Current IntelPower LibraryShop main store

Troubleshooting

Why a 1 A relay input on 5 A CTs reads five times the current

Protection: breakers, fuses and SCCR Published 7 min read By Current Intel engineering team

Short answer

When a motor protection relay shows about five times a current you trust, its phase CT input is the 1 A hardware variant on 5 A CTs: a 100:5 CT at 104 A delivers 5.2 A, and an input that treats 1 A as 100 A displays 520 A. Correct the input variant, not the CT ratio, the motor data or the CTs.

On this page
  1. Where the factor of five comes from
  2. The arithmetic on this motor
  3. Separate a false reading from a real overload
  4. Confirm which input variant the relay has
  5. Keep the 100:5 CTs
  6. The fix, case by case
  7. Questions asked

A motor protection relay displaying about five times a current you have verified with a clamp meter is not seeing more current. Its phase CT input is the wrong secondary variant. A 100:5 A CT on a 104 A motor feeds 5.2 A into the relay, and a 1 A input with the primary set to 100 A reports that as 520 A. The correction is the relay's input hardware, not the CT ratio, the motor data or the CTs. Below is the mechanism, the arithmetic on the documented 800 hp case, the checks that separate this from a real overload, and the decision for each case.

Where the factor of five comes from #

A current transformer with a 100:5 nameplate makes its full nominal secondary current when the primary carries 100 A, which is twenty primary amps for every secondary amp. The relay converts secondary current into primary current using the primary rating you program and the nominal secondary of its input hardware. Both must agree with the CT.

The two input variants are different hardware. A higher-secondary input treats its nominal secondary as 100 percent of the programmed primary; the lower-secondary input treats its own nominal the same way. Feed a CT's output into the wrong input variant and every reading is multiplied by the ratio of the two secondary ratings, 5 ÷ 1 = 5. The settings sheet can still show the correct ratio, because the program only holds the primary number, which is why the configuration looked right while the hardware was wrong. No parameter turns one input variant into the other: they are separate order codes, and since the lower secondary rating is common in IEC markets, a supplier can ship the wrong one unless the order specifies it.

The case that documents the failure:

Item What was installed What it means
Motor 800 hp, 4160 V, three-phase, FLA 104 A Reference for every load checks
Phase CTs 100:5 A Higher secondary rating, 20 A primary per secondary amp
Original relay Phase CT input matched to the CTs Served correctly for years
Replacement relay 1 A phase CT input (a Multilin 469) Multiplied every reading by five
Pre-trip display about 500 A Actual current about 100 A

The arithmetic on this motor #

Run the numbers with the motor at full load:

  • Secondary current from the CT: I_sec = 104 A × (5 A ÷ 100 A) = 5.2 A.
  • What the wrong input reports: with the primary rating programmed as 100 A, a 1 A input maps each secondary amp to 100 A, so the display reads 5.2 A × (100 A ÷ 1 A) = 520 A.
  • Error factor: 520 A ÷ 104 A = 5, exactly the ratio of the two secondary ratings.

The reported pre-trip display back-calculates the same way: 500 A ÷ 5 = 100 A actual, just under full load, which matches the repair shop's finding that the motor was healthy after they checked it for a broken rotor bar.

A power check closes the argument. At full load the input power is √3 × 4160 V × 104 A × 0.8 power factor ≈ 599 kW, about 804 hp at the terminals, consistent with an 800 hp machine once efficiency is allowed for. A real 500 A would be √3 × 4160 V × 500 A × 0.8 ≈ 2.9 MW, roughly 3,900 hp into an 800 hp motor. That cannot run for minutes without burning or tripping something upstream, so the display was the thing that was wrong, not the machine.

Separate a false reading from a real overload #

An overload trip has three possible sources: real motor current, a broken measurement chain, or wrong protection settings. Decide with one comparison, the relay display against a true-RMS clamp meter on the same conductor:

  • Relay reads about five times the clamp value, on every phase: the input-variant mismatch above. Confirm the variant and replace the unit; do not touch the CT ratio or the motor data.
  • Relay and clamp agree, and the current sits above nameplate FLA: a real overload. Chase load, mechanical binding and supply voltage; a relay that trips at full load with a service factor of 1.0 is a settings and motor-data question, covered in a motor protection relay that trips at full load.
  • Relay and clamp agree at running current, but the trip comes during acceleration: capture the start current and duration and compare them with the CT's documented capability and the protection model, following setting overload relays for high-inertia motor starts.
  • Readings plausible but the trip timing odd: verify the programmed primary, FLA and protection settings against the nameplates, and read the relay's event record before changing anything.

In the documented case the first bullet was the answer, found only after the motor had made a pointless trip to the repair shop.

Confirm which input variant the relay has #

Anything that opens the relay cabinet or touches CT secondary wiring begins with lockout and a test for absence of voltage: NFPA 70E, 2024 edition, covers establishing an electrically safe work condition, and your plant procedure and the authority having jurisdiction govern the details. Never open an energized CT's secondary circuit, because the open winding develops a hazardous voltage.

  1. Read the full part number on the relay nameplate and compare it with the ordering information in the manual. The two phase-input variants are different order codes; the unit in this case was ordered as one and needed the other.
  2. Print the settings and note the programmed primary and motor FLA. A correct-looking ratio proves only that the primary number was entered; it says nothing about which input hardware sits behind the terminals.
  3. Read each CT nameplate: ratio, secondary rating and accuracy class. Designations like the extended-range mark are covered in what an ext. 100% marking means on a current transformer.
  4. Compare one phase at running load: clamp the primary, or read the secondary at the relay's test block without opening the circuit, and compare with the display. A constant factor of five is the signature of the wrong input variant.
  5. Do not confuse the phase inputs with the ground-fault input. On this relay family the standard ground CT input has a secondary rating settable to either of the two standard values, while the phase inputs are fixed hardware. A settable ground input does not mean the phase inputs can be switched in software.

Keep the 100:5 CTs #

The CTs were never the problem, and two rules of thumb that circulated with this fault deserve straight answers.

A CT primary does not need to sit above full-load current. Motor protection wants the primary near FLA so the relay measures load current well inside its accurate range. Here the primary rating and the full-load current are within 4 percent of each other, and the secondary sits 4 percent above its nominal rating at full load, an ordinary operating point. IEEE C57.13, the standard for instrument transformers, defines the accuracy classes, burdens and continuous rating factors that state how far above nominal a CT may run, and that factor is printed on the CT nameplate.

Sizing the CT ratio from the upstream breaker rating suits feeder metering and coordination; it says nothing about motor heating. A motor relay's thermal model needs load resolution near FLA and a start-current measurement within the CT's and the input's documented limits. The breaker's frame rating is not part of that calculation.

And do not install larger CTs to make the display plausible. The 500 A reading that suggested a 500:5 ratio was never drawn; changing CTs on the strength of an uncorrected indication would bury the real fault one layer deeper.

The fix, case by case #

Commit to the pairing of CT secondary and relay input, then act:

  • Wrong input variant on the higher-secondary CTs, the documented case: replace the relay with the unit whose input matches the CTs. Keep the CTs, keep the 100 A primary setting and the motor data. Commissioning check: at load the display must match the clamp value within a few percent on each phase, and a recorded start should show the expected inrush with no measurement fault.
  • The mirror image, matched the other way: readings come out at one-fifth of actual, so thermal protection is blind to a real overload. Correct it the same way, with matched hardware, never by rescaling settings.
  • Display agrees with reality and the current is genuinely high: a load or motor problem, not a measurement problem; work it as the real-overload case above.
  • Trip only during acceleration with a verified measurement chain: a protection-model question. Capture the start profile and set the model from it.

In the plant that documented this fault, exchanging the wrong-variant unit for the matched one ended the false overloads. The CTs, the motor and the settings were never at fault.

Questions asked

Can I program the primary rating to 20 A so the 1 A input displays correctly?

Arithmetically yes: 5.2 A of secondary times a 20 A primary gives the true full-load current. But the input hardware still carries 5.2 A on a circuit rated 1 A, more than five times nominal continuously, and about 31 A during a six-times-FLA start. That is outside the input's documented continuous capability and accuracy band, so the display improves while the input is abused. Replace the unit instead.

Why did the overload protection trip if the motor was healthy?

The thermal model integrates whatever current the relay measures. Fed the false five-times value, it saw roughly five times full load and accumulated thermal capacity at that rate, so an overload trip was the expected outcome of the scaling error, not evidence of a motor fault. That is also why the trip resembled a broken rotor bar: the current profile was real to the relay and meaningless in amperes.

The 1000 hp motor nearby runs fine on 150:5 CTs. Does that make its ratio the right pattern?

No. It works because its relay input matches its CT secondary, not because the primary sits above its 127 A full load. At full load those CTs produce 127 A × 5 ÷ 150 = 4.23 A, comfortably below nominal, while the 100:5 CTs produce 5.2 A at their motor's full load, slightly above nominal. Both pairings are sound because each input matches its CT's secondary. Proximity of the CT primary to FLA is a resolution choice, not a correctness test.

How do I keep the wrong variant off my shelf again?

Write the CT secondary rating into the purchase specification and the relay order code, and compare the nameplate part number with the ordering table in the manual before the unit goes into the cabinet. The two phase-input variants are distinct hardware and not convertible in software. Spare relays for a plant wired to the higher secondary rating should be that variant; a spare of the other variant, ordered to a different standard, is how this failure arrived.

Keep reading

  • Troubleshooting

    Why a motor current unbalance trip can show balanced phase currents

    When a protection relay trips on current unbalance and an independent logger shows the phases within 2%, the disagreement itself is the finding: the relay builds its unbalance quantity from its FLA base, CT scaling and its own definition, and an error anywhere in that chain trips on balanced current. Verify the settings arithmetic against the nameplate, compare relay metering with simultaneous independent measurements, and test supply voltage unbalance under load before condemning the motor.

    Protection: breakers, fuses and SCCR

  • Comparison

    Why induced voltage defeats simple phase loss protection

    A spinning motor regenerates roughly half its normal voltage onto an open phase, so a phase loss relay that watches voltage alone can hold the contactor in while the motor single-phases. Set the relay's dropout above your measured back-feed voltage — or drop voltage sensing for per-phase current, unbalance or phase-angle detection, which the back-feed cannot fool.

    Protection: breakers, fuses and SCCR

  • Selection guide

    Overload relay range selection for an 18.5 kW motor

    Select the relay by the motor's nameplate full-load current, not by kilowatts: pick the adjustable range that brackets that current away from both dial ends, then set the trip class from the measured acceleration time — class 10 for starts under 10 seconds, class 20 up to about 20. An 18.5 kW motor on a 400 V supply works out near 35 A; verify against the nameplate before you buy.

    Motors and motor starters