Current IntelPower LibraryShop main store

How-to

Why CT nameplate VA is not the secondary winding resistance

Protection: breakers, fuses and SCCR Published 6 min read By Current Intel engineering team

Short answer

The VA on a CT nameplate is the permitted secondary burden, not the copper resistance of the winding, which is usually below 0.1 ohm. Measure it with a four-wire milliohmmeter at the terminals, or inject DC and divide the terminal voltage by the current; a two-wire multimeter mostly reads its own leads.

On this page
  1. The nameplate VA fixes a burden, not the copper
  2. Short and isolate the secondary first
  3. Measure with a four-wire milliohmmeter
  4. Fall back on terminal voltage over current
  5. What the winding resistance is used for
  6. Worked example on a 15 VA, 5 A secondary
  7. The decision for each case
  8. Questions asked

The VA figure on a CT nameplate is the permitted burden: the apparent power the secondary may deliver into its connected load at rated secondary current. It is not the DC resistance of the secondary winding, which is usually well below 0.1 Ω. To get the real winding resistance at site, measure it with a four-wire (Kelvin) milliohmmeter, or inject a known DC current and divide the voltage read directly at the CT terminals by that current. A two-wire multimeter cannot do the job at this level, because its leads and probe contacts sit in series with the winding and routinely exceed it. The steps below give the isolation routine, both measurement methods, and what the result is good for.

The nameplate VA fixes a burden, not the copper #

The rated burden is the impedance the secondary may feed while the CT still holds its accuracy class. Convert it with Z = VA / I², using the rated secondary current. IEC 61869-2, the product standard for inductive current transformers, fixes how the accuracy class and rated burden are defined; nameplates on older installations were built to IEC 185, its withdrawn predecessor. The saturation behavior of a specific type comes from the manufacturer's excitation characteristic, and the winding resistance comes from the data sheet for that exact type or from the measurement below. Confirm the class and burden on the nameplate against the CT's own documentation, because nothing printed there is an ohm value for the copper.

Short and isolate the secondary first #

De-energize the primary circuit and verify absence of current by the site's approved method before touching any secondary wiring. Never open a CT secondary while primary current flows: the open winding develops a hazardous voltage and drives the core toward saturation. Apply the CT's shorting arrangement first, then disconnect the burden wiring (relays, meters, test blocks) until only the winding remains between the two secondary terminals, and record every lead you remove. Measure at the CT terminals: anything left connected puts the burden circuit or a parallel path across the winding, and the instrument reports that combination instead of the copper.

Measure with a four-wire milliohmmeter #

The Kelvin connection drives test current through one pair of leads and senses voltage through a second pair. The sense input draws negligible current, so the drop in the current leads and at the current contacts never enters the reading.

  1. Inspect and clean both secondary terminals; corrosion and loose hardware are resistance too.
  2. Select a four-wire range suited to values below 1 Ω, a milliohm range on most instruments.
  3. Clamp the current leads onto the two terminals.
  4. Land each sense lead on its terminal, inside the current clamp's contact point where the instrument allows; that separation is what removes the contacts from the measurement.
  5. Apply the test and hold both contacts steady until the display settles.
  6. Reverse the test polarity and repeat. A meaningful difference between the two readings points to thermal EMF or contact problems, not to the winding.
  7. Record the resistance, the terminal pair, the instrument, and the winding or ambient temperature.
  8. Reconnect once and repeat. A shifted reading points at the test contacts; the winding did not change.

Fall back on terminal voltage over current #

With only a DC current source and a voltmeter, the four-wire principle is built by hand:

  1. Connect the source across the isolated winding.
  2. Connect a separate voltmeter directly at the CT terminals.
  3. Raise to a stable current within the CT manufacturer's limit.
  4. Read terminal voltage and loop current together and calculate R_w = V_terminal / I_test.
  5. Repeat at a second current. Similar results show that contact drop and self-heating are under control.

The source's internal resistance does not enter the result when the voltage is measured at the terminals and the current in the loop; the supply only has to deliver the current. What does enter is lead and contact drop if you read the supply's front-panel voltage instead, because that reading can include everything between the supply and the CT depending on where the supply senses its output.

What the winding resistance is used for #

The winding is one term of the secondary loop. At any current the CT must develop a secondary voltage equal to that current times the loop total (winding, cable, connected burden), and the manufacturer's excitation curve says whether the core can deliver it; why CT saturation at the knee point cuts secondary current shows what happens to the output when it cannot. Winding resistance alone does not set that limit: leakage reactance, core excitation, the burden and the fault-current magnitude all count. The measured value also matters when you inject current through a CT left in the test circuit, because its winding sits in series with the injection path; reverse current injection with a CT: burden voltage decides covers that case. Compare the result with the manufacturer's data for the exact type and with sister cores measured at the same temperature: copper gains roughly 0.4 % per °C, so a winding 25 K warmer reads about 10 % higher.

Worked example on a 15 VA, 5 A secondary #

Hypothetical ring-type CT, 5 A secondary, nameplate burden 15 VA, measured at 20 °C ambient.

Permitted burden as an impedance: Z = VA / I² = 15 VA / (5 A)² = 15 / 25 = 0.6 Ω. That is the ceiling on the connected load, not the winding.

Four-wire readings at the terminals: 0.0435 Ω one way, 0.0432 Ω reversed. The mean is 0.04335 Ω, rounded to 0.0434 Ω, and the 0.0003 Ω spread (about 0.7 %) is contact-level noise, so the mean stands.

Cross-check with a current source: 1 A DC injected, the voltmeter at the terminals reads 43 mV, so R_w = 0.043 V / 1 A = 0.043 Ω. That matches the four-wire mean within rounding and confirms the isolation and the contacts.

Two-wire attempt with a hand-held multimeter: 0.31 Ω, of which about 0.27 Ω is leads and probe contacts. Reject it.

Decision: record 0.043 Ω at 20 °C as the winding resistance. Keep it, the 0.6 Ω permitted burden, and any cable-loop measurement as three separate numbers in the saturation calculation.

The decision for each case #

  • Four-wire milliohmmeter on site: measure at the CT terminals, reverse polarity, record the mean with its temperature. That is your winding resistance.
  • Only a DC source and a voltmeter: use the terminal voltage-over-current method, and never read the supply's own display as the voltage.
  • Only a two-wire multimeter: you have no valid winding number. A reading that moves when the probes move is lead and contact resistance, so get one of the two methods above before the value goes into a study.
  • Loop resistance wanted for the saturation check: run a separate end-to-end measurement that includes cable and burden, and record it separately from the winding.
  • A winding that disagrees with its sisters or with the manufacturer's data: clean and tighten the terminals and re-measure first; a persistent large deviation means the CT is investigated for shorted turns before it is trusted again.

Questions asked

Will a DC winding test leave the CT core magnetized?

It can. Direct current through the winding leaves remanent flux in the core, and a protection CT with remanence responds differently to its first fault after re-energization. Follow the manufacturer's demagnetization procedure after the test and before returning the CT to service; if the documentation gives none, get the procedure from the manufacturer rather than assuming the core is clean.

How much test current is safe through the secondary?

The winding carries its rated secondary current, 1 A or 5 A on most CTs, continuously in service, so a test current at or below that value cannot overheat it. Above that, heating raises the copper's resistance while you measure and the reading drifts. Stay within the instrument's limit and the CT manufacturer's limit, whichever is lower.

Can I just zero the leads on my two-wire multimeter?

Zeroing removes one fixed offset, but the probe contacts at the CT terminals are a separate, variable resistance in series with the winding, commonly a few tenths of an ohm and unstable when the probes move. On a winding below 0.1 ohm that error can exceed the value you want several times over, so no zeroed two-wire reading is publishable as winding resistance.

Can comparing the three phase CTs find a bad unit?

Yes, with care. Identical cores measured the same way at the same temperature should agree closely; check the manufacturer's tolerance for the type. One winding markedly higher usually means a poor connection or extra length in the test path, while one markedly lower can indicate shorted turns. Fix the terminals and re-measure before condemning the CT.

Keep reading

  • Explainer

    Reverse current injection with a CT: burden voltage decides

    A CT multiplies current only into a burden that is nearly a short circuit. Into 1,200 Ω, 100 mA forces 120 V and 12 W at the output, which reflects as 75 MΩ and 30 kV on the 250-turn winding, beyond any 400 µA source and any CT core or insulation. Lower the burden to ohms or less, where secondary injection is standard practice, or drive the load from a 60 Hz source that supplies the voltage and power directly.

    Protection: breakers, fuses and SCCR

  • How-to

    Calculating low-side fault current with source impedance

    For a 20 MVA, 8.2%, 161:13 kV transformer with an assumed 2500 MVA utility source, the source adds 0.008 pu to the transformer's 0.082 pu, and dividing the 888 A low-side base current by the 0.090 pu total gives about 9.87 kA. If the nameplate secondary is actually 13.8 kV, the answer is about 9.3 kA.

    Protection: breakers, fuses and SCCR

  • How-to

    How to calculate transformer secondary fault current in per-unit

    Yes — use one MVA base for the whole study, and the transformer rating is the convenient one: with 16.091 kA available at 230 kV and a 24 MVA, 8.8%Z, 230/13.2 kV transformer, the source impedance is 0.003744 pu, the total is 0.091744 pu, and the secondary fault current is about 11.44 kA at 13.2 kV. The infinite-bus figure, 11.93 kA, is the ceiling to rate against when the primary source is ignored or unknown.

    Protection: breakers, fuses and SCCR