Multi-ratio current transformer nameplate: four cores, one unit

Protection: breakers, fuses and SCCR Published 7 min read By Current Intel engineering team

Short answer

The notation 3000/2500/2200/1000-5-5-5-5 names one current transformer assembly with four separate 5 A secondary cores, each a multi-ratio tapped winding, not four different CT types. Land each core only at its selected tap pair per IEEE C57.13, short every unused core across its full winding, and read the accuracy class at the tap actually wired.

On this page
  1. What each part of the notation covers
  2. The standard tap table for a 3000:5 core
  3. How the accuracy class follows the tap
  4. Worked example: a 900 A feeder on the largest core
  5. Shorting rules for spare cores and spare taps
  6. Checks before the feeder returns to service
  7. Questions asked

The string 3000/2500/2200/1000-5-5-5-5 on a specification or a nameplate is one current transformer assembly with four separate secondary cores, each wound for a 5 A secondary and each carrying its own multi-ratio taps — not four transformer types, and not four coils sharing one winding. IEEE C57.13-2016 defines a multi-ratio CT as one that reaches three or more ratios through taps on the secondary, and the slash list simply gives this assembly's four full-winding primary ratios. The cores may sit in one housing or as separate units stacked on the same conductor or bushing; electrically they stay separate circuits. Land each core only at the tap pair you select, leave the unused taps of a working core alone, short every unused core across its full winding, and read the accuracy class at the tap actually wired, because that class falls with the turns in use.

What each part of the notation covers #

Read the string in two halves. The slash list gives the four cores' full-winding primary ratios: 3000:5, 2500:5, 2200:5 and 1000:5. The trailing 5-5-5-5 lists one 5 A secondary rating per winding, and by the letter of the standards that count is the core count — four 5s, four cores. Writing the ratio list with slashes follows CSA practice; an IEEE drawing calls the same hardware a multi-ratio core and prints its designation on the nameplate.

The four secondaries share the primary conductor and nothing else, so treat them as four circuits for isolation, testing and burden accounting. IEEE-drawn diagrams label them X1-X5, Y1-Y5, Z1-Z5 and W1-W5; IEC-style diagrams mark the same windings 1S1 through 1S5, 2S1 through 2S5, and so on. Take core identity from the printed terminal marks, never from a winding's position in the stack.

The standard tap table for a 3000:5 core #

IEEE C57.13-2016, Table 11 tabulates the standard multi-ratio taps for cores from 600:5 through 5000:5. For this assembly's largest core the schedule is:

Ratio Secondary terminals
300:5 X3-X4
500:5 X4-X5
800:5 X3-X5
1000:5 X1-X2
1200:5 X2-X3
1500:5 X2-X4
2000:5 X2-X5
2200:5 X1-X3
2500:5 X1-X4
3000:5 X1-X5

The pairs are sections of one 600-turn winding: X4-X5 is the outer 100 turns, X3-X4 adds the next 60, X1-X2 covers 200 turns, and X1-X5 spans all 600 to give the full ratio. For this particular listing the tap pairs come out the same under either standard; a few other ratios differ slightly between CSA and IEEE tables, so wire each core from its own printed schedule, never by analogy from this table.

How the accuracy class follows the tap #

Each core carries its own accuracy line on the nameplate, and the four rarely match: a metering core might show a 0.3 metering class tied to a lettered burden such as B0.2, while the protection cores show C classes. Read the line printed for the core you are wiring.

A C rating fixes a voltage capability. C200 on the full winding means the core holds its ratio accuracy into any burden up to the resistance that develops 200 V at 20 times the rated secondary — 100 A — so 2 ohms. The rating belongs to the full winding: a tap puts fewer turns to work and the capability falls roughly with those turns. Half the turns, half the volts: the same core behaves about like C100 at its 1500:5 tap. Take that scaling as an estimate and use the manufacturer's per-tap data for the installed unit.

Count the whole circuit in the burden: the winding itself, the leads and every device input. The nameplate VA figure is not the winding resistance — CT nameplate VA versus measured winding resistance explains the difference when you budget from the VA line.

Worked example: a 900 A feeder on the largest core #

Inputs for this example (illustrative, not a nameplate): feeder maximum load 900 A; the relay sits on the 3000:5 core, whose nameplate reads C200 at the full winding; the relay input measures 0.20 ohms, the test switch 0.02 ohms and the secondary leads 0.30 ohms; the meter goes on the 1000:5 core.

Pick the ratio one step above the load: the 1200:5 tap, terminals X2-X3. At the design load the relay sees 900 A × 5 ÷ 1200 = 3.75 A. Land that pair and set the relay's ratio to the tap.

Landing the wrong pair is worth quantifying. Left on the full winding, that primary current gives 900 A × 5 ÷ 3000 = 1.5 A, so the relay reads 1.5 A instead of 3.75 A — 60 percent low — and every pickup calculated against real amperes is off by the same factor.

Budget the accuracy at the wired tap: it uses 1200 of the 3000 effective turns, so the voltage capability is about 0.4 × 200 V = 80 V at 20 × 5 A = 100 A, a burden limit of 80 V ÷ 100 A = 0.8 ohms. The connected burden totals 0.20 + 0.02 + 0.30 = 0.52 ohms, under that limit, so the relay holds ratio accuracy up to 20 times its rated secondary.

The meter core needs no tap: across its full winding, 900 A × 5 ÷ 1000 = 4.5 A, close to rated secondary, which is where a metering core belongs.

Decision: relay on the largest core at X2-X3 with its ratio set to the tap and a 0.52 ohm burden against the 0.8 ohm budget; meter on the 1000:5 core's full winding; the 2500:5 and 2200:5 cores stay spare, shorted across their full windings until assigned.

Shorting rules for spare cores and spare taps #

An energized CT must never run into an open secondary: with its burden gone, the winding can build a voltage high enough to break down insulation and injure anyone at the terminals, and every rule below follows from that hazard.

  • Spare core: short it across its full winding at the designated end terminals (X1 to X5 on an X-labeled core) at the CT shorting block or terminal strip, and leave the short in place until the core is assigned to a device.
  • Working core on an intermediate tap, say X2 and X4: land only that pair and leave the core's remaining taps open. Bridging the leftover terminals shorts part of an energized winding, distorts the ratio the device sees and can drive circulating current between sections.
  • Moving a device: take the primary circuit out of service, lock out and verify absence of voltage before the secondary is opened at the block. Safe electrical work practices, including that voltage-verification step, are covered by NFPA 70E, 2024 edition; confirm the job's requirements with the authority having jurisdiction and the equipment documentation. If no outage can be taken, the plant's written energized-work procedure governs every step and the protective equipment it requires, and the sequence does not change: short through the block first, move the leads second, and lift the short only once the new circuit is proven continuous.

Checks before the feeder returns to service #

Walk the as-left wiring against the drawing terminal by terminal: each device on its assigned core, the selected pair landed on each, polarity consistent. X1 — 1S1 on an IEC-marked winding — is the polarity terminal, and a reversed pair corrupts differential and directional protection and skews watt and var metering.

Prove continuity with the circuit isolated, using test methods gentle enough for meter and relay inputs. A ratio test closes the commissioning: inject a known primary current, read both sides and compare with the wired ratio — checking a transformer protection CT's ratio by injection walks one example. Before any core is condemned on a bushing-mounted assembly, read why a bushing CT ratio test can read high.

Back in service, compare every reading with the ratio wired: at full load the relay must show 3.75 A and the meter 4.5 A. A relay showing 1.5 A means the tap still sits on the full winding — correct the wiring before touching a single setting.

Questions asked

What does the C number in a protection core's rating actually guarantee?

Under IEEE C57.13, the number after C is the secondary voltage the core supports across its burden at 20 times rated secondary current. For a 5 A winding that current is 100 A, so the burden limit in ohms is simply the class number divided by 100: C200 carries 2 ohms, C100 carries 1 ohm, with ratio error held within 10 percent. The capability belongs to the winding in circuit, so read it at the wired tap.

Can a meter and a relay share one core?

Yes, by wiring their current circuits in series so the same secondary current passes through both, provided the combined burden stays within the wired tap's rating. Add the ohms of every device, the test switch and the leads, then compare the sum with the tap's voltage capability divided by 100 A. Never parallel two secondaries or bridge two different cores: unequal ratios drive circulating current between them and corrupt both readings.

May a CT secondary sit open while the primary is de-energized?

The hazard comes from primary current, so an open secondary is harmless while the primary is locked out and absence of voltage is verified. Close the short again before primary-injection testing and before the feeder returns to service, because the first load current through an open winding strikes the dangerous voltage. Verify the absence of voltage yourself; do not accept someone else's open breaker as proof.

How do I identify the wired tap when the drawing is missing?

Isolate, lock out and verify absence of voltage, disconnect the burden, then run a ratio test: inject a known primary current and read the secondary. A measured ratio near 240 to 1 identifies the 1200:5 tap; near 600 to 1, the full 3000:5 winding. Record the found pair on a fresh as-left drawing so the next crew does not repeat the hunt.

Keep reading

  • Explainer

    Why a 50:5 zero-sequence CT fits an 800 A motor

    Keep the 50:5 zero-sequence CT. Balanced phase currents cancel in the window, so the ratio never follows the 800 A motor full-load current; it follows the ground-fault current the 25 A resistor permits, the relay's secondary pickup, and the practical floor for a window-type CT, which sits near 50:5.

    Protection: breakers, fuses and SCCR

  • Explainer

    What an ext. 100% marking means on a current transformer

    Ext. 100% on a CT nameplate is a continuous thermal current rating factor of 1.0 under IEEE C57.13: the CT carries its rated primary current continuously at the stated ambient and nothing above it. The short-time and emergency ratings are separate, time-limited values, so the deciding quantity for a load is the permitted continuous primary current at the specified ambient and accuracy class.

    Protection: breakers, fuses and SCCR

  • How-to

    Why CT nameplate VA is not the secondary winding resistance

    The VA on a CT nameplate is the permitted secondary burden, not the copper resistance of the winding, which is usually below 0.1 ohm. Measure it with a four-wire milliohmmeter at the terminals, or inject DC and divide the terminal voltage by the current; a two-wire multimeter mostly reads its own leads.

    Protection: breakers, fuses and SCCR