Comparison
Step-up transformer losses on a VFD single-phase input
Short answer
Yes. A step-up transformer draws a fixed core loss every hour it is energized, about 2 percent of its rating on a generic dry-type, plus a load loss of roughly 2 to 5 percent of the power it carries. On a 20 kVA unit that is about 400 W around the clock; the better arrangement is usually a manufacturer-approved low-voltage-class VFD on the motor's 38 A connection, with no transformer at all.

On this page
- What the transformer changes and what it does not
- Core loss and load loss: the two numbers to ask for
- The two arrangements side by side
- Worked example: 400 W of core loss on a 20 kVA transformer left energized all year
- Which current sizes each connection
- Approval, derating and the phase-loss trip
- The decision for each case
- Questions asked
Yes — a step-up transformer draws power on its own, every hour the panel is energized, whether or not the motor turns. It carries two separate losses: a fixed core loss whenever the winding is energized, and a load loss that grows with the current, together roughly 2 to 5 percent of the power it passes on a generic dry-type design. It also does something the motor-shop talk sometimes skips: it does not create a third phase. Stepping 220 V single-phase up to 440 V leaves 440 V single-phase at the secondary, so the drive must be approved for single-phase input either way. That fact, plus the around-the-clock idle loss, decides between a low-voltage-class drive on the motor's low-voltage connection and the transformer-plus-high-voltage-drive arrangement — and for most machines that idle, the transformer is the arrangement to delete.
What the transformer changes and what it does not #
An ordinary single-phase transformer changes voltage and current and nothing else. Feed it the single-phase supply and it delivers the same single phase at twice the voltage: the same phase count, half the current at the secondary terminals. The variable frequency drive — not the transformer — is what rectifies the input and synthesizes the three phases the motor sees, in both arrangements.
The whole motor load still comes out of the single-phase service. The nameplate currents confirm it is the same machine on either connection: √3 × the supply voltage × 38 A and √3 × the high-voltage connection's rating × 19 A both come to about 14.5 kVA. Moving the motor to its high-voltage connection halves the current in the motor leads, which helps on a long conductor run, but the energy the machine consumes does not change, and every watt of it still flows in through the supply side.
Core loss and load loss: the two numbers to ask for #
Transformer losses split into two groups, and only one of them stops when the motor stops.
Core loss — also called no-load or excitation loss — comes from hysteresis and eddy currents in the laminations. It sits at a nearly constant level whenever the winding is energized, set mainly by voltage, frequency and core design; a fair planning figure for a generic ventilated dry-type is about 2 percent of rating. Energy-efficient designs cut it hard: the 2016 U.S. Department of Energy efficiency levels for three-phase dry-type distribution transformers run from 97.89 percent upward as the kVA class grows, and manufacturer design guides treat low core loss as the headline feature of those units.
Load loss is the I²R heating of the windings plus stray and eddy losses, and it rises with the square of the current. Total loss at rated load commonly lands between 2 and 5 percent of throughput, nearer the 5 percent end for a unit whose nameplate makes no energy-efficient claim.
That band is for planning, not purchasing. The manufacturer's test report, prepared under IEEE C57.12.01 for dry-type distribution transformers, lists the actual no-load loss and load loss in watts for your serial number; an efficiency percentage on a label cannot be split back into those two numbers.
The two arrangements side by side #
The real choice is not transformer versus no transformer on habit; it is which power path the drive manufacturer actually approves. Both paths put a drive between the supply and the motor — in both, the drive makes the three phases.
| Criterion | Low-voltage drive, no transformer | Step-up transformer plus the existing high-voltage drive |
|---|---|---|
| Power path | 220 V single-phase supply into the drive; the drive outputs three phase to the motor | the single-phase supply to the transformer, 440 V single-phase into the drive, three phase to the motor |
| Motor connection | low-voltage connection, 38 A nameplate current | high-voltage connection, 19 A nameplate current |
| Loss while the machine sits idle | none added — there is no transformer | the transformer's full core loss, every energized hour |
| Loss while the motor runs | drive and motor losses only | drive and motor losses plus the transformer's load loss (2-5% of throughput) |
| Extra equipment to install and maintain | none beyond the drive and its input protection | transformer, its overcurrent protection, conductors and switching |
| Condition that must be documented | the manufacturer lists the drive for single-phase input at the 38 A output | the manufacturer lists the existing drive for single-phase input at the 19 A output |
| Where each wins | new builds, and machines that idle more than they run | a verified single-phase-approved high-voltage drive on a machine that runs long shifts |
Worked example: 400 W of core loss on a 20 kVA transformer left energized all year #
Inputs. A 20 kVA dry-type step-up transformer — a sizing assumption for this service, not a measured nameplate. A no-load loss of 2 percent of rating — the working assumption for a generic non-energy-efficient dry-type; the real figure comes from the test report. Energized 8,760 hours a year — the panel is left on around the clock.
Rule. No-load watts equal the loss fraction times the rated VA. Idle energy in kilowatt-hours equals watts times energized hours, divided by 1,000.
Arithmetic. 0.02 × 20,000 VA = 400 W of core loss, drawn steadily. 400 W × 8,760 h = 3,504,000 Wh; ÷ 1,000 = 3,504 kWh per year, spent before the motor contributes anything.
Result. About 3,500 kWh a year keeping iron magnetized. Compare that with the transformer's work: at the motor's full 14.5 kVA throughput, 2 to 5 percent is 290 to 725 W — the same order as the 400 W the idling unit burns standing still.
Decision. When idle hours are on the same order as running hours, the core loss is the larger half of the transformer's energy bill — switch the transformer with the machine, or better, take it out of the design entirely. The transformer only pays its way energized when the machine runs most of the hours the panel is on.
Which current sizes each connection #
Neither nameplate current sizes the incoming path — the drive's published single-phase input current does. It is listed separately from the three-phase figure, and it is higher, roughly in proportion to the single-phase derating, because the rectifier and DC-link capacitors carry the same power through fewer line half-cycles. Which frame survives that derating at your motor's load is worked through in sizing a VFD for a three-phase motor on single-phase input. NFPA 70, the National Electrical Code, 2023 edition, requires adjustable-speed drive input conductors to have an ampacity of at least 125 percent of the drive's rated input current in the article's adjustable-speed drive provisions; confirm the exact section and any local amendments with your authority having jurisdiction and the drive documentation.
An idealized check shows why the primary side deserves attention: the motor's 14.5 kVA on a 220 V single-phase primary is S = V × I, so 14,480 VA ÷ 220 V ≈ 66 A, and the real RMS input runs higher because a rectifier draws current in pulses rather than a smooth sine. The transformer's kVA rating must cover the drive's input kVA with margin for that waveform, not just the motor's nameplate. The same input-kVA method, worked on a smaller machine, is in whether a 6 kVA transformer is enough for a 5 hp motor drive.
Approval, derating and the phase-loss trip #
The common screening rule doubles the drive's horsepower rating on single-phase input — a 30 hp frame for this 15 hp motor. Treat it as a first filter, nothing more: the continuous and overload output current actually permitted on single-phase input is whatever the manual states for that exact model, and some drives are simply not permitted single-phase input at any frame size. What that manufacturer listing means, and why it is not optional, is covered in why a variable speed drive needs single-phase motor approval.
The phase-loss trip gets its own word. Many drives at the higher voltage class monitor the input for a missing phase, and a three-phase-only drive will trip on single-phase — sometimes behind a setting that looks changeable. That trip is the drive reporting an unsupported input configuration. The fix is a drive whose manufacturer documents single-phase operation at your required output current, with its protective functions kept exactly as the instructions set them for the approved application. A parameter change that silences the trip does not make a three-phase-only drive single-phase rated; it leaves the rectifier and DC-link capacitors loaded in a way their ratings were never checked for.
The decision for each case #
Before you open the panel to read a nameplate or move a motor lead, de-energize the equipment, lock out and verify absence of voltage at the point of work; NFPA 70E, 2024 edition, defines that as the electrically safe work condition, and nothing here is a go-ahead for live work.
Building new, or buying a drive anyway: take the low-voltage-class drive the manufacturer approves for single-phase input at the low-voltage connection's rated current, feed it from the supply, and leave the transformer out. You delete the around-the-clock core loss, one voltage class of gear and the transformer's protection from the design — and the single-phase service was carrying the whole load regardless.
Keeping the high-voltage drive you already own: workable only if its manual documents single-phase input at the continuous output the motor needs on the high-voltage connection. Then size the transformer, its protection and the supply-side conductors on the drive's published single-phase input current with the code's conductor margin, and switch the transformer with the machine once inrush and the drive's power-cycling limits are checked — energizing the transformer first and starting the load a few seconds later, so inrush and locked-rotor current never stack, is exactly the sequencing to verify against the drive manual.
Any other case: if the only way to make the existing drive accept the input is to quiet its phase-loss protection, the answer is no — replace the drive, not the protection.
Questions asked
Does a transformer draw power when the motor is off?
Yes, for as long as it is energized. Core loss from hysteresis and eddy currents flows whether or not a load is connected; on the worked example, 2 percent of a 20 kVA rating is 400 W every hour, about 3,500 kWh a year if the panel stays on. Your unit's real figure is on its test report, not its efficiency label.
Can a transformer convert single-phase supply to three-phase?
No. It changes voltage only: 220 V single-phase in, 440 V single-phase out. The drive creates the three-phase motor supply in either arrangement, so whichever drive you pick must be documented by its manufacturer for single-phase input at the output current your motor demands.
How big should the transformer be for a drive load?
Rate it from the drive's published single-phase input current, not the motor's nameplate current. A single-phase-fed drive draws well more than the motor load, because the drive itself is derated and its rectifier pulls pulsed current rather than a smooth sine. Cover that input kVA with margin, and keep the transformer's own protection sized for its inrush.
Is it worth switching the transformer off between runs?
When the machine idles more than it runs, yes: the fixed core loss then costs more energy than the load loss the transformer adds while working. Before making the switching routine, confirm the drive tolerates power cycling at that interval and that the switching device handles transformer inrush.
Does running the motor on its high-voltage connection halve its energy use?
No. The load is identical either way: √3 × the supply voltage × 38 A and √3 × the high-voltage connection's rating × 19 A both come to about 14.5 kVA. The higher voltage only halves the current in the motor leads, which helps conductor size on long runs; every watt still arrives through the single-phase supply.

