with a bolted fault; it is the input the IEEE 1584-2018 model uses to compute the arcing current. The arcing current is what actually flows through the arc, usually well below the bolted value at 480 V, and the clearing time read at that arcing current, not at the bolted value, is what drives the incident energy.

On this page
- Bus fault current: the available short-circuit current
- Arcing current: what actually flows through the arc
- Why the clearing time must be read at the arcing current
- Worked example: clearing time on a 480 V bus at 30 kA bolted and 21 kA arcing
- The three quantities side by side
- Checking the report before you trust the number
- Questions asked
Bus fault current and bus arcing current describe two different faults, and each does a different job in an arc flash study. Bus fault current is the available short-circuit current at the bus for a bolted, zero-impedance fault — the value the short-circuit study produces. Bus arcing current is what the IEEE 1584-2018 model predicts will actually flow through the arc, computed from that bolted value, and at 480 V it usually sits well below it. The bolted current feeds the model; the arcing current, paired with the protective-device clearing time read at that current, is what produces the incident energy. The classic mistake is reading the clearing time at the bolted current, and it makes a hazardous bus look tame.
Bus fault current: the available short-circuit current #
Bus fault current is the current the sources can deliver through a fault assumed to have zero impedance — conductors bolted solid across the three phases. No arc enters that calculation. The fault path holds only source impedances, transformer and conductor impedances, and the rotating-machine contribution, which is why the value comes straight out of the short-circuit study for each bus and each operating mode. Reports sometimes call it the available fault current at the bus; how that figure relates to a transformer's secondary short-circuit current is its own comparison, covered in available fault current vs secondary short-circuit current.
IEEE 1584-2018, the Guide for Performing Arc-Flash Hazard Calculations, builds its process on this value: collect the system and installation data, determine the modes of operation, determine the bolted fault currents — only then does the arcing-current calculation run. The bolted current is a major input to the arcing-current equation, not the fault current an arc itself sees.
It also carries a job the arc-flash study does not use: equipment duty. Breaker and fuse interrupting ratings are checked against the bolted current at the point of installation, a separate check from everything below.
Arcing current: what actually flows through the arc #
An arcing fault is not a bolted connection. The arc is a column of ionized gas with its own voltage drop, so it adds resistance in series with the fault path and pulls the current down. At 480 V the effect is strong: the arcing current typically lands well below the bolted value, because the arc's resistance takes a large share of the total impedance in a low-voltage fault path.
IEEE 1584-2018 supplies the models and the analytical process that turn bus data into a predicted incident energy and an arc-flash boundary. The arcing-current equation takes the bolted fault current as its major input and adjusts for what the arc will see at that bus: the system voltage, the electrode gap between the conductors, and the enclosure configuration around them. That is why the workflow collects system data, fixes the operating modes and determines the bolted currents before it computes anything; how the arcing current is calculated from the maximum bolted fault current works the equation through step by step.
The 2018 model is documented for three-phase systems from 208 V to 15 kV at 50 or 60 Hz. The previous edition let engineers set aside equipment below 240 V unless it was fed through at least one 125 kVA or larger low-impedance transformer; the 2018 edition removed that exclusion, so a 208 V panel is calculated like any other bus.
Drop one assumption immediately: the arc does not always lower the current. At high bolted currents and tight electrode gaps the equations can return an arcing current above the bolted input — why IEEE 1584 arcing current can exceed the bolted fault current covers when that happens and what it does to the report.
Why the clearing time must be read at the arcing current #
Incident energy is arc power multiplied by time, and the time that counts is how long the protective device lets the arc burn. That response has to be read at the arcing current, because a device does not answer both currents the same way. A feeder breaker whose instantaneous pickup sits above the arcing current snaps a bolted fault open in its instantaneous band, while the same fault through an arc falls below pickup and rides the short-time delay. Same bus, same breaker, two different clearing times — and only the second one belongs in the energy calculation.
That pairing is the step most often fumbled, enough that clearing time is based on the arcing current, not the bolted current fills a page of its own. Which device clears is not always obvious either: in a motor control centre, the upstream device that actually interrupts sets the duration, and which breaker sets MCC arc flash duration walks through that selection.
This is also why the study order matters. Run the short-circuit study and the coordination study first, then the arc-flash run, so the calculation consumes a real bolted current and device response times taken from the actual settings files.
Worked example: clearing time on a 480 V bus at 30 kA bolted and 21 kA arcing #
Every figure here is an illustrative study value chosen to show the reading order — not results from a particular installation. The bus is 480 V, three-phase, 60 Hz. The short-circuit study reports a bolted three-phase fault current of 30 kA for this operating mode. The arc-flash run reports an arcing current of 21 kA, about 70 percent of the bolted value and typical of where a 480 V arc lands. The feeder breaker's instantaneous pickup is set at 24 kA. Read from the device's time-current curve, the clearing time at the bolted current is 0.02 s in the instantaneous band; at the arcing current the device falls below pickup and clears in 0.20 s on its short-time delay.
Hold the electrode gap, enclosure and working distance fixed, and the only moving parts are the two currents and the two times. At those fixed conditions, incident energy rises in near proportion to arcing current multiplied by clearing time — a first-order read of the model, whose arc power tracks the arcing current over this range.
Read the way the study requires: 21 kA × 0.20 s = 4.2 kA·s. Read the wrong way, at the bolted current: 30 kA × 0.02 s = 0.6 kA·s. The ratio between them is 4.2 ÷ 0.6 = 7.0.
Taking the clearing time at the bolted current would understate this example's incident energy by a factor of 7 — an estimate, since converting the product into cal/cm² needs the model's full gap, enclosure and distance inputs. The decision follows: read the clearing time at every current the arc-flash run reports, and treat an arcing current below the instantaneous pickup as the trigger to expect a long clearing time and re-check the energy. The incident energy a real run produces sets the arc-flash boundary and the PPE category under NFPA 70E, 2024 edition — confirm the enforced edition with the authority having jurisdiction and the equipment documentation, and de-energize and verify absence of voltage wherever the work allows it.
The three quantities side by side #
| Quantity | What it measures | Where the study uses it |
|---|---|---|
| Bus fault current | Available three-phase short-circuit current through a zero-impedance fault | Input to the arcing-current equation; basis for interrupting-duty checks |
| Bus arcing current | Modeled current through the arc at that bus | Sets the current at which the device's clearing time is read |
| Clearing time at the arcing current | Device response time at the modeled arc current | Multiplies the arc power in the incident-energy result |
Checking the report before you trust the number #
- All three readings come from the same bus, the same fault type and the same operating mode; a mode mismatch between the short-circuit run and the arc-flash run is the classic silent error.
- Compare the two currents as a sanity check — at this voltage class, expect the arcing value below the bolted one, but read what the model reports rather than applying a ratio.
- Keep the gap, enclosure configuration and working distance on file with the result; the incident energy cannot be reproduced without them.
- Record the currents, the clearing time and the mode together so the next engineer can audit the run without rebuilding it.
- Re-run the sequence for each operating mode the system can present, and carry the worst case into the field documentation.
Get those five right and the incident energy traces cleanly from bus data to PPE label — which is the whole point of keeping the two currents straight.
Questions asked
Is the arcing current a fixed share of the bolted fault current?
No, and no fixed percentage substitutes for the calculation. The 2002 edition ran a second case at 85 percent of the arcing current; the 2018 edition instead computes a median arcing current and applies a variation correction factor to bracket the range. Read the device response at each current the report lists. A rough ratio between the two currents is a sanity check, never the result.
Do breaker and fuse duty checks use the arcing current?
No. Interrupting ratings and a panel's short-circuit current rating are checked against the bolted short-circuit current at the point of installation, with whatever asymmetry adjustments the applicable standard calls for. The arcing current exists only for the arc-flash model. Keep the two checks separate: a bus with comfortable interrupting margin at the bolted value can still carry a severe arc-flash result, because the device cleared slowly at the lower arcing current.
What inputs does the arcing-current calculation need besides the bolted fault current?
System voltage, the electrode gap between the conductors at the bus, the enclosure or box configuration around them, and the working distance. The 2018 guide provides tables of typical gaps and box types by equipment class, and study software fills them from the equipment record you build. A different gap or box type moves the arcing current and the incident energy with it, so copy the values from the actual equipment whenever the data exists.
Does a change in the utility source or switching state change the arcing current?
Yes. Every source configuration and switching state changes the bolted fault current at the bus, and that value is a major input to the arcing-current equation. The 2018 process identifies the system's modes of operation early, and the arc-flash result is reported per mode. Run the short-circuit and coordination cases for each mode before accepting any single incident-energy number for the bus.
Does the arc-flash boundary come from the same calculation?
Yes. The 2018 guide computes it from the same arcing current and clearing time as the incident energy, with the boundary set where the incident energy falls to 1.2 cal/cm2, roughly the onset of a second-degree burn. A slow clearing time pushes the boundary outward just as it raises the energy, so both numbers move together and both belong to one bus and one operating mode.