How-to
Reconnecting a 12-lead 575 V delta motor to 480 V wye
Short answer
Reconnection follows the standard 12-lead map whether the winding is concentric or lap: jumpers 4-7, 5-8 and 6-9 come off, leads 4, 5, 6, 10, 11 and 12 tie into one star point, and pairs 1-7, 2-8 and 3-9 land on the lines. Series delta at 575 V puts 287.5 V on each group; parallel wye at 480 V puts 277 V, about 3.6 percent low. Make the move only when the nameplate lists the wye connection at the new voltage.

On this page
- Does a concentric winding change how you reconnect a 12-lead motor?
- Can a 575 V delta motor run on 480 V wye?
- What do you read on the nameplate before touching a jumper?
- How do you identify twelve leads when the tags are gone?
- How do the jumpers change from series delta to parallel wye?
- How do you prove the winding is healthy before energizing?
- What currents should the first run show?
- Questions asked
A twelve-lead motor moving from series delta on a 575 V system to parallel wye on a 480 V system follows one standard lead map, whether the stator is lap-wound or concentric-wound: the external connection acts on the numbered leads in the conduit box, not on the coil layout inside the frame. This procedure takes you through the validity check, the nameplate reading, lead identification, the jumper changes and the first run, and it assumes both systems run at 60 Hz. One condition decides everything: the nameplate must list the wye connection for the new supply, and if it does not, the job stops right there.
Does a concentric winding change how you reconnect a 12-lead motor? #
No — the external reconnection depends only on the numbered leads in the conduit box, so a concentric-wound stator follows the same jumper chart as a lap-wound one, and the coil layout inside the frame matters only when the motor is rewound.
Concentric and lap describe how coils sit in the slots. A concentric winding nests coils of several spans inside one another under each pole group; a lap winding repeats a single coil span around the stator. Either way, what reaches the conduit box is the same set of group starts and finishes, stamped with numbers 1 through 12, and every jumper chart acts on those numbers alone. That is why a reconnection never needs the internal winding diagram you may have been hunting for; it needs the external connection diagram on the nameplate or the conduit-box lid. The internal layout returns as engineering only at a rewind, and if your job is heading there, a page on concentric-to-lap winding conversion calculations for AC motors works through the math a rewind shop applies.
Can a 575 V delta motor run on 480 V wye? #
Yes, when the nameplate lists the wye connection for the new supply: the series delta in the box now puts 287.5 V across each winding group, and a parallel wye on the 480 V lines puts 277 V, about 3.6 percent lower, which a healthy machine tolerates.
Group voltage sets the flux in the iron, so the validity question reduces to comparing the voltage on one winding group before and after the change:
- Series delta, 575 V line-to-line: each of the three branches spans the full line voltage and carries two groups in series, so each group sees 575 V ÷ 2 = 287.5 V.
- Parallel wye, 480 V line-to-line: each branch spans the phase voltage, the line voltage divided by the square root of three, so 480 V ÷ 1.732 = 277.1 V, and with each phase's two groups in parallel, every group still sees 277.1 V.
- The change: (277.1 − 287.5) ÷ 287.5 = −10.4 V, which is −3.6 percent.
Those are estimates from nameplate line voltages, and the connection diagram shipped with the machine is the governing document. A 3.6 percent drop in group voltage drops flux by the same fraction, so torque capability falls roughly with the square of it — 0.964 squared is 0.93, about 7 percent — while slip and running current at a given load rise slightly. Insulation stress falls with the voltage, so the insulation class gains margin. That is an ordinary operating shift, and the full-load current the plate lists for the wye connection already includes it. What the arithmetic cannot do is authorize the connection on a machine whose plate lists nothing but the delta.
What do you read on the nameplate before touching a jumper? #
Three entries decide the job before any lug moves: twelve numbered leads in the conduit box, a connection diagram that lists the wye connection for the new supply with its own full-load current, and a 60 Hz rating that matches both systems.
- Lead count: twelve leads in the conduit box, each stamped with its number. Any other count is a different winding — two-winding multi-speed stators bring out many more — and it leaves this procedure at the door.
- Connection diagram: the plate or the box lid lists every allowed voltage with its connection and its own full-load current. The entry you need is the wye connection at the new supply voltage, and it carries the current figure you will set into the overload later; our article on why motor nameplate current is line current, not winding current explains what that figure measures.
- Frequency: 60 Hz on the plate matching 60 Hz on the new system, so the flux comparison above holds.
The decision is binary. If the wye entry for the new voltage is on the plate, continue below. If the plate lists only the series delta, the machine is not documented for the change: the reconnection waits until the manufacturer or the winding shop supplies a connection sheet that shows the wye connection and its rating.
How do you identify twelve leads when the tags are gone? #
Work from continuity, not from memory: each winding group shows one low-resistance pair between two of the twelve leads, six such pairs account for all of them, and every lead leaves the box wearing exactly one tag.
Before the box opens, lock the feeder out and verify absence of voltage at the motor terminals with a meter you have just proven on a known live source; NFPA 70E, the 2024 edition, covers that lock-and-verify sequence, and your plant's electrical safety program and the authority having jurisdiction set the local rules. Then:
- Photograph the existing delta connection before a single lug turns.
- Pair the leads with a continuity tester: each winding group reads as one low-resistance pair, six pairs across the twelve leads, and no lead reads to the frame.
- Tag both ends of every pair with the same phase letter and a start and finish suffix — the u1 and x1 style used on six-lead machines, extended group by group — so each lead carries exactly one identity.
- Remember that continuity proves which ends belong together, not which end is the start; a reversed group passes every resistance test and shows up only as current unbalance on the uncoupled run.
- If the factory numbers are gone altogether, the numbering comes from the nameplate diagram or from the spiral lead-identification procedure a winding shop runs; a guessed numbering puts groups in opposition.
How do the jumpers change from series delta to parallel wye? #
Three jumpers come off, one star point ties six group ends, and three line pairs land on the supply: 4-7, 5-8 and 6-9 removed; 4, 5, 6, 10, 11 and 12 tied; 1 with 7, 2 with 8, 3 with 9 as the line connections.
- Keep the lockout from the lead identification in force and re-verify absence of voltage at the leads.
- Photograph and tag the existing series delta: its line leads are 1, 2, 3, 10, 11 and 12, two per corner, with the three series jumpers between them.
- Open the three corners and pull the three series jumpers so all twelve leads hang free.
- Tie the six group ends the nameplate lists — 4, 5, 6, 10, 11 and 12 on the common layout — into one star point under a single rated lug, and insulate the joint.
- Pair 1 with 7, 2 with 8 and 3 with 9 and land those three pairs on supply conductors L1, L2 and L3.
- With the supply still locked out, read continuity from each line pair to the star point: three equal low readings, and an open reading from every lead to the frame.
These numbers follow the common twelve-lead layout; where the nameplate diagram differs, the diagram wins. If the terminal box carries star and delta jumper bars instead of loose lugs, the page on what star and delta jumper bars mean on a motor terminal box shows how the same two connections map onto those bars.
How do you prove the winding is healthy before energizing? #
Two meter tests stand between the reconnection and the first start: a winding-resistance balance taken across the three line pairs, and an insulation-resistance reading from the winding to the frame.
Winding resistance: with a low-resistance ohmmeter and the supply still locked out, read across the three line pairs to the star point. Three matching readings mean the two parallel groups of each phase are intact; a pair that sits apart from the other two flags a bad joint or a failing group before it ever sees load. The page on what a multimeter shows about three-phase motor winding resistance covers the method and its limits in detail.
Insulation resistance: bundle the leads together, then test from the bundled winding to the frame with a megohmmeter at 500 V DC, the usual level for machines of this voltage class. Compare the reading against the minimum the manufacturer or rewind shop publishes for the winding class and against the motor's own trend history; the failure pattern to watch for is pictured in our article on reading motor lead-to-ground ohms.
What currents should the first run show? #
Bump the motor uncoupled, then judge three current readings in order: three near-equal unloaded currents well below the nameplate figure, three near-equal loaded currents at or under the wye connection's full-load rating, and an overload set to that same nameplate value.
Bump first: uncoupled, a second of power, and confirm rotation; swap any two line pairs to reverse it. Run uncoupled and read the three line currents: a correct parallel wye draws magnetizing current only, so each phase sits well below the nameplate full-load figure and all three track closely. One phase riding high means a jumper is wrong or a group is reversed — back to the box before anything couples. Then couple the load and read the three currents against the full-load value the plate gives for the wye connection, a line current by definition; the physics that makes one motor draw different line current in wye and delta is exactly why that figure changes when the connection does. Set the starter's overload to the wye figure from the plate, never to the delta value or a hand-scaled guess, and check frame temperature after the first loaded hour.
The decision: a twelve-lead machine whose plate carries the wye connection for the new supply makes this move in an afternoon of lug work — three jumpers off, one star point on, three line pairs to the line — and runs inside its rating. A plate that lists only the delta connection holds the motor on its original supply until a connection sheet from the manufacturer says otherwise.
Questions asked
What happens if the motor stays in series delta on the 480 V supply?
Each group then sees 480 V ÷ 2 = 240 V instead of the 287.5 V it carried on the higher supply, about 16 percent low. Torque capability falls with the square of the group voltage, so roughly 30 percent of it disappears; at rated load the motor then draws excess current, heats and trips the overload. Reconnect to parallel wye or put the machine back on its original supply.
Which full-load current goes into the overload relay after the reconnection?
The full-load current the nameplate lists for the wye connection at the new voltage, not the delta figure and not a hand-scaled value. That plate number is line current at the motor terminals, which is exactly what the overload carries, so set the relay to it directly. Inside the box, the winding carries that same line current in the wye connection; in delta the line carries more than the winding does, which is why the plate lists a current for each connection.
Can you make the move when the nameplate lists only the delta connection?
No, not on the strength of the nameplate alone. The group-voltage arithmetic favors the change, but nothing else on the machine is documented at the lower voltage: no connection diagram, no full-load current for the wye connection, no maker tolerance statement. Ask the manufacturer or the winding shop for a connection sheet showing the wye connection and its rating before any jumper moves, and run the motor on its original supply until it arrives.
What if the stator brings out more than twelve leads?
Then it is a different winding, most often a two-winding multi-speed stator, and the twelve-lead chart does not apply. Count and tag every lead, record the resistance of each pair, and connect nothing until the manufacturer's connection diagram is in hand; a two-winding stator connected off the wrong sheet can put supply voltage across a winding that was never built for it.