Spindle motor overload fault: drive, motor or the control?

Variable frequency drives Published 8 min read By Current Intel engineering team

Short answer

The display that raised the alarm decides the first test; OL1 and OL2 on the spindle drive are its own current-time overload calculations: OL2 during acceleration points at ramp time and mechanical drag, OL1 at speed points at running load. A motor-overload message on the CNC while the drive is clean comes from builder or control logic, and you trace its diagnostic bit, not the motor. One winding-resistance reading decides nothing; captured output current at the fault does.

On this page
  1. First decision: who raised the alarm?
  2. What OL1 and OL2 actually are
  3. The CNC alarm with a quiet drive
  4. Why the ohm reading cannot decide it
  5. Capture the current at the fault instant
  6. Worked example: ramp time against acceleration torque
  7. The decision, case by case
  8. Questions asked

The display that shows the alarm decides the first test. If the spindle drive's own display shows OL1 or OL2, the drive's electronic thermal calculation tripped on measured output current, and the first suspects are load, ramp time and mechanics, not the motor. If the CNC screen shows a motor-overload message while the drive display stays normal and its fault history adds nothing, that message was generated by control or machine-builder logic, and you trace the signal that sets it. Neither case is decided by a winding-resistance reading: 1.8 ohms through about 12 feet of cable is neither a pass nor a fail without the motor's specified line-to-line value. The decisive quantity is output current captured while the fault is being made.

First decision: who raised the alarm? #

Work through this list before anything is opened or unplugged:

  • Read the drive display at the moment the machine stops. An active OL1 or OL2 means the drive's protection operated; write down the code and what the machine was doing: accelerating, at speed, in a gear change, during an axis move.
  • If the drive display is normal when the CNC alarms, open the drive's fault history. A new entry at that moment is still a drive event; no new entry means the alarm was made somewhere else.
  • Treat the two records as separate evidence. On this machine the day's count was three motor-overload trips and one inverter-overload trip, and a later look showed four and one. A history that stores counts but no event times cannot be matched to a CNC alarm, and nothing in it says when the fourth event happened or what the cycle was doing at the time.

What OL1 and OL2 actually are #

On this drive the manual's fault table defines OL2 as output current above the inverter overload level, with reduce load and extend acceleration time as the corrective actions, and OL1 as output current above the motor overload level, with reduce load as the action. Codes are model-specific: read the table in your drive's own manual, because the same letters carry other meanings on other series.

The timing tells you where to look:

  • OL2 while the spindle spins up puts the problem in the acceleration interval. Bringing rotor, pulleys, chuck and workpiece up to speed takes torque on top of friction, and a short ramp, a binding gear train or a brake that drags all raise the current there.
  • OL1 after the spindle has reached speed puts it in the running interval: cutting demand, gear selection, accumulated load. OL1 is a current-and-time calculation, not a winding-temperature measurement and not proof of a defective motor. A healthy motor driving too much load trips it exactly like a degraded one drawing extra current.

An instantaneous overcurrent code is a different failure: a short or a drive output-stage problem fires within milliseconds of the first pulses, not after seconds of moderate excess. That path is covered in VFD OC1 overcurrent fault during acceleration causes.

The CNC alarm with a quiet drive #

If the control alarms and the drive logs nothing at that moment, the message came from builder or control logic, and pulling the spindle motor is the wrong move. A control can synthesize a motor-overload message from a drive-fault relay that never closed, a motor thermostat contact, an e-stop chain state, or logic that compares spindle feedback with the command. The reported text, PLC: 4002 motor overload, names the control's PLC as its origin, not the drive.

Trace it: with the alarm active, open the control's diagnostic status display, find the bit or input that sets the message, then follow what feeds it — a terminal, a relay, a timer. If the ladder is not available, the alarm number is what the machine builder needs to identify the source. Two observations from this machine sharpen the direction:

  • The message appeared during gear changes and axis rapids with the drive display normal, conditions that have nothing to do with spindle current.
  • It cleared temporarily when connectors were unplugged and replugged, then returned. That is the signature of an intermittent contact or relay in the alarm chain, a family worked through in why an intermittent spindle motor overload clears on reset.

One test settles ownership: if the CNC alarm still appears with the spindle motor disconnected from the drive, the alarm is not reporting spindle current at all, and the search belongs in the control's input chain.

Why the ohm reading cannot decide it #

Before opening the drive cover or a terminal box, lock out the feeder and test for absence of voltage, and honor the discharge time the drive manual states for its DC bus, which holds charge after power-off.

The reported measurement, 1.8 ohms from the drive terminals through roughly 12 feet of cable and a winding path, fails as a verdict for three reasons. There is no specified line-to-line value for this motor to compare against, and a figure from an external reference is not a specification. At this level the meter's lead resistance and low-ohm accuracy are the same order as the differences that matter, so zero the leads on the instrument first. And copper moves with temperature, about 0.4 % per degree Celsius, so a winding 25 °C warmer reads roughly 10 % higher than the same winding cold.

What the reading can do: compare the three line-to-line pairs measured directly at the motor terminals, leads zeroed. The three should agree; a pair that stands out from the other two is the finding, whatever the absolute number. For a real verdict on the windings, the test that belongs here is insulation resistance to the frame with a megohmmeter, and even that has its limits, as why a motor meggers good but trips the breaker on start shows. Resistance balance and insulation resistance together still do not measure load; only current capture does.

Capture the current at the fault instant #

  • First choice: the drive's own output-current monitor on its display. It is the same signal the overload calculation integrates, so it is the number that tripped. Read it while the fault is being made, and check whether the manual says the drive freezes output current in its trip record.
  • Second check: a true-RMS clamp meter specified for drive output, on one output conductor at a time. A clamp around the whole cable reads approximately zero, because the three conductor currents cancel.
  • Never put a handheld ammeter in series with the drive output; the switched waveform and the voltage make it the wrong instrument in the wrong place.
  • Do not judge motor load from the input side. The rectifier draws peaky, harmonic-rich current, so input current runs above output current at the same load: one drive documented at 43 A rated input and 42 A rated output read 44.5 A out with 60 to 64 A in during a field check.
  • The load-meter terminals are not a place for a simple ammeter. They carry a scaled analog meter signal, and the manual states the signal and its scaling, so read them with a DC voltmeter and convert. That is a workable substitute for the missing load meter on this machine.

Worked example: ramp time against acceleration torque #

Hypothetical numbers, to show how far the ramp setting moves the current in the interval that produced OL2. Example motor nameplate: 7.5 kW, 400 V three-phase, 50 Hz, 1500 rpm, 14.5 A. Example combined inertia of rotor, pulley, chuck and workpiece: J = 0.35 kg·m².

The arithmetic:

  • Speed change: ω = 2π × 1500 / 60 = 157.1 rad/s.
  • Ramp 2.0 s: α = 157.1 / 2.0 = 78.5 rad/s², so acceleration torque T = J × α = 0.35 × 78.5 = 27.5 N·m.
  • Rated torque: 7500 W / 157.1 rad/s = 47.7 N·m. The ramp alone asks 27.5 / 47.7, about 58 % of rated torque, before any friction.
  • Ramp 4.0 s: α = 157.1 / 4.0 = 39.3 rad/s², T = 0.35 × 39.3 = 13.7 N·m, about 29 % of rated.

Doubling the ramp time halves the acceleration torque, and that is the whole content of the fault table's extend-acceleration-time action. The decision: stretch the ramp until the acceleration share sits under about a third of rated torque, confirm on the current monitor, and if OL2 still trips with the gear train verified free by hand under lockout, stop adjusting. The fault is then in the drive's current measurement or output stage: that drive goes to the service bench, and the motor is not the suspect.

The decision, case by case #

  1. OL2 while accelerating: the drive's own calculation on a real load. Extend the ramp per the worked example, confirm the brake releases and the gear train turns freely, and re-test. Only a trip that survives those steps condemns the drive.
  2. OL1 at speed or in the cut: a running-load problem. Watch the output-current monitor through the cut, correct cutting parameters and gear selection, and verify the drive's motor-data entry against the nameplate, because the OL1 level is computed from it. When current genuinely exceeds the motor's rating with the mechanics free, the motor goes to winding tests, not back into service. The cutting-only variant is covered in why a spindle VFD trips motor overload only during cutting.
  3. CNC overload message with a quiet drive: a control-chain problem. Trace the diagnostic bit to its contact, reseat or replace what you find, and prove it by reproducing the alarm while watching that bit change. The spindle motor stays in service until a drive-side event is captured.
  4. Conflicting history counts: not evidence yet. Time-correlate the next event with a person at each display, and only then assign it to a device.

The drive, the motor and the control each leave a different signature: a drive thermal code on a live display, a CNC message with an unchanged history, a resistance reading that agrees or disagrees with its own pairs. Read the signature first; the meter comes second.

Questions asked

The drive shows no fault with the motor disconnected. Doesn't that clear the drive?

It proves the drive powers up and its control is alive, no more. An overload trip needs current through a load, so an unloaded drive cannot produce OL1 or OL2 in the first place. A drive with a failing output stage usually declares itself with an instantaneous overcurrent or ground-fault code within the first output pulses, not with a clean unloaded power-up. Reconnect the motor and run while watching the output-current monitor: the trip condition only exists with current flowing.

Can I raise the drive's overload level so the spindle keeps running?

No. The electronic thermal overload is the motor's protection, and its level is computed from the motor rated current entered in the drive. Raising the level or stretching the trip time removes that protection while the real load problem stays. First verify the rated-current entry against the motor nameplate, since a wrong value trips early or late. Then reduce the actual load or repair the mechanics that create it.

How do I time-match a CNC alarm to a drive fault when the history has no timestamps?

Run the cycle with one person at the drive display and one at the control, or film both screens together, and note the machine command active when the message appears. Record the history count before and after each run: a count that increments at the moment the CNC alarms makes it a drive event, while an unchanged count proves the control generated the message. Repeat across gear changes and axis moves, because the pattern across conditions is the real evidence.

Why did the alarm clear after reseating connectors and then come back?

Because unplugging and replugging remade the contact for a while. An alarm that responds to connector disturbance lives in wiring, terminals or a relay, not in a motor winding, since windings do not heal when plugs are moved. That behavior narrows the search to the alarm's input chain: the drive-fault relay, the terminal strip and the control's input card. Reseating is a diagnostic clue, never the repair; find the contact with the alarm bit active and replace the part.

Keep reading

  • Troubleshooting

    VFD output phase loss fault: tracing the broken phase

    An output phase loss fault means the drive's current monitor sees one of the three phases at its U, V and W terminals drawing no current or far less than the others, so the break is almost always between the drive and the motor windings: the cable, a termination, output fusing, a contactor pole or the winding itself. Lock out, compare the three line-to-line resistances at both ends, and the readings name the broken phase.

    Variable frequency drives

  • Explainer

    Why a VFD motor overload current setting takes nameplate FLA

    Enter the motor's nameplate full-load current — for a 2 hp, 460 V motor, 3.4 A — in every drive field that asks for motor rated or overload current. The drive's thermal model applies its own margin and trip curve on top, so pre-multiplying by 125% stacks a second margin and pushes the effective pickup near 156% of nameplate. NEC 430.32's 125% and 115% figures cap separate overload devices; they are not data-entry instructions.

    Variable frequency drives

  • Troubleshooting

    Running two motors on one VFD with output contactors

    One VFD can run a 3 hp motor and a 1/2 hp motor one at a time: size the drive for the larger motor, connect each through its own interlocked output contactor, change over only with the drive disabled, and give each motor its own overload relay set from its own full-load current. If both motors must ever run together, use two drives.

    Variable frequency drives