Comparison
Fixed-current vs motor-impedance motor starting dip
Short answer
The fixed-current formula, dip = LRA × (R cosθ + X sinθ), holds locked-rotor current at its full-voltage value, while the divider method, dip = 1 − |Zm ÷ (Zs + Zm)|, lets the current fall as the motor voltage sags — so the divider always gives the smaller dip. Keep the divider result for motor-terminal and flicker work and treat the fixed-current result as a conservative upper bound.

On this page
The two methods model the same series circuit — upstream impedance feeding a locked-rotor motor — and they disagree for one reason: the fixed-current formula holds the motor's locked-rotor amperes at the full-voltage value, while the voltage divider lets that current fall as the motor voltage sags. The divider is the self-consistent model; the fixed-current result is a conservative upper bound that overstates the dip by roughly the size of the dip itself. On a 500 kVA start through a 1000 kVA transformer the two give 5.1% and 4.9%; on a weak source the gap stretches to several points. What follows fixes the observation point, puts every impedance on one base, runs both calculations on real numbers, and says which result to keep.
Two methods, one circuit #
Both methods push one current through one chain of impedance, so nothing differs except the current model. The fixed-current method imposes the motor's locked-rotor amperes on the upstream R + jX and multiplies. The divider method replaces the motor with its locked-rotor impedance and solves the whole circuit at once, so terminal voltage and current come out together.
| Fixed-current formula | Motor-impedance divider | |
|---|---|---|
| Current model | Locked-rotor current held at the full-voltage value | Current follows the total impedance and falls as the motor sags |
| Inputs | Locked-rotor current, starting power factor, upstream R and X | Zs (utility, transformer, cable) and Zm from the starting kVA |
| Motor impedance | Left out; adding it would double-count the motor | It is the load |
| Result | Upper bound that overstates by about the dip itself | Self-consistent; Kirchhoff's voltage law closes |
| Best use | Quick screen on a stiff source | Motor-terminal dip, weak sources, flicker studies |
Mark the infinite bus and the observation point #
The infinite bus is a definition, not something you find on a drawing: the point held at constant voltage, and it must sit upstream of every impedance in the calculation. With a service transformer, put it at the primary and let the transformer impedance carry the utility's share, or move it further back and add the utility contribution explicitly. Never report a dip at the infinite bus — by definition it does not move.
The observation point decides what belongs in Zs, the upstream impedance:
- Motor terminals: utility, transformer and cable — the dip the motor's starting torque actually sees.
- Transformer secondary bus: utility and transformer only — the dip every other load on that bus rides through.
- Point of common coupling: everything up to the utility connection — the number a flicker requirement applies to.
Switching the observation point moves the answer further than switching methods does, so mark both points on the one-line diagram before any arithmetic.
One base for every impedance #
Work in ohms or in per-unit, never mixed, and never add nameplate percent impedances that sit on different kVA bases. The convenient base for motor starting is 100 kVA, because the motor's locked-rotor impedance on that base is Zm = 100 ÷ kVA_start — the classic manual form %Zm = 10,000 ÷ kVA_start. A 500 kVA start is 0.20 per-unit, or 20%.
The starting kVA comes from the motor data: for three-phase line current, kVA_start = √3 × V_LL × LRA ÷ 1000; for single-phase, kVA_start = V × LRA ÷ 1000 — check which current the data quote. The other elements convert exactly as in a transformer secondary fault current calculation in per-unit: transformer impedance scales by base kVA ÷ transformer kVA, the utility enters through its available fault capacity, and cable values come from the conductor tables of NFPA 70, the National Electrical Code, 2023 edition (Chapter 9, Tables 8 and 9) for the installed size and raceway.
Add resistance and reactance separately and take the magnitude last: |Z| = √(R² + X²).
The fixed-current formula #
With LRA taken at the calculation voltage, θ the locked-rotor power-factor angle, and R + jX the total impedance ahead of the motor:
ΔV = LRA × (R cosθ + X sinθ)
dip = ΔV ÷ V_phase
Two habits keep it honest. R and X must be the whole upstream chain — a cable-only sum quietly drops the transformer, the largest term on most services. And the motor impedance stays out of the circuit: LRA already represents the motor, so adding Zm counts it twice. The starting power factor is a soft input — sinθ stays close to one while R is small, so a modest error there barely moves the answer; use the manufacturer's value when the data sheet gives one.
Holding the full-voltage LRA is exactly what makes the method conservative: it assumes the motor keeps drawing full locked-rotor current after its own terminals have sagged.
The motor-impedance divider #
Treat the locked rotor as an impedance and solve the circuit with the source at 1.0 per-unit:
I_start = V_source ÷ (Zs + Zm)
V_motor = I_start × Zm = Zm ÷ (Zs + Zm)
dip = 1 − |V_motor|
Zs and Zm add as complex quantities — (Rs + Rm) + j(Xs + Xm). Replacing that with a root-sum-square of the two magnitudes discards the cross terms and changes the answer; the other classic slip is building the divider between the cable and the transformer, which treats the cable as the load. The motor is the load: Zm is the second term in the denominator, and Zs is everything upstream.
Before believing the number, check Kirchhoff's voltage law in rectangular form: the drop across Zs plus the drop across Zm must rebuild the source voltage, real and imaginary parts separately.
Worked example: a 500 kVA start on a 1000 kVA transformer #
Every input below is illustrative — substitute your transformer impedance, your cable table values and your motor data.
- 480 V bus, observation at the motor terminals, infinite bus at the transformer primary.
- Transformer: 1000 kVA, 5.75% nameplate impedance, X/R of 6 — per phase |Zt| = 0.0575 × 480² ÷ 1,000,000 = 0.0132 Ω, split Rt = 0.0022 Ω and Xt = 0.0131 Ω.
- Cable: 200 ft of 4/0 AWG copper in steel conduit — Rc = 0.0122 Ω (0.0608 Ω per 1000 ft, uncoated copper at 75 °C, Table 8) and Xc = 0.0080 Ω (0.040 Ω per 1000 ft, near the Table 9 reactance for this size in magnetic conduit — take the entry for your raceway).
- Motor: 500 kVA starting load at 480 V, locked-rotor power factor 0.20 — LRA = 500,000 ÷ (√3 × 480) = 601 A; on the 100 kVA base, Zm = 100 ÷ 500 = 0.20 per-unit; the base impedance is 480² ÷ 100,000 = 2.304 Ω, so Zm = 0.20 × 2.304 = 0.4608 Ω, split Rm = 0.0922 Ω and Xm = 0.4515 Ω.
Upstream sum: Rs = 0.0022 + 0.0122 = 0.0144 Ω and Xs = 0.0131 + 0.0080 = 0.0211 Ω. Phase voltage: 480 ÷ √3 = 277.1 V.
Fixed-current pass #
R cosθ + X sinθ = 0.0144 × 0.20 + 0.0211 × 0.980 = 0.00288 + 0.02068 = 0.0236 Ω.
ΔV = 601 × 0.0236 = 14.2 V, so the dip is 14.2 ÷ 277.1 = 0.051 — 5.1% at the motor terminals.
Divider pass #
Zs + Zm = (0.0144 + 0.0922) + j(0.0211 + 0.4515) = 0.1066 + j0.4726 Ω, with magnitude √(0.1066² + 0.4726²) = 0.4845 Ω.
I_start = 277.1 ÷ 0.4845 = 572 A. V_motor = 572 × 0.4608 = 263.6 V, so the dip is 1 − 263.6 ÷ 277.1 = 0.049 — 4.9%.
Check Kirchhoff: 572 × (0.0144 + j0.0211) = 8.2 + j12.1 V, and 572 × (0.0922 + j0.4515) = 52.7 + j258.3 V; the sum, 60.9 + j270.4 V, has magnitude 277.1 V and closes against the source. Notice the current: 572 ÷ 601 = 0.95, so the divider current fell to the motor's terminal-voltage fraction — that single feedback is the entire difference between the methods.
The same start at the transformer secondary #
Loads on the secondary bus see |Zcable + Zm| ÷ |Zs + Zm| = 0.4712 ÷ 0.4845 = 0.973, a 2.7% dip — barely half the motor-terminal figure, on the identical start.
Why the divider reads lower #
The fixed-current formula bills full-voltage current to a circuit whose voltage has already dropped. The divider closes that loop: the terminal sag cuts the locked-rotor current by the same fraction, which shrinks the drop that caused it. In scalar form, the divider dip ≈ the fixed-current dip ÷ (1 + the fixed-current dip): 5.1% maps to 4.85% (the phasor-exact answer here is 4.9%), and a 20% fixed-current dip on a weak source maps to 16.7%. The gap is the model, not an arithmetic slip, and it widens as the source softens.
| What you see | Likely cause | Correction |
|---|---|---|
| Divider a few points below the fixed-current result | Current falls with terminal voltage | Expected — keep the divider number |
| Fixed-current dip suspiciously small | Transformer or utility impedance left out | Rebuild Zs from the infinite bus downstream |
| Divider answer jumps when impedances are combined | Magnitudes root-sum-squared instead of R and X added | Add components first, take the magnitude last |
| Divider built between cable and transformer | Motor left out; cable treated as the load | Zm is the load; Zs is the whole upstream |
| Two studies of one start disagree | Different observation points or bases | Compare the same bus on the same base |
Which number to keep #
- Motor-terminal dip, starting-torque checks, weak or generator-fed sources: the divider, every time. Whether that dip is tolerable is a separate question — what decides acceptable voltage drop for MV motor starts covers the limits side.
- Flicker at the point of common coupling: the divider with Zs taken up to that point. One start produces a dip; flicker, the repeated fluctuation that limits address, comes from frequent starts and cyclic loads. IEC 61000-3-3:2013 with Amendment 1:2017 limits voltage changes and flicker for equipment rated up to 16 A per phase on public low-voltage networks, so it does not govern a several-hundred-kVA motor; that start is judged against the utility's flicker requirement at the connection point, which you confirm with the utility or the authority having jurisdiction.
- A quick screen on a stiff service: the fixed-current formula is fine — it is the idea behind estimating voltage sag from motor inrush current. Its overstatement is roughly the square of the dip, so under a 5% dip the two methods sit within a quarter of a point; take it as an upper bound and move on.
- Never both in one circuit: LRA as a fixed current plus Zm as an element double-counts the motor.
Confirm it on the start #
At commissioning, capture the minimum RMS voltage and the current at the same observation point the calculation used — a power-quality recorder with cycle-by-cycle capture, or existing metering on the circuit's current transformers — and compare the reading with the divider prediction, with the fixed-current figure as the bound. Opening an energized panel to make that connection is not part of this check: follow NFPA 70E, 2024 edition, and your site's electrical safety program, and de-energize and verify absence of voltage before opening a panel.
Questions asked
I only have the motor's full-load current. What locked-rotor current can I screen with?
Only a first screen: a NEMA design B induction motor commonly draws six to eight times its full-load current with the rotor locked, so a 124 A motor screens between roughly 740 A and 990 A. Before committing a transformer size or a flicker number, replace the range with the nameplate locked-rotor current or the value from the NEC motor tables (NFPA 70, 2023 edition, Article 430).
The utility gave me available fault current, not impedance. How do I put it in series?
Convert it on the chosen base: the utility impedance equals the base kVA divided by the utility's three-phase fault kVA at that point. A 50 MVA fault capacity becomes 0.002 on a 100 kVA base (100 divided by 50,000), a negligible term on a stiff service but the deciding one on a weak feeder. Add it ahead of the transformer's per-unit impedance and run either method unchanged.
Does the divider method work for a soft starter or a wye-delta start?
Yes, with the reduced starting load in place of the across-the-line value. A wye-delta start draws about one-third of the line current while in wye, and a soft starter's current depends on its voltage setting; convert the reduced current at the actual terminal voltage to a starting kVA, rebuild the motor impedance from it, and the divider returns the dip for that part of the start. The fixed-current formula works the same way with the reduced current.
My measured dip is smaller than both calculations. Why?
The locked-rotor model describes the worst instant of the start; as the motor accelerates its effective impedance rises, so the minimum voltage lasts only the first cycles, and a meter averaging over a long window under-reads it. Capture the minimum with a cycle-by-cycle RMS recorder. Then confirm the observation point: a reading at the transformer secondary bus is naturally smaller than the motor-terminal prediction.