Selection guide
Selecting current transformers for protection relay requirements
Short answer
Current transformer requirements are never optional, even for plain overcurrent protection. Match the CT's secondary rating to the relay input, its protection class (5P20 IEC or a C-class under IEEE C57.13) and its rated burden, then compute the available accuracy limit factor and require it to exceed the maximum fault current multiple; the worked example below fails at 16.4 available against 20 required.

On this page
- What must the CT match before any setting is touched?
- Which nameplate lines decide a protection CT?
- How do you check an IEC 5P20 CT against the real burden?
- How does an ANSI C-class rating work for the same check?
- When does a metering class CT fail in protection service?
- What can you change when the CT comes up short?
- What safety step comes first when the CT circuit must be opened?
- Questions asked
Current transformer requirements are not optional, not even for a plain overcurrent element. A CT that fits the panel window and reads load current correctly can still distort the first time a real fault arrives, because the relay then needs a multiple of rated current the core cannot reproduce. Select against three nameplate lines and one calculation: the secondary rating matched to the relay input (1 A or 5 A), the protection class (5P20 under IEC 61869-2 or a C-class under IEEE C57.13-2016), and a burden-and-accuracy-limit check that clears the maximum fault current multiple. The worked example below uses a 400/5 A, 30 VA, 5P20 unit that fails its own feeder at 16.4 available against 20 required, and shows the two changes that fix it.
What must the CT match before any setting is touched? #
Three things match before you touch a setting: the CT secondary rating against the relay input, the protection class against the function the relay performs, and a burden-plus-accuracy-limit figure that covers the maximum fault current through that CT.
Start from the relay manufacturer's application documentation, which states a CT requirement for each protection function it offers. Plain overcurrent is the least demanding function, and even it needs the class and burden met; differential, distance and high-impedance elements demand more, and high-impedance schemes state a specific voltage class outright. The secondary rating is the first mismatch to catch: a full-rating CT loop feeding a lower-rated relay input reports five times the real current, as the article on mismatched CT secondary ratings shows. Decide the CT from the relay's requirement table before you open any catalog; a CT that fits the window and reads load correctly has not yet qualified for anything.
Which nameplate lines decide a protection CT? #
Read four lines off the nameplate and its test report: the ratio (400/5 in the worked example), the rated secondary current, the protection class and burden together (30 VA, class 5P20), and the secondary winding resistance (0.15 Ω in the example, from the test report).
The class designation carries the commitment: 5P20 means composite error within 5 % up to twenty times rated primary current with rated burden connected, with P marking protection service. Metering designations instead carry an instrument security factor (FS5, FS10) that licenses early saturation to protect meters — the opposite of what a fault path needs. IEC 61869-2 (2012 edition and later amendments) defines these P classes, and IEC 61869-1:2023 adds optional wideband accuracy classes for inductive CTs (the WB2 extension); they matter only where a specification or relay datasheet calls for wideband performance. On multi-ratio units each tap changes both the ratio and the burden rating that applies, so read the nameplate guide to multi-ratio current transformers before ordering from one tap's numbers. Where the CT feeds a differential element, verify the ratio match the way the walk-through of checking a 600/5 CT ratio for transformer protection does it.
How do you check an IEC 5P20 CT against the real burden? #
Compute the available accuracy limit factor with ALF' = ALFn × (Sn + Rct) ÷ (Sa + Rct) and require it to exceed the fault multiple; the example below lands at 16.4 against a required 20, so that CT fails and must change before any setting is touched.
The formula is the correction for winding resistance published in CT manufacturers' application guides, built on the accuracy limit factor definition in IEC 61869-2: the rated factor on the nameplate applies only when the connected burden equals the rated burden, and every ohm added in the loop buys back a proportional loss of factor. Worked example, every input an example value:
- CT: 400/5 A, rated secondary 5 A, nameplate 30 VA, class 5P20
- CT secondary winding resistance Rct: 0.15 Ω, from the routine test report
- Relay input burden: 0.02 Ω at the rated secondary current, from the relay datasheet
- Leads: 100 m each way in 2.5 mm² copper, about 0.0074 Ω/m per conductor, so the loop is 200 m × 0.0074 Ω/m = 1.48 Ω
- Maximum fault through the CT: 8 kA primary, from the system study
| Step | Arithmetic | Result |
|---|---|---|
| Rated burden Sn | 30 VA ÷ (5 A)² | 1.2 Ω |
| Actual burden Sa | 1.48 Ω leads + 0.02 Ω relay | 1.50 Ω |
| Available ALF' | 20 × (1.2 Ω + 0.15 Ω) ÷ (1.50 Ω + 0.15 Ω) = 20 × 1.35 ÷ 1.65 | 16.4 |
| Required multiple | 8,000 A ÷ 400 A | 20 |
| Verdict | 16.4 < 20 | fails |
Lead resistance usually dominates the loop, which is why guide on high nominal CT burden, saturation and protection solutions treats the whole secondary circuit, not just the relay, as the burden. Past the accuracy limit factor the composite error climbs steeply, and the relay can under-reach, over-reach or delay on the distorted waveform. Treat the result as a design estimate: confirm the inputs against the CT test report and the relay's burden data before the selection is signed.
How does an ANSI C-class rating work for the same check? #
Under IEEE C57.13-2016, a C-class rating states the RMS voltage the CT delivers at twenty times rated secondary current with up to 10 % ratio error, so a C400 unit on the full-rating secondary covers 4 Ω of everything in the loop: winding, leads and relay input.
C means the ratio correction is calculable from winding and lead resistance; T means the manufacturer established the class by test, and its published performance governs. The standard relay voltage classes are 100, 200, 400 and 800 V on the full-rating secondaries. The burden check divides the class voltage by twenty times rated secondary current: 400 V ÷ (20 × rated secondary current) = 4 Ω of total loop impedance for a C400 unit. The worked example's loop totals 1.65 Ω once winding, leads and relay add up, so it clears 4 Ω on the simple check. The published saturation-threshold method adds the two inputs that simple figure ignores — the maximum fault current and the system X/R ratio — because the DC offset component of fault current drives the core toward saturation faster than the AC term alone. Decide the C class from total ohms at twenty times rated secondary current, then verify the offset condition with that method before signing.
When does a metering class CT fail in protection service? #
At the first fault, because a metering CT is engineered to saturate early: its class designation, for example class 0.5 with an FS5 security factor, is allowed to distort from five times rated current upward, while a protection element needs a faithful waveform at twenty times rated current and beyond.
The security factor caps how long the metering core stays linear: with FS5, the manufacturer guarantees only that distortion grows beyond five times rated current, protecting the meters instead of the trip decision. A P class inverts that contract and holds composite error inside 5 % out to the accuracy limit factor. Nothing on a normal-load display reveals the difference: the metering CT's load reading can be flawless while its fault trace collapses. Decide once: a metering class designation feeding a protection input is a hardware defect to correct with a P-class or proven C-class CT, not a behavior to tune around with pickup or delay.
What can you change when the CT comes up short? #
Cut the loop ohms or raise the class: re-running the example with 4 mm² leads lifts ALF' from 16.4 to 24.8, and selecting 5P25 on the same wiring lifts it to 20.5 — either clears the required 20, while loosening pickup or delay settings clears nothing.
Each fix moves a term you can compute before ordering anything. Larger conductors: 4 mm² copper runs about 0.0046 Ω/m, so the same 200 m loop drops to 0.92 Ω, the actual burden falls to 0.94 Ω, and ALF' becomes 20 × 1.35 ÷ 1.09 = 24.8. Higher class: 5P25 on the unchanged wiring gives 25 × 1.35 ÷ 1.65 = 20.5. Higher rated burden: a 60 VA rating doubles Sn and lifts ALF' to 30.9 on the original loop. The relay still receives a distorted waveform regardless of its settings, so a looser pickup or longer delay compensates for nothing. After any change, prove the element with the relay manufacturer's secondary-injection commissioning procedure and record phase readings and trip outputs against the approved settings. Decide by margin: a small shortfall is cheapest to fix in copper, a new purchase should step the class, and a remote relay building a long run belongs on a 1 A secondary.
What safety step comes first when the CT circuit must be opened? #
De-energize the primary and short the secondary winding before any CT terminal is opened, because an energized CT driving a near-infinite burden develops a secondary voltage high enough to injure a person and to puncture insulation; the shorting block or test switch is the documented means.
NFPA 70E, 2024 edition, covers the work practices that apply: de-energize, lock out and verify absence of voltage before a panel, terminal box or CT circuit is opened, and treat anything less as energized work governed by that standard's provisions — requirements differ by country, edition and local amendment, so confirm with the authority having jurisdiction and the equipment documentation. For CT secondaries the added rule is physics rather than jurisdiction: with the primary carrying current, an open secondary drives the core into a hazardous voltage, which guide on CT secondary voltage versus burden physics and open-circuit hazards explains in detail. Close the shorting block or test switch before any meter lead leaves a terminal, and leave secondary injection testing to qualified personnel under the approved procedure. Decide the sequence once and repeat it every time: short, then open, then measure.
Questions asked
What does each part of the 5P20 designation specify?
The 5 is the composite error limit, 5 %, held at the accuracy limit factor; the P marks a protection class; the 20 is that factor, twenty times rated primary current, delivered with rated burden connected. A 5P10 holds the same error to ten times rated current and a 5P30 to thirty times, so the last digit scales the coverage directly.
Where does the winding resistance value come from?
The CT's routine test report lists it per ratio or tap. If the report is missing, a four-wire micro-ohmmeter measurement at the secondary terminals reproduces it; isolate and short the circuit first and follow the CT manufacturer's test procedure. Never substitute a generic value, because the available accuracy limit factor moves with every 0.1 Ω.
Does a 1 A secondary make long lead runs easier?
Yes, by a factor of twenty-five in ohms at the same volt-ampere rating: rated burden equals volt-amperes divided by the square of rated secondary current, so 30 VA is 1.2 Ω on a 5 A CT and 30 Ω on a 1 A CT. For a relay room far from the switchgear, the 1 A loop cuts lead burden by that factor.
Can a protection class CT also feed the plant revenue meter?
A 5P class holds ratio error near 1 % at rated current, accurate enough for indication and plant energy monitoring, but revenue billing normally requires a dedicated metering core of tighter class, and the utility sets that requirement. Keep the cores separate on multi-core units and confirm the metering class with the utility before sharing.