Sizing a generator for unbalanced delta loads

Power distribution and transformers Published 6 min read By Current Intel engineering team

Short answer

The 100 + 200 + 300 kVA branch sum of 600 kVA is only a load inventory. At 480 V with one common power factor the worst line carries 908 A, the limiting winding needs 251.7 kVA, and the minimum is 755 kVA, so the selection is an 800 kVA set.

On this page
  1. What does the 600 kVA branch sum tell you?
  2. How do you convert each branch's kVA into a current?
  3. How do the branch currents combine into line currents?
  4. Which winding sets the size on a wye-connected generator?
  5. Does a delta-connected generator change the answer?
  6. What moves the 755 kVA requirement?
  7. Which generator do you order?
  8. Questions asked

A delta panel with 100 kVA on AB, 200 kVA on BC and 300 kVA on CA holds 600 kVA of connected load, and that sum is only an inventory. The branch currents reach the generator as phasors, and the winding carrying the largest line current decides the size. Worked at 480 V with one common power factor, the worst line carries 908 A, the limiting winding needs 251.7 kVA, and the minimum machine is 755 kVA, so the order is an 800 kVA set. Below is the arithmetic, what moves the number, and where the usual shortcuts land.

What does the 600 kVA branch sum tell you? #

The sum 100 + 200 + 300 = 600 kVA is a correct inventory of connected apparent power, but it does not size the machine: a 600 kVA generator at this voltage is rated 722 A per line, and this panel's worst line runs 126% of that. A synchronous generator is three equal single-phase windings on one shaft, and each winding has its own current limit. Balanced load splits evenly and the nameplate arithmetic holds; unbalanced load shares unevenly, so a total that looks fine can hide one winding over its limit. Size from the winding currents, then use the total only for the real-power check: at a common power factor the panel draws 600 times that factor in kilowatts, 600 kW at unity.

How do you convert each branch's kVA into a current? #

Divide each branch's apparent power by the line-to-line voltage, I = S / V, because every single-phase load sits line to line; at the nominal voltage the three branches draw 208.3 A, 416.7 A and 625.0 A. The arithmetic is 100,000 VA / 480 V = 208.3 A on AB, 200,000 VA / 480 V = 416.7 A on BC, and 300,000 VA / 480 V = 625.0 A on CA. Magnitude is only half of each current: the angle comes from that branch's power factor, and magnitudes alone cannot be added.

How do the branch currents combine into line currents? #

Each line carries the phasor difference of the two branch currents that end on it: I_A = I_AB − I_CA, I_B = I_BC − I_AB and I_C = I_CA − I_BC, with every branch current placed at its own angle. For the worked case take one common power factor: a common factor rotates all three branch currents by the same angle, so every line current rotates by that angle and keeps its magnitude, which makes unity power factor a fair stand-in. With the branch voltages 120° apart and V_AB as the 0° reference:

Line Phasor sum Magnitude
A 208.3∠0° − 625∠120° = 520.8 − j541.3 A 751 A
B 416.7∠−120° − 208.3∠0° = −416.7 − j360.8 A 551 A
C 625∠120° − 416.7∠−120° = −104.2 + j902.1 A 908 A

As a check, voltage times the three branch-current magnitudes, (208.3 + 416.7 + 625.0) A, returns 600 kW: real power is conserved, and only its split among the lines is uneven.

Which winding sets the size on a wye-connected generator? #

The winding carrying the largest line current sets it, because a wye stator puts each line current through one phase winding at phase-to-neutral voltage, which is the line-to-line value over √3, 277.1 V. The three winding loads follow directly:

  • 277.1 V × 751 A = 208.2 kVA on phase a
  • 277.1 V × 551 A = 152.7 kVA on phase b
  • 277.1 V × 908 A = 251.7 kVA on phase c

The windings are built equal, so each must be rated for the largest loading: the nameplate minimum is 3 × 251.7 = 755 kVA. This is the same winding-by-winding method as sizing a three phase transformer for unbalanced 230 V loads: the coils are equal, and the loaded one decides.

Does a delta-connected generator change the answer? #

No: a delta stator resolves the same line currents into winding currents equal to one-third of the line-current differences, and its most loaded winding carries 524 A, which is the same 251.7 kVA at the winding's line-to-line voltage. With no circulating current in a symmetric delta:

  • J_AB = (I_A − I_B)/3 comes to 318 A
  • J_BC = (I_B − I_C)/3 comes to 434 A
  • J_CA = (I_C − I_A)/3 comes to 524 A

Then 524.3 A × 480 V = 251.7 kVA, and 3 × 251.7 = 755 kVA again: the connection changes winding current and voltage, not the machine size. The shortcut of tripling the largest branch, 3 × 300 = 900 kVA, imagines a stator winding carrying a panel branch outright; the winding actually carries a difference current, which is why the computed need comes out lower and the shortcut runs conservative for this panel.

What moves the 755 kVA requirement? #

A common power factor does not move it at all, but branch power factors that differ, a terminal voltage below nominal, and loads that never peak together each move it, and the first moves it most.

  • Unequal power factors: let the CA branch alone run at 0.8 lagging. Its current swings 36.9°, I_C climbs to 1021 A, phase c becomes 283 kVA, and the minimum becomes 849 kVA, moving the order up to a 900 kVA set.
  • Terminal voltage: at 460 V the same kVA draws 480/460 = 4.3% more current, lifting the minimum to 755 × 1.043 = 788 kVA, still inside the 800 kVA order but with the margin spent.
  • Coincidence: the figures need all three branches peaking together. The 300 kVA branch running alone draws its full branch current down two lines and needs only about 520 kVA behind it, so compute each real operating combination, not the connected total.

Which generator do you order? #

Order an 800 kVA set at this voltage: it is rated 962 A per line against the 908 A worst line, its 0.8 power-factor nameplate delivers 640 kW against the 600 kW real load, and a 750 kVA machine falls 6 A short at 902 A. ISO 8528-1, 2018 edition, defines the application, ratings and performance of engine-driven generator sets, and the rating class you buy must match this panel's duty, because the same hardware carries a different nameplate under standby, prime and continuous ratings. Confirm from the manufacturer's data that the set's published phase-unbalance capability covers a worst line at 126% of the balanced-share current, and confirm the installation requirements with the authority having jurisdiction.

After commissioning, record all three line currents and line-to-line voltages at maximum coincident load, and hold the highest current under 962 A. If the panel must be opened for any reading, de-energize, lock out and test for absence of voltage first, and run the task under your electrical safety program; NFPA 70E, 2024 edition, covers the shock and arc-flash risk assessment it needs. The neutral treatment of the new set is a separate decision, and choosing generator neutral grounding for a 480 V diesel set walks through it.

Questions asked

Is tripling the largest branch a safe shortcut for this panel?

For these three branch ratings, yes. The worst line current can never exceed the sum of the two branch currents meeting at it, 625 A plus 417 A, which caps every power-factor mix at 1.732 times (300 kVA + 200 kVA), or 866 kVA, under the 900 kVA shortcut. That margin belongs to these numbers alone: two large branches sharing a line at opposed power factors can beat the shortcut on a different panel.

Why don't the three winding loadings add back to 600 kVA?

Each is a magnitude, the phase-to-neutral voltage times one line's current, and once the load is unbalanced every line current sits at an angle to its own phase voltage, so the magnitudes pick up a cross term and total about 613 kVA. Real power is untouched: the panel still draws 600 kW at unity power factor, which is why the kilowatt check runs separately from the current check.

Can you rebalance the panel instead of buying a larger set?

Yes, and it recovers the full economy of the branch sum: shift single-phase loads until every branch carries about 200 kVA, and each line current falls to 1.732 times 416.7 A, or 722 A, exactly the line rating of a 600 kVA machine. The move goes only as far as the loads can be reconnected line to line and stay coincident in service.

Keep reading

  • Selection guide

    Sizing a padmount transformer for a 120/240 V delta load

    Select the 300 kVA four-wire delta padmount and reject the 225 kVA unit: the center-tapped winding runs at 129% of its rating during the start on the smaller unit and 97% on the larger one. The choice holds only with a written tapped-section rating covering the start and continuous loading calculated here; otherwise use a single-phase bank or a 208Y/120 V wye secondary.

    Power distribution and transformers

  • How-to

    How many 480 V fixtures on a 30 A three-pole breaker

    Fifteen 2.4 A fixtures fit on a 30 A three-pole 480 V breaker: five each on A-B, B-C and C-A draw 20.8 A per line, under the 24 A continuous-load limit, because a three-pole breaker's pole ratings never add.

    Power distribution and transformers

  • How-to

    Transformer sizing from the highest leg current on a panel

    Size the transformer from the highest recorded leg current, never the sum of the legs: 240 V x 50 A is a 12 kVA load, the 1.25 continuous factor points at a 15 kVA standard unit, and the panel main becomes 80 A. First measure line-to-line, because about 240 V confirms a single-phase source while about 208 V means two legs of a wye and a different transformer.

    Power distribution and transformers