How-to
Sizing a three phase transformer for unbalanced 230 V loads
Short answer
Convert the connected kilowatts to kVA with the load power factor, spread the single-phase loads over the three phases, and multiply the heaviest phase by three: each winding of an 11 kV/415 V star secondary carries only its own loads. In the worked example, 1000 kW at PF 0.8 with a 420 kW heaviest phase needs 3 × 525 = 1575 kVA, so the next standard rating, 1600 kVA, is the selection.
On this page
Sizing a three-phase transformer for a fleet of 230 V single-phase loads is decided by the most heavily loaded phase, not the average. Convert the connected kilowatts to kVA with the load power factor, split the loads across the three phases, then multiply the largest phase kVA by three: each winding of an 11 kV/415 V star secondary carries only the loads wired line-to-neutral to it. Worked below for a 1000 kW fleet at a power factor of 0.8 with the heaviest phase at 420 kW, the rule demands 1575 kVA, so the selection is the next standard rating up, 1600 kVA, not the 1250 kVA a balanced calculation suggests.
The sizing steps in order #
- List every single-phase load with its kilowatts and its power factor, and assign it to L1, L2 or L3.
- Convert each phase to kVA: phase kVA equals that phase's kilowatts divided by the power factor.
- Multiply the largest phase kVA by three. That product is the minimum three-phase rating.
- Compare it with the balanced result, total kilowatts divided by the power factor, and keep the larger.
- Apply a demand factor only where a load study documents one, and apply it phase by phase before rerunning the three-times rule.
- Order the next standard rating above the result from the manufacturer's list.
- Check the secondary line current, the neutral conductor, the tap range and the switchgear ratings against that selection, then verify by measurement after energization.
Convert the connected load to kVA #
Transformers are rated in kVA, so the kilowatt figure of the 230 V fleet is only the start. The conversion is kVA = kW / PF: at a power factor of 0.8 the example load converts as 1000 kW / 0.8 = 1250 kVA, at 0.9 it is 1111 kVA, and at unity it stays at 1000 kVA.
That power factor is an assumption until it is measured with a power analyser or read off the load datasheets, and for motor-heavy fleets the choice moves the answer — see which power factor to use in a motor current calculation before picking the number. Run the same relation backwards, kVA = (V × I × 1.732) / 1000, to turn a kVA rating into a line current; it is the standard balanced three-phase relation used in manufacturer sizing guidance. Every figure in this article is a sizing estimate to be confirmed against the transformer datasheet and the governing installation code.
Why the worst phase sets the rating #
On a star secondary the three windings are independent on the load side: winding L1 sees only what is wired from L1 to the star point. A three-phase nameplate divides into thirds, one third of rated kVA per winding, so a winding that needs more than its third forces the whole unit up — hence kVA_required = 3 × kVA_max_phase. The loads connect line-to-neutral, the phase-to-neutral voltage is the line voltage divided by √3 — here 415 V / 1.732 ≈ 239.6 V — and the star point returns the imbalance as neutral current.
Uneven splitting also drags the three phase-to-neutral voltages apart; the page on resolving wye voltage imbalance with balanced phase-to-neutral loading shows what moves and how to pull it back. Rebalancing is the cheapest lever: moving 60 kW from the heaviest phase to the lightest cuts the rating requirement by 3 × (60 / 0.8) = 225 kVA.
Worked example: the load spread unevenly #
Declared inputs: 1000 kW of connected single-phase load; an assumed power factor of 0.8; an 11 kV/415 V star secondary, vector group Dyn11 as an example for this class — confirm the nameplate; loads wired line-to-neutral; phase split L1 420 kW, L2 310 kW, L3 270 kW.
Phase conversions: 420 / 0.8 = 525 kVA, 310 / 0.8 = 387.5 kVA, 270 / 0.8 = 337.5 kVA, which sum to the balanced 1250 kVA. The requirement follows the heaviest winding: 3 × 525 = 1575 kVA, and the next rating on the usual IEC series is 1600 kVA — confirm the list your supplier builds to.
At the balanced assumption each winding may carry only 416.7 kVA, so winding L1 would run 108 kVA past its share: that is the overheating mechanism behind undersized units on lumpy fleets.
| Phase | kW | kVA at PF 0.8 | Winding current |
|---|---|---|---|
| L1 | 420 | 525 | 2191 A |
| L2 | 310 | 387.5 | 1617 A |
| L3 | 270 | 337.5 | 1409 A |
Currents at the selection: worst-phase winding current 525,000 VA / 239.6 V ≈ 2191 A; secondary line current at the full rating (1600 × 1000) / (1.732 × 415) ≈ 2226 A; primary line current (1600 × 1000) / (1.732 × 11,000) ≈ 84 A at 11 kV.
One large load or many spreadable ones #
If the loads can be distributed over the three phases, the unit above is right and rebalancing does the rest. If it is one large machine or a fleet fixed to a single phase, a three-phase transformer is the wrong tool: two windings sit idle, so two thirds of the capacity never carries current. Use a single-phase transformer sized on its own kVA instead; the supply side then behaves as described in the primary current a single-phase load draws from a three-phase transformer, and the switching device follows the logic of sizing a three-pole breaker for a single-phase transformer. Confirm the utility accepts that much single-phase load on the 11 kV feeder before ordering.
Check the switchgear, neutral and taps #
- Secondary switchgear: about 2226 A flows per line at the selected rating, so busbars, incomer and outgoing devices must be rated and coordinated above that figure — the same discipline as checking an incomer against the transformer it feeds.
- Neutral: with most of the load single-phase, the neutral carries the vector sum of the three phase currents, and triplen harmonics from electronic loads ride on top of it; size the neutral conductor and the star-point busbar to that calculated current, not to a token fraction of the phase conductor.
- Taps and feeder drop: specify the high-voltage taps so the loads sit inside their rated band at the supply voltage actually delivered, and remember feeder voltage drop stacks on top — the arithmetic is worked through in the voltage-drop calculation for single-phase fittings on a three-phase supply.
Which standard covers the unit #
A distribution transformer of this class sits under IEC 60076-24:2020, which applies to medium power transformers from 25 kVA up to 3150 kVA with a highest voltage for equipment up to 36 kV; the IEC 60076-20 series defines the energy-performance class that EU regulation makes mandatory in its market. Standards, connection rules and rating lists differ by country and edition, so confirm the required class, the impedance and the tap data with your local authority having jurisdiction and the transformer manufacturer's documentation before ordering.
Confirm the sizing under load #
After energization, take three readings at maximum demand: line current on each phase, neutral current, and phase-to-neutral voltage at the busbar. On a sound installation the line currents match the design split within a few percent, the neutral current sits near the calculated imbalance, the phase-to-neutral voltage holds inside the load band, and the winding temperature stabilizes within the nameplate rise. A phase running past its share, or a neutral that never settles, means the split is wrong or harmonics are loading the star point: rebalance and remeasure. A power analyser on the secondary side, clamp meters on each line and a clamp on the neutral bar give all three readings.
Opening the secondary compartment for these readings is energized work: NFPA 70E, 2024 edition, covers it and requires the shock and arc-flash risk assessment, protective equipment and a verified absence of voltage before anyone opens an enclosure. De-energize, lock out and verify first wherever the installation allows, and confirm the rules that apply with your authority having jurisdiction.
The decision #
Spreadable fleet at the example power factor with the heaviest phase at 420 kW: order the 1600 kVA unit and hold each phase under its third. One large load that cannot move: a single-phase transformer sized on its own kVA, after the utility confirms the connection. A fleet stuck uneven: the rating is three times the worst phase, even when that lands well above the balanced kVA — the hottest winding, not the average, is what heats.
Questions asked
How much spare capacity should the transformer carry for future loads?
Buy the margin your load forecast needs rather than a fixed percentage. The three-times rule already covers the imbalance you have today, but every extra kilowatt that lands on the heaviest phase costs three times its kVA in rating. If more circuits will go to one phase, recompute that phase before ordering and step up a frame if the product climbs.
Why does one heavy phase force a larger transformer than the total load suggests?
Because windings do not share load between themselves. Each winding is limited to one third of the nameplate kVA, so if winding L1 must carry 525 kVA, the nameplate has to be three times that, 1575 kVA, however light L2 and L3 run. The heaviest winding, not the average, decides the temperature rise.
What voltage do the single-phase loads actually see at the busbar?
The line-to-neutral value: the line voltage divided by the square root of three, about 239.6 V on this secondary before any load drop. If loads sit low, check the tap setting first and then the feeder voltage drop, which stacks on top of the transformer's own regulation; blaming the transformer rating alone misses both.
When is a single-phase transformer the better choice?
When the load cannot be spread: one large machine, or circuits fixed to one phase by the layout. A three-phase unit then idles two windings, and even on the high-voltage side a single-phase unit loads only two of the three feeder lines, which is what the utility connection check looks at. Size it on its own kVA and treat the switching and protection as a single-phase circuit.
How is the neutral current worked out before the transformer is energized?
As the vector sum of the three phase currents at their 120 degree displacements. For line currents I1, I2 and I3 the magnitude is sqrt(I1² + I2² + I3² − I1·I2 − I2·I3 − I3·I1), valid for balanced phase angles and before any triplen harmonics. Measure the real value after energization and size the conductor and star point to what the load fleet actually draws.