Sizing a precharge resistor for drive DC-link capacitance

Variable frequency drives Published 8 min read By Current Intel engineering team

Short answer

Sum the DC-link capacitance you will actually charge, then size the precharge resistor from initial current, pulse energy and the drives' idle draw. For a 22.2 V pack feeding three branches totalling about 984 µF, a 10 Ω pulse-rated resistor gives a 2.22 A initial pulse, 0.242 J and a bus within about 1.5 V of the pack, so the contactor closes across about two volts.

On this page
  1. The three numbers that pick the resistor
  2. Adding up the DC-link capacitance
  3. The worked example: three branches on one bus
  4. The quiescent draw that sets the endpoint
  5. Closing on measured voltage, not on a timer
  6. Pulse duty, retries and the discharge side
  7. The decision for each case
  8. Questions asked

Precharge sizing comes down to three numbers: the current the resistor lets through at first contact, the heat pulse the capacitance dumps into it, and the endpoint the drives' idle draw leaves across it. For the worked example in this article — a 22.2 V battery pack feeding three drive branches totalling about 984 µF of DC-link capacitance — a 10 Ω pulse-rated resistor gives a 2.22 A initial current, a 0.242 J charge pulse, and a bus that settles within about 1.5 V of the pack, so the main contactor closes across a volt or two instead of the full pack voltage. Close that contactor on a measured voltage difference, not on a timer's estimate. The sections below work the arithmetic and end with the decision for each bus size.

The three numbers that pick the resistor #

A precharge path is a resistor and a small relay in series, wired so it feeds the DC bus while the main contactor is still open. The relay closes first and charges the bus through the resistor; once the bus is within a volt or two of the source, the main contactor makes with almost no voltage across its contacts, then carries the operating current for the rest of the run. That resistor-and-bypass arrangement is the standard topology laid out in a DC-link precharge circuit design guide.

Three quantities size the resistor:

  • Initial current, I = V ÷ R. At first contact the discharged bus looks like a short, so the full pack voltage lands across the resistor.
  • Pulse energy, E = 0.5 × C × V². In an ideal charge from a stiff source, the resistor's heat per start equals the energy the capacitor stores.
  • Endpoint, V_bus = V_pack - I_q × R, where I_q is the drives' combined idle current. This sets the residual difference the main contactor must make across its contacts.

The branch operating ratings never enter the resistor calculation. In the example they are up to 80 A per drive, 240 A summed, through a single main contactor in the 300 A class; that current flows after closure and sizes the conductors, the contactor and the branch protection instead.

Branches hung on a common bus charge in parallel, so their capacitances add: C_total = 3 × 328 µF = 984 µF for the example hardware. A short production run of the same boards used about 400 µF per branch, so carry 1,200 µF as the upper design value, and confirm what your boards actually have before you order parts. Added input capacitance, a DC choke or snubber capacitance on the bus all add to the total, and hardware revisions can move it. If the value is undocumented, charge the bus through a known resistance, time the rise, and divide the measured time constant by that resistance to get the capacitance.

The worked example: three branches on one bus #

Treat the pack as a stiff source and the bus as discharged:

  • Initial current: I = V ÷ R = 22.2 V ÷ 10 Ω = 2.22 A. That is the first thing the relay contacts and the resistor see.
  • Pulse peak: P = V × I = 22.2 V × 2.22 A = 49.3 W, decaying as the bus charges.
  • Stored energy: E = 0.5 × C × V² = 0.5 × 0.000984 F × 492.84 V² = 0.242 J, which is also the resistor's heat per start; at the 1,200 µF upper design value it rises to 0.296 J.
  • Time constant: τ = R × C_total = 10 Ω × 984 µF = 9.84 ms, so holding the relay for 5τ, about 49 ms, takes an unloaded bus to roughly 99% of source voltage.

These are first-pass estimates for a discharged bus: a real pack sags under the pulse, wiring adds resistance, and the drives draw current the whole time. Check the final part choice against the drive and resistor documentation before you build.

The quiescent draw that sets the endpoint #

The drives are not passive loads during precharge: the example hardware idles near 1 W per branch once its control supply is up. At the pack voltage that is about 50 mA per branch, roughly 0.15 A for all three, and it flows through the resistor for as long as the relay stays closed. The bus therefore settles short of the source: V_drop = I_q × R = 0.15 A × 10 Ω = 1.5 V, leaving the endpoint near 20.7 V, or 20.5 V if you run the sum at a rounded 22 V. The resistor also holds (0.15 A)² × R ≈ 0.225 W of steady heat while it conducts.

The size of that drop is what rules out an oversized part. With 100 Ω, the same idle current would drop 15 V, stall the bus near 7 V, and hand the main contactor a 15 V closure — the inrush the precharge path exists to prevent — while stretching the ramp to a 98 ms time constant. The reselection rule falls straight out of the drop: R_max = the allowed residual volts ÷ I_q. For a 2 V budget and 0.15 A of idle draw that is about 13 Ω, so the worked part sits under the ceiling with margin. One caution: a drive's idle draw behaves closer to constant power than constant current, so its current climbs as the bus falls — measure the loaded endpoint rather than trusting the model at low voltage.

Closing on measured voltage, not on a timer #

The 5τ figure assumes a fixed source and no load. Real packs sag under the charge pulse, the drives' startup draw is not constant, and any added capacitance stretches the ramp — so make the closure decision on the measured difference. Read voltage on both sides of the open main contactor and close when the difference is within two volts. At the worked residual, the closure event only has to move 0.5 × C × (1.7 V)² ≈ 1.4 mJ, about a thousand times less than the charge pulse, so the contacts make with no meaningful arc energy.

Symptom during precharge Likely mechanism Next measurement
Bus rises, then stalls well below the source Idle current times resistance eats the difference Compare the stall point with source volts minus idle amps times resistance
Bus stays near zero Relay not making, resistor open, or a branch loading the bus Check the relay command and resistor continuity, then each branch's current
Bus rises and collapses repeatedly A controller cycling its own startup supply Capture bus voltage and current together
Crack or flash when the main contactor closes Endpoint left too high: resistance too large or ramp cut short Read the difference across the contactor immediately before closing
Resistor runs hot after a failed start Conduction stretched out or attempts stacked Check conduction time and retry spacing against the resistor's pulse curve

The main contactor needs its own make-and-carry rating for the operating current, and switching a drive's power input through a contactor carries manual-side rules of its own — input versus output contactors covers what those manuals allow on each side of the drive.

Pulse duty, retries and the discharge side #

A resistor marked 3 W continuous is not automatically good for a 49.3 W pulse, even for a few tens of milliseconds — pulse capability is its own rating, published as a pulse-energy or overload curve by the resistor maker. The worked pulse peaks at 49.3 W and decays with the same 9.84 ms time constant, and the total heat is roughly a quarter joule per start plus about 0.225 W while the relay holds. Pick a type sold for pulse duty — wirewound or thick-film power parts are the usual candidates — and give the part time to cool between attempts, because back-to-back starts stack pulses even when each one looks clean.

Open the main contactor and the bus keeps the charge it just received. Size a bleed resistor across the bus for a defined decay: IEC 61800-5-1, 2021 edition, the product-safety standard for adjustable-speed electrical drive systems, governs how quickly a drive's DC link must shed hazardous residual voltage, which is why drive manuals publish a wait before you open the cabinet — confirm the requirement that applies to your installation with the authority having jurisdiction and the equipment documentation. Before touching that bus, de-energize, wait the stated time, and verify absence of voltage with a meter rated for the installation.

The decision for each case #

  • Single branch of the example hardware, about 328 µF: the worked resistor stands. Stored energy falls to 0.081 J and the time constant to 3.3 ms; the endpoint does not move, because it is set by idle draw and resistance alone.
  • The three-branch bus of the worked example: the pick stands — 2.22 A initial, 49.3 W pulse peak, 0.242 J per start, bus settling near 20.7 V, contactor closed at a measured difference under two volts.
  • The upper design value of 1,200 µF: same initial current, 0.296 J and a 12 ms time constant; still within reach of a small pulse-rated part, but re-verify its curve.
  • A pack that charges well above nominal, or drives with heavier idle draw: rerun all three numbers at the worst case — pulse at full-charge voltage, endpoint at measured idle current — and reselect. The ordering that works: fix the endpoint ceiling first, resistance no more than the allowed residual volts divided by the total idle amps; then confirm the pulse curve at the highest source voltage; then confirm the hold time.

Questions asked

Can the precharge resistor stay in the circuit after the contactor closes?

No. The resistor path is sized for the charge pulse only. Carrying even one 80 A branch would demand dissipation in the tens of kilowatts, about 64 kW for the example rating, and burn the part open. The main contactor carries the operating current from closure onward, and the small relay opens the resistor path once the bus is charged, leaving the resistor idle until the next start.

How long should the precharge relay hold before the contactor closes?

Hold at least five time constants, about 50 ms for the worked bus; 150 to 200 ms total adds margin for pack sag, added capacitance or a slow relay. Better, hold until the measured difference across the main contactor is under about 2 V and use the timer only as a backstop.

Do I need to redo the calculation at full charge voltage?

Yes. Current scales with voltage, and pulse power and stored energy scale with voltage squared. If the worked pack charges to 25.2 V full, six lithium cells at 4.2 V each, the initial pulse becomes about 2.52 A and 63.5 W and the capacitor energy about 0.312 J, roughly 29 percent more heat per start. Check the resistor's pulse curve at those full-charge figures before you finalize the part.

What if the drives draw more than the example's idle power?

Then the endpoint moves. Idle current times resistance is how far the bus settles short: at 5 W per branch, about 0.68 A for three branches, the worked resistor would stall the bus roughly 7 V below the pack. Reselect so idle current times resistance stays within about 2 V, roughly 3 Ω here, which raises the initial pulse to about 7.4 A and 164 W, so recheck the pulse curve too.

Keep reading

  • Explainer

    DC bus sharing on servo drives: one supply, one filter group

    A shared DC bus collapses the AC side to exactly one protected mains supply for the whole network, caps drives at six per passive line filter, and limits total motor cable behind that filter as PWM frequency rises. Size the single breaker and filter on the group's continuous current, not the nameplate sum.

    Variable frequency drives

  • Selection guide

    Line reactor sizing for servo drives on 240 V single phase

    Size a servo-drive line reactor from the drives' documented single-phase input currents, never from motor kilowatts. A 3 kW servo group on 240 V has a 12.5 A ideal floor but draws near 23 A in practice, so each machine branch takes a 25 A, 3 % reactor with the maker's documented two-coil single-phase connection.

    Variable frequency drives

  • Selection guide

    Sizing a VFD for a three-phase motor on single-phase input

    On single-phase input, size the drive's continuous output current at no less than twice the motor nameplate full-load amps when the drive's 50% derating applies, and feed it from a branch circuit sized to 125% of the drive's published single-phase input current — never from the ideal wattage estimate. For a 10 hp, 208 V motor that means a drive rated at least 61.6 A output.

    Variable frequency drives